Operating Instructions
15
Fault
Possible
cause
Repairement
Overload tripped
Resetting of overload
Current of the specifi c
Testing of current (ampere),
part too high
replace defect part
Burnt or broken cable
Repair broken cable
Loose connection
Tighten all contacts and terminals
Insuffi cient power supply
Test power supply
Option:
Flow switch tripped
Flow switch dirty
Clean fl ow switch
Flow switch defect
Replace fl ow switch
Pump defect
Replace pump
Pump rotation -
Testing of correct pump rotation,
wrong way around
see arrow on pump
Fluid (water, emulsion, oil)
Testing of suffi cient fl uid in system
level too low
and damaged or clogged up piping
Option
Test the setting of the
Anti-freeze
Anti-freeze
thermostate
thermostat
Fluid (water, emulsion, oil)
Testing of correct temperature
temperature
too
low
setting on controller
controller defect
Option:
fl oat switch tripped
Water level in tank too low
Testing of waterlevel, refi lling of tank
Float switch defect
Replace fl oatswitch
(parts are identifi ed on the wiring diagram)
5
FAULT DIAGNOSIS
Содержание Chilly
Страница 21: ...20 Operating Instructions FOR YOUR NOTICE ...
Страница 33: ......
Страница 34: ......
Страница 35: ......