Installation, Operating and Maintenance Instructions 

 

 

 

      5/7

 

for Alarm Switchgear AS1-M

 

 

 

 

 

 

 

 

 

 

 

 

2331.827/03-EN

 

 

 

 

Date: 2015/10/04 

2.  Conditions for Safe Application

 

 

Nominal Power Supply

 

Mains voltage: AC 230 V ±10 %/50 - 60 Hz

 

All limits and restrictions defined for the voltage source must be upheld.

 

 

Chemical and Mechanical Resistance

 

Before the AS1-M alarm switchgear is deployed, it must be ensured that the materials 
comprising the switchgear resist the ambient conditions present in the room in which the 
device will be installed as well as sufficiently resist all other external influences from a 
chemical and mechanical compatibility perspective.

 

In there is any doubt, an expert must be consulted before the device is deployed. The 
product must not be used until final clarification has been made.

 

 

Exclusion of Damp and Moist Rooms

 

The AS1-M alarm switchgear must 

not

 be installed in damp and moist rooms.

 

 

Exclusion of Rooms That Can Become Flooded

 

The AS1-M alarm switchgear must 

not

 be installed in rooms that can become flooded.

 

 

Exclusion of the Effects of Moisture and Humidity on the AS1-M Alarm Switchgear

 

The AS1-M alarm switchgear must not be used in areas in which the device could be 
subjected to moisture and humidity.

 

 

Exclusion of Potentially Explosive Atmospheres

 

The AS1-M alarm switchgear

 

and the M 1 (K) alarm contactor

 must not be installed in 

potentially explosive atmospheres.

 

 

Excessive Discharging

 

Not using the AS1-M alarm switchgear for an extended period of time can cause the built-
in rechargeable battery to become excessively discharged. This, in turn, greatly reduces 
the service life of the battery, so that the device, when subsequently used, may not emit 
an alarm in the event of a power failure.

 

 

 

3.  Installation, Connection, Commissioning and Maintenance, Governing Rules and 

Regulations

 

 

The AS1-M alarm switchgear and M 1 (K) alarm contactor must be installed, 
connected, commissioned and maintained in full compliance with all information and 
documentation provided, and the instructions contained therein must be observed and 
followed without exception.

 

 

Installation, connection, commissioning and maintenance personnel must also 
familiarise themselves with all applicable standards, requirements, local 
regulations and special circumstances and act accordingly.

 

The AS1-M alarm switchgear must be installed in compliance with VDE 

Содержание AS1-M

Страница 1: ...al must be handed to the fitter installer operator service personnel of our products together with all other relevant documentation and user information The manual must be carefully stored in a safe p...

Страница 2: ...of Application Page 3 2 Conditions for Safe Application Page 5 3 Installation Connection Commissioning and Maintenance Governing Rules and Regulations Page 5 4 Installing the AS1 M Alarm Switchgear Pa...

Страница 3: ...n turns the device off releasing the switch turns the device on When the AS1 M alarm switchgear is turned on an alarm is emitted as soon as the liquid level raises the float switch of the M 1 K alarm...

Страница 4: ...and followed without exception at all times Applications outside the envelope of the key technical data specified are prohibited This brochure must have been read and understood by the qualified speci...

Страница 5: ...y on the AS1 M Alarm Switchgear The AS1 M alarm switchgear must not be used in areas in which the device could be subjected to moisture and humidity Exclusion of Potentially Explosive Atmospheres The...

Страница 6: ...connection must be checked and verified a second time before commissioning is carried out A further check must also be performed to ensure that dangerous or hazardous situations cannot arise as a resu...

Страница 7: ...dards requirements local regulations and special circumstances and proceed accordingly prior to performing maintenance work 8 Repair Any opening of the alarm switchgear and alarm contactor and all rep...

Страница 8: ...tr 11 67466 Lambrecht declares that the following product which is new and designed for use in dry rooms Alarm Switchgear AS1 M complies with the Directives 2006 95 EC low voltage and 2004 108 EC EMC...

Отзывы: