Krom Schroder JSAV 50 Скачать руководство пользователя страница 2

GB-2

D

GB

F

NL

I

E

Checking the usage

JSAV

Safety shut-off valve for securing downstream fittings 
against excess gas pressure.

This function is only guaranteed when used within 

the specified limits – see page 7 (Technical data). 

Any other use is considered as non-compliant.

Type code

Code

Description

JSAV

Safety shut-off valve

50 – 00

Nominal size

T

T-product

A

Flange to ISO 7005 

ANSI flange

50

Inlet pressure p

u max.

 = 5 bar (72.5 psig)

/

Over-pressure shut-off p

do

-0

No pressure test point

Part designations

10 

  Measuring unit

  Screw plug with position indicator

   Connection for impulse line (closed with plastic 

plug)

4

 Inlet

5

 Outlet

6

  Arrow of direction of flow

7

 Reset

8

  Arrow of direction of reset

9

  Reset lever

0

  Connection for breather line (closed with plastic 

plug)

Type label

Max. inlet pressure, upper trip pressure p

do

, ambient 

temperature: see type label.

D-49018 Osnabrück, Germany

JSAV

TS=

P

u

 max:

Wh

o

:

p

do

:

AGo: +/- 10%

Installation

 CAUTION

Please observe the following to ensure that the 

JSAV is not damaged during installation:

–   Sealing material, cuttings and other impurities 

must not be allowed to get into the housing.

–   We recommend installing a filter upstream of the 

JSAV in order to protect it against impurities in 

the pipe.

–   The installation location must be dry. Do not 

store or install the JSAV in the open air.

–   Install the JSAV in the pipe free of mechanical 

stress.

–   Do not clamp the unit in a vice or use it as a 

lever. Risk of external leakage.

–   Max. inlet pressure p

u max.

 5 bar (72.5 psig).

–   Installation in the vertical or horizontal position, 

never upside down.

  

 The housing must not be in contact with ma-

sonry. Minimum clearance 20 mm (0.78"). Ensure 
that there is sufficient space for installation and 
adjustment.

  

  Remove the adhesive foil from the inlet and outlet 

on the JSAV.

  

 Insert seal between pipe and unit.

 

Note direction of flow.

Содержание JSAV 50

Страница 1: ...ions may only be carried out by qualified gas technicians Electrical interventions may only be carried out by qualified electricians Conversion spare parts All technical changes are prohibited Only use OEM spare parts Changes to edition 10 15 The following chapters have been changed Installation Setting the trip pressure pdo Certification Operating instructions D GB GB 1 03250885 Translation from ...

Страница 2: ...trip pressure pdo ambient temperature see type label D 49018 Osnabrück Germany JSAV TS Pu max Who pdo AGo 10 Installation CAUTION Please observe the following to ensure that the JSAV is not damaged during installation Sealing material cuttings and other impurities must not be allowed to get into the housing We recommend installing a filter upstream of the JSAV in order to protect it against impuri...

Страница 3: ...ial Ensure that there is sufficient tube length for the impulse line 0 Rp NPT Connecting the breather line Remove the plastic plug in the breather line connection and connect an Rp NPT pipe We recommend a pipe diameter of 12 x 1 5 mm 1 Install the breather line and seal with approved sealing material Route the breather line to a safe area 0 Rp NPT Tightness test WARNING An additional tightness tes...

Страница 4: ...isc Ensure that the JSAV and outlet gas line are closed 1 Vent the system 2 Slowly open the manual valve at the inlet 3 The outlet pressure pd must not rise Setting the trip pressure pdo 1 Select the trip pressure pdo according to the outlet pressure pd of the pressure regulator 20 0 40 60 80 100 140 180 220 260 300 340 50 100 150 200 250 300 350 400 450 500 pd mbar p do mbar VSBV JSAV 2 Remove th...

Страница 5: ... reset lever until the valve disc opens and clicks into place and the SHUT mark is no longer visible The red SHUT mark must not be visible once the valve disc has clicked into place The JSAV is ready for operation Replacing the measuring unit The measuring unit has to be replaced if the JSAV no longer opens or can no longer be reset We recommend cleaning the O ring seats and lightly greasing the O...

Страница 6: ...e to the impulse line to close the valve 2 Detach the impulse and breather lines from the JSAV 7 6 4 5 3 Press the reset lever and turn until the valve disc is on top WARNING Risk of injury The spring wire is under high stress 10 11 8 12 14 13 9 15 16 Insert new O rings from the seal set Press the spring wire into the notch in the plate 17 Follow the reverse procedure when reassembling using the n...

Страница 7: ...urther half a turn See the drawing labelled Contacts in the en closed position switch installation and connec tion instructions for measuring the switching point 9 Prevent the position switch from rotating using the fitted lock nut 10 Wire the position switch See the drawing labelled Contacts in the en closed position switch installation and connec tion instructions for the electrical wiring 11 Af...

Страница 8: ... Part designa tions Report any transport damage immediately Storage Store the product in a dry and clean place Storage temperature see page 7 Technical data Storage time 6 months before using for the first time If stored for longer than this the overall service life will be reduced by the corresponding amount of extra storage time Packaging The packaging material is to be disposed of in ac cordanc...

Отзывы: