BCU 560, BCU 565 · Edition 02.16
51
Fault signalling
Fault message (blinking)
DISPLAY
Description
Outlet valve(s) leaking
41
Leak found on outlet valve
Pressure switch/gas valve wiring
44
Gas valve wiring
45
Reversed valve connection
Safety interlock failure
51
Permanent remote reset
52
Remote reset input activated > 25 s
Timing cycle too short
53
Minimum timing cycle not observed
Waiting for ignition position (LDS)
54
Faulty feedback signal of the control element po-
sition for ignition capacity
Wiring for multi-flame control
56
Faulty wiring for multi-flame control
Incorrect voltage supply to terminal 44
57
menox
®
mode without HT signal
Internal error
80
Flame amplifier error/device error
Internal error
89
Error in processing internal data
Internal error
94
Error at digital inputs
Internal error
95
Error at digital outputs
Internal error
96
Error when checking the SFR
Internal error
97
Error when reading the EEProm
Internal error
98
Error when writing to the EEProm
emBoss
99
Shut-down without application error
Minimum capacity not reached
A
Position for minimum capacity has not been
reached after 255 s
Maximum capacity not reached
A
Position for maximum capacity has not been
reached after 255 s
Ignition capacity not reached
A
Position for ignition capacity has not been reached
after 255 s
Communication with bus module
E
Bus module fault
Parameter chip card (PCC)
Incorrect or defective PCC
▼