BCU 560, BCU 565 · Edition 02.16
87
Parameters > Air control
11 .6 .10 Air actuator control
Parameter 48
In cyclic operation, parameters 48 and 49 on BCU..F1, F2 and F3
determine the behaviour of the air actuator during burner start.
Parameter 48 = 0: opens on external activation.
t
SA
t
Z
A4
02
03
00 A0
t
t
FS
2
10
∨
53
A
88
ϑ
46
1
11
9
5
37-38
13
V1
14
V2
17-18
M
This setting together with parameter 49 = 0, see page 89
(Air actuator can be activated externally on start-up), is re-
quired for burners on which the air/gas ratio is controlled by
a pneumatic air/gas ratio control system and which need to
be started at low-fire rate, e.g. on two-stage-controlled burn-
ers, see page 8 (Two-stage-controlled burner). In this case,
activation of the air actuator during burner start via the input
at terminal 2 must be prevented.
External control allows switchover between low fire and high
fire during operation.
Parameter 48 = 1: opens with valve V1 1
st
stage
t
SA
t
Z
A4
A2
A3
00 A0 00
t
t
FS
A0
2
10
∨
53
A
88
ϑ
46
1
11
9
5
37-38
13
V1
14
V2
17-18
M
Parameter 48 = 2: opens with valve V2 2
nd
stage
t
SA
t
Z
A4
02
03
00
t
t
FS
00
A0
2
10
∨
53
A
88
ϑ
46
1
11
9
5
37-38
13
V1
14
V2
17-18
M
The air actuator can be activated externally via the input at ter-
minal 2 for cooling the burner in the start-up position (standby).
This function is not available during burner start-up and during
operation.
▼