Checking the usage
Intended use
Magnetic relief valve, open when de-energized, for
the monitoring of gas valves for tightness used in
conjunction with a visual discharge unit. For purging
excess or leakage gas.
This function is only guaranteed when used within the
specified limits – see page 7 (Technical data). Any
other use is considered as non-compliant.
Type code
Code
Description
VAN
Magnetic relief valve
Size: 1
2
T
T-product
0 – 50
Nominal size
DN
R
N
Rp internal thread
NPT internal thread
N
Quick opening, quick closing
K
P
Q
Y
W
Mains voltage: 24 V DC
100 V AC, 50/60 Hz
120 V AC, 50/60 Hz
200 V AC, 50/60 Hz
230 V AC, 50/60 Hz
S
G
Closed position switch:
with visual position indicator
with visual position indicator and gold contacts
R
L
Viewing side: right
left
Electrical connection:
M20 cable gland
Part designations
VAN..S, VAN..G
VAN
1
2
3
4
5
6
7
Solenoid actuator
Flow body
Connection box
4
Connection flange
5
Closed position switch
6
Connection parts
7
Sealing plug
Mains voltage, electrical power consumption, ambi-
ent temperature, enclosure, inlet pressure and instal-
lation position: see type label.
D-49018 Osnabrück, Germany
VAN
CE-0063BU1564
Installation
CAUTION
Please observe the following to ensure that the
magnetic relief valve is not damaged during instal-
lation and operation:
– Important! The gas must be dry in all conditions
and must not contain condensate.
– Sealing material and dirt, e.g. thread cuttings,
must not be allowed to get into the valve hous-
ing.
– A filter must be installed upstream of every sys-
tem.
– Do not store or install the unit in the open air.
– Dropping the device can cause permanent
damage. In this event, replace the entire device
and associated modules before use.
– Do not clamp the unit in a vice. Only secure the
flange by holding the octagon with a suitable
spanner. Risk of external leakage.
– Solenoid valves with overtravel switch and visual
position indicator VAN..SR/SL: actuator cannot
be rotated.
– Cleaning work on the solenoid actuator may not
be performed using high pressure and/or chemi-
cal cleaning agents. This can cause moisture
to get into the solenoid actuator and may lead
to a dangerous failure.
Installation position: black solenoid actuator in the
vertical upright position or tilted up to the horizontal,
not upside down.
▷
The housing must not be in contact with masonry.
Minimum clearance 20 mm (0,78").
Note direction of flow.
2
3