8 Installation, removal
8.3 Mounting the pump station
8.3 Mounting the pump station
Notice
Soiling in the pipe system impairs the service life of the pump station. If the pipe system is flushed us-
ing the pump station during the initial commissioning, an additional commissioning filter has to be in-
stalled temporarily before the pump station. Alternatively the strainers supplied as standard can be re-
placed during commissioning by fine-meshed commissioning strainers.
Personnel qualification:
o
Transport personnel
o
Fitter
Personal protective equipment:
o
Work clothing
o
Protective gloves
o
Safety boots
Aids:
o
Mobile crane, forklift, hoisting equipment
WARNING
Risk of injury and damage to equipment through falling and toppling parts.
► Only fasten the pump station on a stable bearing underground.
► Ensure that fastening elements and pipings are fastened sufficiently.
ATTENTION
Damage to device through impurity in the pipe system.
► During welding work attach protective covers in front of the connecting flanges.
► Ensure when welding that welding beads and abrasive dust cannot get into the pipe system and
the pump station.
► Ensure that a commissioning filter is installed when the pipe system is flushed and cleaned using
the pump.
Requirement:
ü
Pump station connections protected against soiling, for example by using the protective cover
mounted in the factory
1.
Bring the pump station into the installation position.
2.
Fasten the pump station with fastening elements securely on the underground.
After the connecting work clean the pipe system thoroughly
Ä
Commissioning, Page 23.
8.4 Protecting the pump station against pressure peaks
ATTENTION
Damage to the plant components through pressure peaks.
► Use pulsation damper.
Notice
The pulsation damper is available as an option from the manufacturer.
Install the pulsation damper in the pipe system.
-or-
Mount the pulsation damper on the pump station.
18
OIK 10en-GB Edition 2021-06
Operation instructions