Closed position switch

 

VAN open: contacts 

 and 

 closed, 

VAN closed: contacts 

 and 

 closed.

 

Indicator of closed position switch: 
red = VAN closed, white = VAN open.

 CAUTION

Please observe the following to ensure smooth 
operation:

–   Route valve and closed position switch cables 

separately through M20 cable glands or use 
two separate plugs. Otherwise, there is a risk of 
interference between valve voltage and closed 
position switch voltage.

 

To make wiring easier, the connection terminal 

for the closed position switch can be removed.

1

2

3

1

2

3

1

2

3

1 3

2

LV1

(+)

N

(-)

1 3

2

LV1

(+)

N

(-)

2

1

3

2

1

Meldeschalter

schwarz

weiß

rot

LV1 (+) = black, N (–) = blue

1

2

3

1

2

3

1

2

3

1 3

2

LV1

(+)

N

(-)

1 3

2

LV1

(+)

N

(-)

2

1

3

2

1

CPS

black

white

red

 

Label the plugs to avoid confusion.

1 = N (–), 2 = LV1 (+)

1

2

3

1

2

3

1

2

3

1 3

2

LV1

(+)

N

(-)

1 3

2

LV1

(+)

N

(-)

2

1

3

2

1

CPS

black

white

red

 

Ensure that the connection terminal for the 
closed position switch has been reconnected.

Finishing the wiring

Tightness test

  

 Close the gas solenoid valve.

  

 To be able to check the tightness, shut off the 

downstream pipeline close to the valve.

0

0

3

6

4

7

8

5

0

 

Open the 

solenoid 

valve.

 9 

 Tightness OK: open the pipeline.

 

Pipeline leaking: replace O-ring on flange, see 
page 6 (Seal set for sizes 1 – 2). Then check 
for tightness once again.

 

Unit leaking: remove the unit and return it to the 
manufacturer.

Содержание VAN Series

Страница 1: ...ntially fatal situations WARNING Indicates possible danger to life and limb CAUTION Indicates possible material damage All interventions may only be carried out by qualified gas technicians Electrical interventions may only be carried out by qualified electricians Conversion spare parts All technical changes are prohibited Only use OEM spare parts Changes to edition 10 16 The following chapters ha...

Страница 2: ...tal lation position see type label D 49018 Osnabrück Germany VAN CE 0063BU1564 Installation CAUTION Please observe the following to ensure that the magnetic relief valve is not damaged during instal lation and operation Important The gas must be dry in all conditions and must not contain condensate Sealing material and dirt e g thread cuttings must not be allowed to get into the valve hous ing A f...

Страница 3: ...2 Shut off the gas supply Wiring to EN 60204 1 4 3 First push through the knock out then unscrew the cover If the M20 cable gland or plug is already fitted it is not necessary to push through the knock out M20 cable gland LV1 N 5 6 7 8 9 Plug LV1 black N blue LV1 N 5 6 7 8 When installing two plugs on a VAN with closed position switch label the sockets and plugs to avoid confusion Socket 1 N 2 LV1...

Страница 4: ... 2 LV1 N 1 3 2 LV1 N 2 1 3 2 1 Meldeschalter schwarz weiß rot LV1 black N blue 1 2 3 1 2 3 1 2 3 1 3 2 LV1 N 1 3 2 LV1 N 2 1 3 2 1 CPS black white red Label the plugs to avoid confusion 1 N 2 LV1 1 2 3 1 2 3 1 2 3 1 3 2 LV1 N 1 3 2 LV1 N 2 1 3 2 1 CPS black white red Ensure that the connection terminal for the closed position switch has been reconnected Finishing the wiring Tightness test 1 Close ...

Страница 5: ...tor as described here VAN 1 use all seals from the actuator adapter set VAN 2 use the small seal from the actuator adapter set and only one of the large seals VAN 1 2 10 11 Slide seal under the second groove 12 Position new actuator 13 Follow the reverse procedure when reassem bling 14 Fit the M20 cable gland or plug and socket 15 Connect the VAN to the electrical power supply see page 3 Wiring Ma...

Страница 6: ...g range adjusting tolerance 15 of the scale value Mean switching differential at min and max setting mbar WC mbar WC DG 17VC 2 17 0 8 6 8 0 7 1 7 0 3 0 8 DG 40VC 5 40 2 16 1 2 0 4 1 DG 110VC 30 110 12 44 3 8 0 8 3 2 DG 300VC 100 300 40 120 6 15 2 4 8 Deviation from the switching point during testing pursuant to EN 1854 Gas pressure switches 15 Seal set for sizes 1 2 When retrofitting accessories o...

Страница 7: ... 40 W 44 VA 230 V AC 40 W 44 VA Switching frequency max 15 x per minute duty cycle 100 Power factor of the solenoid coil cos φ 0 9 Closed position switch contact rating Type Voltage Min current resistive load Max cur rent resis tive load VAN S 12 250 V AC 50 60 Hz 100 mA 3 A VAN G 12 30 V DC 2 mA 0 1 A Closed position switch switching frequency max 5 x per minute Switching current A Switching cycl...

Страница 8: ...parately in accordance with local regulations Certification Declaration of conformity We the manufacturer hereby declare that the product VAN marked with product ID No CE 0063BU1564 complies with the requirements of the listed Directives and Standards Directives 2009 142 EC GAD valid until 20 April 2018 2014 35 EU LVD 2014 30 EU EMC Regulation EU 2016 426 GAR valid from 21 April 2018 Standards EN ...