5 Installation at Site
23 of 60
Ama-Drainer 4../5..
5.5.4 Connection to power supply
DANGER
Electrical connection work by unqualified personnel
Danger of death from electric shock!
▷
Always have the electrical connections installed by a trained and qualified
electrician.
▷
Observe regulations IEC 60364.
DANGER
Operating a pump set that has not been fully connected
Explosion hazard!
Damage to the pump set!
▷
Never start up a pump set with power cables that have not been fully
connected or non-operational monitoring devices.
WARNING
Incorrect connection to the mains
Damage to the mains network, short circuit!
▷
Observe the technical specifications of the local energy supply companies.
CAUTION
Flow-induced motion
Damage to the power cable!
▷
Run the power cable upwards without slack.
CAUTION
Improper routing of power cable
Damage to the power cables!
▷
Never move the power cables at temperatures below - 25
℃
.
▷
Never kink or crush the power cables.
▷
Never lift the pump set by the power cables.
▷
Adjust the length of the power cables to the site requirements.
For the electrical connection observe the circuit diagrams (
in the Annex and the information for planning the control system .
The pump set is supplied complete with connection cables. Always use all cables
provided and connect all marked cores of the control cable.
1. Run the power cable upwards without slack and fasten it.
2. Only remove the protective caps from the power cable immediately before
connection.
3. If necessary, adjust the length of the power cable to the site requirements.
4. After shortening the cable, correctly re-affix the markings of the individual cores
at the cable end.
5.6 Checking the direction of rotation
Ama-Drainer SE and NE
The direction of rotation of pumps with single-phase AC motors need not be
checked.