10 teCHnICAL DAtA
Gas supply pressure and air supply pressure each
depend on the use and gas type.
Gas and air pressures:
see burner diagrams at www.docuthek.com.
Special gaskets are available on request for air
pressures of > 100 mbar (39.4 "WC) (e.g. reverse
flow pressure in the furnace).
Burner flow rate curves:
A web app to view the burner flow rate curves is
Gas types:
natural gas, LPG (gaseous), coke oven gas, town
gas, low calorific value gas and biogas; other types
of gas on request.
Combustion air:
The air must be dry and clean in all temperature
conditions and must not contain condensate.
overall lengths:
100 to 500 mm (3.9 to 19.7 inches) or 50 to
450 mm (2 to 17.7 inches), length increments:
100 mm (3.94 inches) (other lengths available on
request).
Control type:
staged: On/Off,
modulating: constant λ value.
Flame control:
with flame rod (UV control as an option).
Ignition:
direct spark ignition; integrated pilot as an option.
Storage temperature: -20°C to +40°C.
Burner body:
BIO: cast steel,
BIOA: AlSi,
BIOW: St + internal insulation.
Most of the burner components are made of corro-
sion-resistant stainless steel.
Ambient conditions:
-20°C to +180°C (68°F to 356°F) (outside the ther-
moprocessing system); no condensation permitted,
painted surfaces may corrode.
Maximum furnace temperature:
BIO(W) in burner block:
up to 1600°C (up to 2912°F),
BIO with burner attachment tube:
up to 600°C (up to 1112°F).
Maximum air temperature:
BIO: up to 450°C (842°F),
BIOA: up to 200°C (392°F),
BIOW: up to 600°C (1112°F).
ReACH Regulation
applies to BIOW only.
Information pursuant to REACH Regulation No.
1907/2006, Article 33.
Insulation contains refractory ceramic fibres (RCF)/
aluminium silicate wool (ASW).
RCF/ASW are listed in the Candidate List of the
European REACH Regulation No. 1907/2006.
10.1 ReACH Regulation
applies to BIOW only.
Information pursuant to REACH Regulation No.
1907/2006, Article 33.
Insulation contains refractory ceramic fibres (RCF)/
aluminium silicate wool (ASW).
RCF/ASW are listed in the Candidate List of the
European REACH Regulation No. 1907/2006.
11 LoGIstICs
transport
Protect the unit from external forces (blows, shocks,
vibration).
Transport temperature: see page 15 ().
Transport is subject to the ambient conditions de-
scribed.
Report any transport damage on the unit or packaging
without delay.
Check that the delivery is complete.
storage
Storage temperature: see page 15 ().
Storage is subject to the ambient conditions described.
Storage time: 6 months in the original packaging before
using for the first time. If stored for longer than this, the
overall service life will be reduced by the corresponding
amount of extra storage time.
12 DIsPosAL
Devices with electronic components:
Weee Directive 2012/19/eU – Waste electrical
and electronic equipment Directive
At the end of the product life (number of op-
erating cycles reached), dispose of the pack-
aging and product in a corresponding recycling
centre. Do not dispose of the unit with the usu-
al domestic refuse. Do not burn the product.
On request, old units may be returned carriage paid
to the manufacturer in accordance with the relevant
waste legislation requirements.