Parameter name
Parameter value
15
Low air pressure protection
0
= Off
1
= With safety shut-down
2
= With fault lock-out
16
Delayed low air pressure protection
0
= Off
1
= On
19
Safety time during operation
0
;
1
;
2
= Time in seconds
28
menox pre-ventilation time t
VLM
0 – 250
= Time in seconds
34
Pre-purge time t
PV
0 – 6000
= Time in seconds
35
Air flow monitoring during pre-purge
0
= Off
1
= With safety shut-down
2
= With fault lock-out
36
Pre-ventilation time t
VL
0 – 250
= Time in seconds
39
Post-ventilation time t
NL
0
–
3
= Time in seconds
40
Capacity control
1
= IC 20
2
= IC 40
3
= RBW
4
= Frequency converter
5
= Air valve
41
Running time selection
0
= Off; checking the positions for min./max.
capacity
1
= On; for approaching the positions for min./
max. capacity
2
= On; for approaching the position for
maximum capacity
3
= On; for approaching the position for
minimum capacity
42
Running time
0 – 250
= Time in seconds
43
Low fire over-run
0
= Off
1
= Up to minimum capacity
44
Controller enable signal delay time t
RF
0 – 250
= Time in seconds
48
Air actuator control
0
= Opens on external activation
1
= Opens with valve V1 (1
st
stage)
2
= Opens with valve V2 (2
nd
stage)
3
= Controller enable following operating signal
or in standby
4
= Opens with V4 burner 1
49
Air actuator can be activated externally on
start-up
0
= Cannot be activated
1
= Can be activated externally
50
Air actuator in the event of fault
0
= Cannot be activated
1
= Can be activated externally
Pa-
ram-
eter
No.
Parameter name
Parameter value
51
Valve proving system
0
= Off
1
= Tightness test before start-up
2
= Tightness test after shut-down
3
= Tightness test before start-up and after shut-down
4
= Proof of closure function
56
Measurement time V
p1
0 – 3600
= Time in seconds
59
Valve opening time 1 t
L1
2 – 25
= Time in seconds
61
Minimum operating time t
B
0 – 250
= Time in seconds
62
Minimum pause time t
BP
0 – 3600
= Time in seconds
63
Switch-on delay time t
E
0 – 250
= Time in seconds
67
Operating time in Manual mode
0
= Unlimited
1
= 5 minutes
68
Function of terminal 50
0
= Off
23
= Purge with Low signal
24
= Purge with High signal
69
Function of terminal 51
0
= Off
8
= AND gating with emergency stop input
(terminal 46)
9
= AND gating with air pressure switch input
(terminal 47)
10
= AND gating with purge pressure switch input
(terminal 48)
11
= AND gating with Gas max input (terminal 50)
12
= AND gating with Gas min input (terminal 49)
13
= IC 40/RBW purge position feedback
70
Function of terminal 65
0
= Off
8
= AND gating with emergency stop input
(terminal 46)
9
= AND gating with air pressure switch input
(terminal 47)
10
= AND gating with purge pressure switch input
(terminal 48)
71
Function of terminal 66
0
= Off
8
= AND gating with emergency stop input
(terminal 46)
9
= AND gating with air pressure switch input
(terminal 47)
10
= AND gating with purge pressure switch input
(terminal 48)
20
= LDS ignition position check