GB-2
D
GB
F
NL
I
E
Checking the usage
Intended use
VGP
Gas solenoid valve for safeguarding gas or air on
various appliances.
This function is only guaranteed when used within
the specified limits – see page 7 (Technical data).
Any other use is considered as non-compliant.
Type code
Code
Description
VGP
Gas solenoid valve
0 – 25
Nominal size
R
Rp internal thread
0
02
p
e max.
150 mbar
p
e max.
200 mbar
Q
W
Mains voltage: 120 V AC, 50/60 Hz
Mains voltage: 230 V AC, 50/60 Hz
5
6
Connection via rectifier adapter
without standard socket
Connection via rectifier adapter
and standard socket
Part designations
6
5
1
2
4
3
Housing
2
Actuator
3
Quick fastener
4
Seals
5
Rectifier adapter
6
Socket
Type label
Rated voltage, electrical power consumption, instal-
lation position, max. inlet pressure p
e max.
, ambient
temperature, enclosure and medium: see type label.
D-49018 Osnabrück, Germany
VGP
Installation
CAUTION
Please observe the following to ensure that the VGP
is not damaged during installation and operation:
– Do not clamp the unit in a vice. Only secure the
flange by holding the octagon with a suitable
spanner. Risk of external leakage
.
– Continuous operation at high temperatures ac-
celerates the ageing of elastomer materials.
– Do not install or store the unit in the open air.
– Dropping the device can cause permanent dam-
age. In this event, replace the entire device and
associated modules before use.
– Check max. ambient temperature – see type
label.
– Check max. inlet pressure – see type label.
▷
Installation position: black solenoid actuator in
the vertical upright position or tilted up to the
horizontal, not upside down.
> 20 mm
▷
The housing must not be in contact with masonry.
Minimum clearance 20 mm.
> 20 mm
▷
Sealing material and dirt, e.g. thread cuttings,
must not be allowed to get into the valve housing.
▷
Install a filter upstream of every system.
▷
Use approved sealing material only.
▷
Use a suitable spanner.
2
3
1
4