FAULT DIAGNOSIS
(parts are identifi ed on wiring diagram)
Fault
Possible
cause
Repairment
Unit does not start
No power supply
Test power supply
Broken main fuse
Replace main fuse
Transformer fuse broken
Replace transformer fuse
Temperature controller
Replace temperature
broken
controller
Fluid temperature
Testing of correct
outside min. or max.
temperature setting
allowable
values
Fluid (water, oil)
temp. too high
Clogged or dirty air fi lter
Replace air fi lter
Dirty evaporator
Clean evaporator
Dirty condensor
Clean condensor
Refrigerant leakage
Repairement only by
(bubbles in sight glass)
refrigeration specialist
Temp.controller setting
Re-adjustment of temp.
incorrect
controller
Water level in tank too low
Testing of waterlevel
refi lling of tank
Ambient temp. too high
Refer to technical
specifi cation or chapter 3
Consumer capacity too high Test consumer capacity and
compare with chiller capacity