MENU INDICATOR M10
7
41
BW25
www.krohne.com
10/2008 • 4000432301 MA BW25 R01 en
Level
Designation
Selection/input
options
Explanation
1.5.1
Inactive
1.5.2
RESET
ERROR
YES - NO
2.1
4-20mA OUT
The analog current output can be set to fixed values in 10 %
steps between 4.00...20.00 mA. This function has no
influence on binary switching outputs.
Note
Note
Note
Note
This test function is switched off in multidrop mode.
Display: "NOT AVAILABLE".
2.2
OUTPUT B1
OPEN
The function assignment in menu 3.2 is not taken into
consideration here.
CLOSED
2.3
OUTPUT B2
OPEN
The function assignment in menu 3.3 is not taken into
consideration here.
CLOSED
2.4
Inactive
3.1
LANGUAGE
ENGLISH
DEUTSCH
FRANCAIS
ITALIANO
ESPANOL
CESKY
POLSKI
NEDERLANDS
3.2
FUNCTION B1
INACTIVE
Output B1 is switched off.
SWITCHING
POINT
The output B1 switches at a set value depending on the
current level value.
3.3
CONTACT B1
NC contact
Output B1 is normally closed. If an alarm situation occurs,
the contact opens.
NO CONTACT
Output B1 is normally open. If an alarm situation occurs,
the contact closes.
3.4
FUNCTION B2
INACTIVE
See FUNCTION B1
SWITCHING
POINT
See FUNCTION B1
3.5
CONTACT B2
NC CONTACT
See CONTACT B1
NO CONTACT
See CONTACT B1
3.6
Inactive
3.7
Inactive
3.8
Inactive