Technical data
Gas types: natural gas, town gas, LPG (gaseous),
biogas (max. 0.1 %-by-vol. H
2
S) or clean air;
other gases on request. The gas must be dry in
all temperature conditions and must not contain
condensate.
Opening time: 0.5 s.
Closing time: < 1 s.
Ambient temperature: -20 to +60°C.
Long-term use in the upper ambient temperature
range accelerates the ageing of the elastomer ma-
terials and reduces the service life (please contact
manufacturer).
Storage temperature: -20 to +40°C.
Safety valve:
Class A, Group 2 pursuant to EN 161.
Mains voltage:
230 V AC, +10/-15%, 50/60 Hz,
120 V AC, +10/-15%, 50/60 Hz.
Electrical connection:
plug with socket to EN 175301-803.
Power consumption:
Type
120/230 V AC
[W]
VGP 10
26
VGP 15
26
VGP 20
35
VGP 25
35
Enclosure: IP 54.
Duty cycle: 100%.
Power factor of the solenoid coil: cos
ϕ
= 1.
Solenoid coil insulation: class F insulating material.
Switching frequency: any.
Valve housing: aluminium,
valve disc: Perbunan.
Internal thread: Rp to ISO 7-1.
Designed lifetime
This information on the designed lifetime is based on
using the product in accordance with these operating
instructions. Once the designed lifetime has been
reached, safety-relevant products must be replaced.
Designed lifetime (based on date of manufacture) in
accordance with EN 161 for VGP:
Type
Designed lifetime
Switching
cycles
Time
[years]
VGP 10 to 15
200,000
10
VGP 20 to 25
500,000
10
You can find further explanations in the applicable
rules and regulations and on the afecor website
(www.afecor.org).
This procedure applies to heating systems. For
thermoprocessing equipment, observe local regu-
lations.
Logistics
Transport
Protect the unit from external forces (blows, shocks,
vibration). On receipt of the product, check that the
delivery is complete, see page 2 (Part designa-
tions). Report any transport damage immediately.
Storage
Store the product in a dry and clean place.
Storage temperature: see page 7 (Technical data).
Storage time: 6 months in the original packaging
before using for the first time. If stored for longer
than this, the overall service life will be reduced by
the corresponding amount of extra storage time.
Packaging
The packaging material is to be disposed of in ac-
cordance with local regulations.
Disposal
Components are to be disposed