Checking the usage

Intended use

VGP

Gas solenoid valve for safeguarding gas or air on 
various appliances.

This function is only guaranteed when used within 

the specified limits – see page 7 (Technical data). 

Any other use is considered as non-compliant.

Type code

Code

Description

VGP

Gas solenoid valve

0 – 25

Nominal size

R

Rp internal thread

0 

02

p

e max.

 150 mbar 

p

e max.

 200 mbar

W

Mains voltage: 120 V AC, 50/60 Hz 

Mains voltage: 230 V AC, 50/60 Hz

 

Connection via rectifier adapter 

without standard socket 

Connection via rectifier adapter 

and standard socket

Part designations

6

 Housing

2

 Actuator

3

  Quick fastener

4

 Seals

5

  Rectifier adapter

6

 Socket

Type label

Rated voltage, electrical power consumption, instal-
lation position, max. inlet pressure p

e max.

, ambient 

temperature, enclosure and medium: see type label.

D-49018 Osnabrück, Germany

VGP

Installation

 CAUTION

Please observe the following to ensure that the VGP 
is not damaged during installation and operation:

–   Do not clamp the unit in a vice. Only secure the 

flange by holding the octagon with a suitable 

spanner. Risk of external leakage

.

–   Continuous operation at high temperatures ac-

celerates the ageing of elastomer materials.

–  Do not install or store the unit in the open air.
–   Dropping the device can cause permanent dam-

age. In this event, replace the entire device and 
associated modules before use.

–   Check max. ambient temperature – see type 

label.

–   Check max. inlet pressure – see type label.

 

Installation position: black solenoid actuator in 
the vertical upright position or tilted up to the 
horizontal, not upside down.

 

> 20 mm

 

The housing must not be in contact with masonry. 

Minimum clearance 20 mm.

 

> 20 mm

 

Sealing material and dirt, e.g. thread cuttings, 
must not be allowed to get into the valve housing.

 

Install a filter upstream of every system.

 

Use approved sealing material only.

 

Use a suitable spanner.

2

3

1

4

Содержание VGP10

Страница 1: ...WARNING Indicates possible danger to life and limb CAUTION Indicates possible material damage All interventions may only be carried out by qualified gas technicians Electrical interventions may only b...

Страница 2: ...D 49018 Osnabr ck Germany VGP Installation CAUTION Please observe the following to ensure that the VGP is not damaged during installation and operation Do not clamp the unit in a vice Only secure the...

Страница 3: ...n be rotated 2 1 3 1 N 2 L 4 5 3 6 7 8 Plug insert can be rotated in 90 steps 10 9 12 11 Tightness test CAUTION Please observe the following to ensure that the VGP is not damaged during the tightness...

Страница 4: ...year or every six months if operated with biogas Checking tightness and function In order to determine whether the VGP is tight and closes securely check the internal and ex ternal tightness see page...

Страница 5: ...observe the following to ensure that the VGP is not damaged during subsequent operation Install the closing spring in the correct position Ensure that the catch of the closing spring is positioned in...

Страница 6: ...Note the inscription on the rectifier adapter 1 2 No resistance replace adapter The rectifier adapter is available separately as a spare part Actuator defective Remove socket and rectifier adapter see...

Страница 7: ...based on using the product in accordance with these operating instructions Once the designed lifetime has been reached safety relevant products must be replaced Designed lifetime based on date of man...

Страница 8: ...equirements of the listed Direc tives and Standards Directives 2009 142 EC GAD valid until 20 April 2018 2014 30 EU 2014 35 EU Regulation EU 2016 426 GAR valid from 21 April 2018 The relevant product...

Отзывы: