Installation, Operating and Maintenance Instructions 

 

 

 

      3/7

 

for Alarm Switchgear AS1-M

 

 

 

 

 

 

 

 

 

 

 

 

2331.827/03-EN

 

 

 

 

Date: 2015/10/04 

1.  Technical Description and Field of Application

 

 

KSB Alarm Switchgear AS1-M

 

 

The AS1-M alarm switchgear, used in conjunction with the M 1 (K) alarm contactor, 
can report impermissibly high water levels.

 

 

The M 1 (K) alarm contactor has a connection cable with a jack plug for connecting to 
the AS1-M alarm switchgear.

 

 

The AS1-M alarm switchgear is fitted with a SCHUKO plug that is inserted into a  
230 V AC SCHUKO socket (type C+E). In the event of a power failure, the operative 
function is maintained for approximately 5 hours via a 9 V NiMH battery. The 9 V 
NiMH battery is supplied fully charged. During normal mains-powered operation a 
permanent trickle charge is provided (refer to Section 2 of these instructions: 
Excessive Discharging).

 

 

A switch on the underside of the housing can be used to turn the AS1-M alarm 
switchgear on and off. Pressing the switch in turns the device off; releasing the switch 
turns the device on.

 

 

When the AS1-M alarm switchgear is turned on, an alarm is emitted as soon as the 
liquid level raises the float switch of the M 1 (K) alarm contactor. The alarm stops as 
soon as the liquid level causes the float switch to travel downward again.

 

 

The AS1-M alarm switchgear features a monitored jack socket so that when the 
device is turned on and the jack plug is pulled out, an alarm is also triggered. No alarm 
is triggered, however, in the event of a broken wire in the connection cable.

 

 

 

Technical data

 

Mains voltage 

 

 

AC 230 V ±10 %/50 - 60 Hz 

Power input   

 

 

Approx. 3 VA 

Rechargeable battery 

9 V NiMH battery; provided with a permanent trickle 
charge during mains operation 

Service life of battery 

Approx. 7 years but only if excessive discharging is 
avoided 

No-load voltage 

 

 

DC 9 V 

Housing 

Upper section made from ABS; lower section made 
from PC/ABS with integrated SCHUKO plug, 
dimensions excluding plug: 120 x 65 x 40 mm 

Enclosure 

 

 

 

IP 20; for interior application only 

Temperature range  

 

0  C to +40 °C 

Altitude requirements 

 

Max. of 1,000 m above sea level 

Sound pressure level of buzzer  Approx. 95 dB at a distance of 0.1 m 

 
 

Содержание AS1-M

Страница 1: ...al must be handed to the fitter installer operator service personnel of our products together with all other relevant documentation and user information The manual must be carefully stored in a safe p...

Страница 2: ...of Application Page 3 2 Conditions for Safe Application Page 5 3 Installation Connection Commissioning and Maintenance Governing Rules and Regulations Page 5 4 Installing the AS1 M Alarm Switchgear Pa...

Страница 3: ...n turns the device off releasing the switch turns the device on When the AS1 M alarm switchgear is turned on an alarm is emitted as soon as the liquid level raises the float switch of the M 1 K alarm...

Страница 4: ...and followed without exception at all times Applications outside the envelope of the key technical data specified are prohibited This brochure must have been read and understood by the qualified speci...

Страница 5: ...y on the AS1 M Alarm Switchgear The AS1 M alarm switchgear must not be used in areas in which the device could be subjected to moisture and humidity Exclusion of Potentially Explosive Atmospheres The...

Страница 6: ...connection must be checked and verified a second time before commissioning is carried out A further check must also be performed to ensure that dangerous or hazardous situations cannot arise as a resu...

Страница 7: ...dards requirements local regulations and special circumstances and proceed accordingly prior to performing maintenance work 8 Repair Any opening of the alarm switchgear and alarm contactor and all rep...

Страница 8: ...tr 11 67466 Lambrecht declares that the following product which is new and designed for use in dry rooms Alarm Switchgear AS1 M complies with the Directives 2006 95 EC low voltage and 2004 108 EC EMC...

Отзывы: