background image

GB-4

D

GB

F

NL

I

E

Valves

Valve 

volume 

V

V

 [l]

Nominal 

size

DN

Pipe  

volume  

V

R

 [l/m]

VK 125

13.6

125

12.3

VK 150

20

150

17.7

VK 200

42

200

31.4

VK 250

66

250

49

VAS 1

0.08

VAS 2

0.32

VAS 3

0.68

VAS 6

1.37

VAS 7

2.04

VAS 8

3.34

VAS 9

5.41

VCS 1

0.05

VCS 2

0.18

VCS 3

0.39

VCS 6

1.11

VCS 7

1.40

VCS 8

2.82

VCS 9

4.34

Calculation example:
 

 Q

max.

 = 100 m

3

/h 

 p

u

 = 100 mbar 

 V

P

 = V

V

 + L x V

R

 = 7 l 

 Q

L

 = 100 m

3

/h x 0.1% = 100 l/h

4 x 

(

100 x 7

 

 + 1 s 

)

 = 32 s

100

 

 Set the next highest value (in this example 40 s) 
with the jumper.

  

 Disconnect the unit from the electrical power 

supply.

  

 Unscrew the housing cover.

 4 

 Connect the jumper to the pin for the required 

test period t

P

 between 10 and 60 s (100 and 

600 s).

V2

V1

L1(+)

N(-)

ϑ

max

N

1 2

1 2

"TEST

:

"

TEST"

:"

 5 

 Position the housing cover and screw tight.

 6 

  Mark the set test period t

P

 on the type label with 

a waterproof pen.

TC

CE-0085AP0020

tp(s)  10 20 30 40 50 60

D-49018 Osnabrück, Germany

Commissioning

 

Indicators and operating controls:

TEST OK

1

2

TEST

 = TEST phase (yellow) 

OK

 

= operating signal (green) 

1

  = fault valve 1 (red) 

2

  = fault valve 2 (red) 

 

= reset button

  

 Main switch on.

  

 Apply mains voltage to terminal 1.

 

If one or both fault lamps (red) are lit, wait ap-
prox. 5 s then press the reset button. The fault 
signal goes out.

  

 Start the tightness test.

 

Mode 

, test before burner start-up.

 4 

 Voltage at terminal 3.

 Or

 

Mode 

, test after burner run.

 5 

 Mains voltage at terminal 1 and renewed test 

after switching off the voltage to terminal 3.

The test begins:

 

LED 

TEST

 is lit.

After test, if the valves are tight:

 

LED 

OK

 is lit.

 

 MODE 1: voltage at terminal 4.

 Or 
 

 MODE 2: voltage at terminal 4 does not arrive 

until voltage is applied to terminal 3.

After test, if the valves are leaking: voltage at termi-

nals 8 and 9.

 

LED 

1

 is lit.

 Or

 

LED 

2

 is lit. 

Power failure

 

If the power fails briefly during the test or during 
operation, the tightness test will restart auto-
matically.

 

After a power failure during a fault, both red fault 

lamps will be lit.

Assistance in the event of 
malfunction

 CAUTION

Electric shocks can be fatal!

–   Before working on possible live components, en-

sure the unit is disconnected from the power supply.

–   Fault-clearance must only be undertaken by 

authorized trained personnel.

–   (Remote) resets may only be conducted by 

authorized personnel.

 

Faults may be cleared only using the measures 
described below.

Отзывы: