 COMMISSIONING / OPERATION 

4

11

OPTIWAVE 5200 C

www.krohne.com

10/2013 - 4003066901 - MA OPTIWAVE5200C-PA-R01-en-

Profile specific Ident. Number (9700hex)

Profile specific Ident. Number (9700hex)

Profile specific Ident. Number (9700hex)

Profile specific Ident. Number (9700hex)
 The 4 AI-FB are available only for cyclic data transfer. Cyclic PROFIBUS services cannot supply 
device-specific diagnosis data. This operational condition can make devices from different 
suppliers operate better together. The system will only use functions that are available to all 
PROFIBUS PA level transmitters. It is not necessary to change the settings of the control system 
to transfer data.

Cyclic layout:

It is necessary to use GSD file PA139700.GSD in this mode. This file is supplied by PROFIBUS 
International (refer to www.profibus.com). It is possible to use this file for all types of PROFIBUS 
DP/PA segment couplers. If this file is used, 

Condensed Status

 is not available.

4.4  Configuration of cyclic data transfer

During network configuration the user has to select which function block input/output data shall 
be transferred between the PROFIBUS master and the PROFIBUS slave. The GSD file described 
above contains several types of modules for this purpose. During configuration a module has to 
be assigned to each slot of the device in order to select which data has to be transferred for the 
corresponding function blocks. The cyclic layout (see section Ident. Number selector) shows 
which module types are valid for each slot. The order of transmission of the data always remains 
the same. If an 

Empty Module

 is assigned to a slot no data will be sent for the corresponding 

function block and all function block data following this empty module will move up one position.

Slot

Function Block

Valid GSD Modules

1

AI-FB

Analog Input (AI) short

Analog Input (AI) long

INFORMATION!

If a different GSD file is used in the PROFIBUS master system, it is not possibe to transfer cyclic 
data.

Содержание OPTIWAVE 5200 C

Страница 1: ...OFIBUS PA interface The documentation is only complete when it is used in combination with the relevant documentation of the level meter OPTIWAVE 5200 C OPTIWAVE 5200 C OPTIWAVE 5200 C OPTIWAVE 5200 C...

Страница 2: ...ry 4 2 2 Device description 4 2 3 Function blocks and the PROFIBUS PA Profile 4 2 4 Technical data 5 3 Electrical connection 6 3 1 Topology of a PROFIBUS PA network 6 3 2 Electrical connection for sig...

Страница 3: ...the readme txt files 1 2 Scope of the document These instructions are supplementary to the standard product documentation of the signal converter The details described herein in particular the safety...

Страница 4: ...PLC The control system cyclic communication services can read or write input and output data The device has these blocks Issued Signal converter Application program System integration Mth year Hardwa...

Страница 5: ...rface This interface agrees with IEC 61158 2 bit rate 31 25 kbit s voltage mode MBP Manchester Coded Bus Powered Device power supply 9 32 V bus powered no additional power supply required Polarity sen...

Страница 6: ...provides the conversion to the PROFIBUS DP bus line In addition it provides the power supply for bus powered PROFIBUS PA devices Refer to the instruction manual of the segment coupler concerning the D...

Страница 7: ...ant that the system components and in particular the bus cables are shielded These shields must have as few gaps as possible Use the shortest possible length of shield wire to connect the electrical c...

Страница 8: ...n address with the network bus ON The user can set the address of the device with the 7 other DIP swtiches item 2 You cannot use the network bus or the local display to change the station address 2 7...

Страница 9: ...code 2712 reset station address to its default value are used If No_add_Cfg flag is set to ON the device will continue to use FACTORY_RESET code 2712 If the Station Address DIP switches are changed fr...

Страница 10: ...download 4 3 Ident Number Manufacturer specific Ident Number 4554hex Manufacturer specific Ident Number 4554hex Manufacturer specific Ident Number 4554hex Manufacturer specific Ident Number 4554hex T...

Страница 11: ...nt couplers If this file is used Condensed Status is not available 4 4 Configuration of cyclic data transfer During network configuration the user has to select which function block input output data...

Страница 12: ...g slot 4 byte float value Float Format according to IEEE Standard 754 Short Real Number 1 byte status value Float value Float value Float value Float value The example that follows shows the format of...

Страница 13: ...tus and Diagnosis automatically during start up of the cyclic data transfer by setting the parameter PRM_COND within the Set_Prm service data using an engineering tool e g DD DTM to write the paramete...

Страница 14: ...verride value not usable Quality Quality substatus Limits Gr Gr QS QS QS QS Qu Qu 27 26 25 24 23 22 21 20 0 1 0 0 1 0 x x substitute set 0 1 0 0 1 1 1 1 initial value 0 1 1 0 1 0 x x maintenance deman...

Страница 15: ...ad function block output value is bad do not use it for process control The Quality Substatus and Limit bits will be used for further diagnostics or limit checking Classic Status Classic Status Classi...

Страница 16: ...s Gr Gr QS QS QS QS Qu Qu 27 26 25 24 23 22 21 20 0 1 0 0 0 0 non specific 0 1 0 0 0 1 last usable value 0 1 0 0 1 0 substitute set 0 1 0 0 1 1 initial value 0 1 0 1 0 0 sensor conversion not accurate...

Страница 17: ...DD DTM to read it Cyclic services transfer diagnosis data to the control system PLC Diagnosis is bitwise coded Thus it is possible to report more than one indication simultaneously The GSD file conta...

Страница 18: ...send the device back to the manufacturer with an indication of the error 35 yes Restart Device is restarted because of power up or warmstart request In case of unexpected restart send the device back...

Страница 19: ...the device until the ambient temperature is back in the given range If the temperature does not stay in the correct range make sure that there is insulation around the signal converter If this error o...

Страница 20: ...back in the given range If the temperature does not stay in the correct range make sure that there is insulation around the signal converter 93 3 Local Operation The device is in configuration mode A...

Страница 21: ...NOTES 5 21 OPTIWAVE 5200 C www krohne com 10 2013 4003066901 MA OPTIWAVE5200C PA R01 en...

Страница 22: ...5 NOTES 22 OPTIWAVE 5200 C www krohne com 10 2013 4003066901 MA OPTIWAVE5200C PA R01 en...

Страница 23: ...NOTES 5 23 OPTIWAVE 5200 C www krohne com 10 2013 4003066901 MA OPTIWAVE5200C PA R01 en...

Страница 24: ...products Products and systems for the oil gas industry Measuring systems for the marine industry Head Office KROHNE Messtechnik GmbH Ludwig Krohne Str 5 47058 Duisburg Germany Tel 49 0 203 301 0 Fax 4...

Отзывы: