Checking the usage

Intended use

Magnetic relief valve, open when de-energized, for 
the monitoring of gas valves for tightness used in 
conjunction with a visual discharge unit. For purging 
excess or leakage gas.

This function is only guaranteed when used within the 

specified limits – see page 7 (Technical data). Any 
other use is considered as non-compliant.

Type code

Code

 Description

VAN

Magnetic relief valve

 

Size: 1 

2

T

T-product

0 – 50

Nominal size 

DN

N

Rp internal thread 

NPT internal thread

N

Quick opening, quick closing

W

Mains voltage: 24 V DC 

100 V AC, 50/60 Hz 

120 V AC, 50/60 Hz 

200 V AC, 50/60 Hz 

230 V AC, 50/60 Hz

 

G

Closed position switch: 

with visual position indicator 

with visual position indicator and gold contacts

L

Viewing side: right 

left

 

Electrical connection: 

M20 cable gland

Part designations

VAN..S, VAN..G

VAN

1

2

3

4

5
6
7

Solenoid actuator

Flow body

Connection box

4

Connection flange

5

Closed position switch

6

Connection parts

7

Sealing plug

Mains voltage, electrical power consumption, ambi-
ent temperature, enclosure, inlet pressure and instal-
lation position: see type label.

D-49018 Osnabrück, Germany 

VAN

CE-0063BU1564

Installation

 CAUTION

Please observe the following to ensure that the 
magnetic relief valve is not damaged during instal-
lation and operation:

–   Important! The gas must be dry in all conditions 

and must not contain condensate.

–   Sealing material and dirt, e.g. thread cuttings, 

must not be allowed to get into the valve hous-
ing.

–   A filter must be installed upstream of every sys-

tem.

–   Do not store or install the unit in the open air.
–   Dropping the device can cause permanent 

 damage. In this event, replace the entire device 
and associated modules before use.

–   Do not clamp the unit in a vice. Only secure the 

flange by holding the octagon with a suitable 

spanner. Risk of external leakage.

–    Solenoid valves with overtravel switch and visual 

position indicator VAN..SR/SL: actuator cannot 
be rotated.

–    Cleaning work on the solenoid actuator may not 

be performed using high pressure and/or chemi-
cal cleaning agents. This can cause moisture 
to get into the solenoid actuator and may lead 
to a dangerous failure.

Installation position: black solenoid actuator in the 
vertical upright position or tilted up to the horizontal, 
not upside down.

 

The housing must not be in contact with masonry. 

Minimum clearance 20 mm (0,78").

  

 Note direction of flow.

2

3

Содержание VAN Series

Страница 1: ...ntially fatal situations WARNING Indicates possible danger to life and limb CAUTION Indicates possible material damage All interventions may only be carried out by qualified gas technicians Electrical interventions may only be carried out by qualified electricians Conversion spare parts All technical changes are prohibited Only use OEM spare parts Changes to edition 10 16 The following chapters ha...

Страница 2: ...tal lation position see type label D 49018 Osnabrück Germany VAN CE 0063BU1564 Installation CAUTION Please observe the following to ensure that the magnetic relief valve is not damaged during instal lation and operation Important The gas must be dry in all conditions and must not contain condensate Sealing material and dirt e g thread cuttings must not be allowed to get into the valve hous ing A f...

Страница 3: ...2 Shut off the gas supply Wiring to EN 60204 1 4 3 First push through the knock out then unscrew the cover If the M20 cable gland or plug is already fitted it is not necessary to push through the knock out M20 cable gland LV1 N 5 6 7 8 9 Plug LV1 black N blue LV1 N 5 6 7 8 When installing two plugs on a VAN with closed position switch label the sockets and plugs to avoid confusion Socket 1 N 2 LV1...

Страница 4: ... 2 LV1 N 1 3 2 LV1 N 2 1 3 2 1 Meldeschalter schwarz weiß rot LV1 black N blue 1 2 3 1 2 3 1 2 3 1 3 2 LV1 N 1 3 2 LV1 N 2 1 3 2 1 CPS black white red Label the plugs to avoid confusion 1 N 2 LV1 1 2 3 1 2 3 1 2 3 1 3 2 LV1 N 1 3 2 LV1 N 2 1 3 2 1 CPS black white red Ensure that the connection terminal for the closed position switch has been reconnected Finishing the wiring Tightness test 1 Close ...

Страница 5: ...tor as described here VAN 1 use all seals from the actuator adapter set VAN 2 use the small seal from the actuator adapter set and only one of the large seals VAN 1 2 10 11 Slide seal under the second groove 12 Position new actuator 13 Follow the reverse procedure when reassem bling 14 Fit the M20 cable gland or plug and socket 15 Connect the VAN to the electrical power supply see page 3 Wiring Ma...

Страница 6: ...g range adjusting tolerance 15 of the scale value Mean switching differential at min and max setting mbar WC mbar WC DG 17VC 2 17 0 8 6 8 0 7 1 7 0 3 0 8 DG 40VC 5 40 2 16 1 2 0 4 1 DG 110VC 30 110 12 44 3 8 0 8 3 2 DG 300VC 100 300 40 120 6 15 2 4 8 Deviation from the switching point during testing pursuant to EN 1854 Gas pressure switches 15 Seal set for sizes 1 2 When retrofitting accessories o...

Страница 7: ... 40 W 44 VA 230 V AC 40 W 44 VA Switching frequency max 15 x per minute duty cycle 100 Power factor of the solenoid coil cos φ 0 9 Closed position switch contact rating Type Voltage Min current resistive load Max cur rent resis tive load VAN S 12 250 V AC 50 60 Hz 100 mA 3 A VAN G 12 30 V DC 2 mA 0 1 A Closed position switch switching frequency max 5 x per minute Switching current A Switching cycl...

Страница 8: ...parately in accordance with local regulations Certification Declaration of conformity We the manufacturer hereby declare that the product VAN marked with product ID No CE 0063BU1564 complies with the requirements of the listed Directives and Standards Directives 2009 142 EC GAD valid until 20 April 2018 2014 35 EU LVD 2014 30 EU EMC Regulation EU 2016 426 GAR valid from 21 April 2018 Standards EN ...