Table 2. Minimum distances to combustible materials requirements for installation
Depth (under the
bottom of appliance)
Width up to height of
the appliance installation
Width above the
appliance
Height
AQF 01
700 mm
150 mm
400 mm
1500 mm
AQF 02
700 mm
100 mm
400 mm
1500 mm
AQF 03
700 mm
100 mm
400 mm
1500 mm
AQF 04
700 mm
100 mm
400 mm
1500 mm
AQF 05
700 mm
100 mm
400 mm
1500 mm
AQF 06
700 mm
100 mm
400 mm
1500 mm
AQF 07
700 mm
100 mm
400 mm
1500 mm
MAX HEIGHT:
Burner cannot be placed higher than 1000 mm above the ground. Minimum depth and
width and maximum height of the appliance must be preserved. Failure to meet the above conditions
will result in the loss of warranty and may lead to dangerous situations such as tipping over the device,
fire or loss of health.
PLEASE NOTE:
If all of these conditions cannot be met, the installation of the device is prohibited.
In such situation, contact the manufacturer to select a dedicated body for the purchased appliance,
which has been tested for safety by the manufacturer.
Table 3. Minimum distances to noncombustible wall of the housing.
Installation requirements
Depth (under the
bottom of appliance)
Width up to height of
the appliance installation
Width above the
appliance
Height
AQF 01
700 mm
100 mm
150 mm
700 mm
AQF 02
700 mm
100 mm
150 mm
600 mm
AQF 03
700 mm
100 mm
150 mm
600 mm
AQF 04
700 mm
100 mm
150 mm
600 mm
AQF 05
700 mm
100 mm
150 mm
600 mm
AQF 06
700 mm
100 mm
150 mm
600 mm
AQF 07
700 mm
100 mm
150 mm
600 mm
The housing made of noncombustible materials must still have at least one of the side walls above
the appliance open.
Noncombustible housing does not exempt the customer to keep the minimum
distances to combustible materials behind the non-combustible walls as per the tables above! Non-
combustible housing cannot be bolted to the combustible wall directly if the minimum required
distances to the combustible materials would not be matched.
Each gas garden fireplace, regardless of the version that was finally selected, must be installed in a
bore made to size as shown in the table below. The minimum dimension of the insulation / table top
made of non-combustible materials according to the diagram above is 150 mm from the outer edge of
the fireplace frame.
Содержание AQF 01
Страница 4: ...WYMIARY URZ DZENIA AQF 01 AQF 02...
Страница 5: ...AQF 03 AQF 04...
Страница 6: ...AQF 05 AQF 06...
Страница 7: ...AQF 07 Rys 1 Zwymiarowane rysunki wszystkich wariant w ogrodowego paleniska gazowego...
Страница 19: ...Rys 4 Schemat pod czenia systemu r cznego sterowania gazem...
Страница 32: ...APPLIANCES DIMENSIONS AQF 01 AQF 02...
Страница 33: ...AQF 03 AQF 04...
Страница 34: ...AQF 05 AQF 06...
Страница 35: ...AQF 07 Fig 1 Dimensional drawings of all variants of the gas garden fireplace...
Страница 47: ...Fig 3 Connection diagram for the manual gas control system...