DEVICE DESCRIPTION
2
19
OPTIBAR 5060
www.krohne.com
04/2021 - 4003591803 - AD OPTIBAR 5060 Exia R03 en
The intrinsically safe circuits are galvanically isolated from parts which can be grounded.
The metallic parts of OPTIBAR * 5060 VGK5/6/D*A/W/V C/U/0/H/T are electrically connected with
the ground terminals.
For applications requiring equipment category 1G or 1/2G, the intrinsically safe supply and
signal circuits must correspond to protection level ia.
For applications that require equipment category 1G or 1/2G, it is preferable to connect the
OPTIBAR * 5060 VGK5/6/D*A/W/V C/U/0/H/T to appropriate equipment with galvanically isolated,
intrinsically safe circuits.
Intrinsically safe circuit for the display and adjustment module
OPTIBAR * 5060 VGK5/6/D*A/W/V C/U/0/H/T with integrated electronics P (Profibus PA),
F (Foundation Fieldbus), version with double chamber housing D, W or R
Circuit for the display and adjustment
module: (spring contacts in the "Ex-i"
terminal compartment)
In protection type intrinsic safety Ex ia IIC
Only for connection to the display and adjustment module.
Circuit for the display and adjustment
module: (spring contacts in the "Ex-i"
electronics compartment)
In protection type intrinsic safety Ex ia IIC
Only for connection to the display and adjustment module.
In the double chamber housing version, the display and
adjustment module in the terminal compartment should only
be equipped if there is no external display unit or
OPTIBAR * 5060 with electronics S or T connected.
Table 2-16: Intrinsically safe circuit for the display and adjustment module
OPTIBAR * 5060 with integrated electronics P or F, version with double chamber housing D, W or R