Tel:
+44 (0)1274 657 088
Fax:
+44 (0)1274 657 087
Web:
www.cromptonlamps.com
Images are for information only. Phoebe LED shall not be held liable for improper operation of the luminaire
in circumstances where procedures and specifications have not been followed correctly. Crompton Lamps Limited 2020
TESTING
24hrs Initial charge time required.
The emergency lighting must be inspected and tested regularly in accordance
with local codes of practice:
note:
for safety reasons tests should be carried out during daylight hours.
AFTER INSTALLATION
Allow 24 hours to ensure full battery charge and then interrupt the supply; the
maximum duration time is 3 hours check that LEDs are still lighting.
FUNCTIONAL TEST (Short)
Monthly, interrupt mains for a short period and check LED lights.
DURATION TEST
Full duration test should be carried out annually, interrupt mains and check LED
lights. LEDs will light and should last for a minimum 3 hours operation:
batteries must be replaced when they can no longer support 3 hour operation.
LED
STATUS
COMMENT
Green
Standby, system ok
Mains operation, battery charging
Off
Battery Operation
Emergency mode:
Mains disconnected or Mains failure
INDICATOR LED
System status is shown locally by the indicator LED.
INSTALLATION MAINTENANCE RECORD
Month
TEST
Year 1
Year 2
Year 3
Year 4
(Out of Warranty)
Signed
Date
Signed
Date
Signed
Date
Signed
Date
1
Short
2
Short
3
Short
4
Short
5
Short
6
Short
7
Short
8
Short
9
Short
10
Short
11
Short
12
Short
3 Hr
Installer
Installation Date
Installation Test Date