INSTALLATION 

15

6.0  INSTALLATION

6.1  Approved Vent Systems

Kozy Heat #816 and #816-CAP 

For use with minimum 6” x 8” I.D. masonry or 7” I.D. Class A metal 
chimneys; includes one roll of 36’ (10.97 m) of expandable 3” flexible pipe 
and round termination cap. 

Other approved vent manufacturers 

BDM, American Metals (Amerivent), Metal Fab, Selkirk, Simpson Dura-
Vent, and ICC.

6.2  Kozy Heat #816 and #816-CAP

IMPORTANT: Proper operation of this insert requires the exhaust pipe 
and combustion air pipe to be connected to their correct flue collar, on 
both the termination kit and the gas fireplace insert vent adapter.
The fireplace insert exhaust flue collar is located on the right side. 
Install termination cap with the exhaust flue collar on the right side. 
NOTE: The exhaust pipe will have a red marking.
IMPORTANT:  Maximum horizontal vent runs of 24 in (609 mm) require 
a 1 in (25mm) rise per 12 in (305 mm) run. Care should be taken when 
installing the flexible vent pipes to avoid a tight bend that may cause 
abrasion or damage to the flexible pipes.

1.  Measure the total chimney length required  and cut #816 (36’ 

[10.97m] of 3” flexible pipe) to the measured length. 

2.  Carefully extend the exhaust and combustion air intake pipes to 

total chimney length required.

3.  Slide the combustion air intake pipe (the end without a collar) 

over termination cap collar (A). Secure to #816-CAP termination 
cap (E) with (3) self-tapping screws (not provided).

4.  Place a bead of sealant around the inner edge at the end of the 

exhaust pipe (without collar / red marking) and slide onto the 
corresponding labeled collar (B) on termination cap (E).

5.  Secure the exhaust pipe to termination cap (E) with (3) self-

tapping screws (not provided). Apply additional sealant around 
joint to ensure a proper seal.

6.  Complete vent system installation by following the instructions 

outlined in Sections 6.3 through 6.6.

COMBUSTION AIR 
INTAKE 3” FLEX LINER

EXHAUST VENT 
3” FLEX LINER

USES #816 36 ft (10.97m) EXPANDABLE 3” FLEXIBLE PIPE

C

A

B

D

C

#816 and #816-CAP

(A)

  Intake Collar (extends 

through bottom plate)

(B)

  Exhaust Collar (extends 

through middle divider 

plate)

(C)

  Sealant (not provided)

(D)

  #816-CAP Termination Cap

VENT ADAPTER (TOP VIEW)

COMBUSTION AIR

INTAKE COLLAR (LEFT)

EXHAUST COLLAR (RIGHT)

Figure 6.1, #816-CAP

Содержание ROOSEVELT 29 BW

Страница 1: ...manufactured home USA only or mobile home where not prohibited by local codes This appliance is only for use with the type of gas indicated on the rating plate This appliance is not convertible for u...

Страница 2: ......

Страница 3: ...being dedicated not only to functionality and reliability but also customer safety We offer our continual support and guidance to help you achieve the maximum benefit and enjoyment from your Kozy Heat...

Страница 4: ......

Страница 5: ...ace and Secure Appliance 17 7 0 GAS LINE CONNECTION 18 7 1 Gas Conversion sold separately 18 7 2 Gas Line Installation 18 8 0 FACING AND FINISHING 19 8 1 Clearances to Combustibles 19 8 2 Shroud Insta...

Страница 6: ......

Страница 7: ...y period a battery operated carbon monoxide detector with an alarm shall be installed 1 3 2 Approved Carbon Monoxide Detectors Each carbon monoxide detector as required in accordance with the above pr...

Страница 8: ...e installed at higher altitudes Please refer to National Fuel Gas Code ANSI Z223 1 NFPA 54 CSA B149 1 Natural Gas and Propane Installation Code local authorities or codes having jurisdiction in you ar...

Страница 9: ...TIONS 9 2 2 Appliance Dimensions Figure 2 1 Appliance Dimensions 201 16 510mm 16 406mm 2711 16 703mm 295 8 753mm 197 8 505mm 1715 16 456mm 13 16 31mm 14 356mm 6 172mm 11 8 28mm 129 16 319mm 33 16 81mm...

Страница 10: ...roved parts with this appliance may result in property damage or personal injury Figure 2 2 Proper Positioning of Appliance Table 2 1 Field Assembled Parts A Fireplace insert G Burner air flow plate B...

Страница 11: ...th Hussong Mfg s barriers for this appliance Only doors certified with the appliance shall be used IMPORTANT Consider the height of hearth finish material when building a fireplace platform Proper ins...

Страница 12: ...D label at bottom of existing firebox so it will be visible if this gas fireplace insert is removed 3 2 1 1 Existing Fireplace Opening Minimum Requirements If installing the RT29 FLP add 3 4 19mm tota...

Страница 13: ...1 Vent Termination Clearances WARNING This appliance must not share or be connected to a chimney flue serving any other appliance Approved vent caps require 12 in 305mm clearance to intersecting wall...

Страница 14: ...ce has no gas access hole s provided an access hole of 1 in 37 5 mm or less may be drilled through the lower sides or bottom of the firebox in a proper workmanship like manner The access hole must be...

Страница 15: ...y cause abrasion or damage to the flexible pipes 1 Measure the total chimney length required and cut 816 36 10 97m of 3 flexible pipe to the measured length 2 Carefully extend the exhaust and combusti...

Страница 16: ...through the chimney place unfaced insulation around the first 3 ft 914 mm of vent system below termination cap Secure with wire 2 Install the 3 x 3 flexible pipes down through existing chimney Guide...

Страница 17: ...appliance is properly positioned Figure 6 4 Aligned Insert 6 5 Connect Vent Pipe to Vent Adapter IMPORTANT Proper operation of this insert requires the exhaust pipe and combustion air pipe to be conne...

Страница 18: ...m tee handle manual shut off valve and flexible gas connector are to be connected to the in 13 mm control valve inlet If substituting for these components please consult local codes for compliance If...

Страница 19: ...Clearances to Combustibles IMPORTANT Adequate accessibility clearances for servicing and proper operation must be maintained COMBUSTIBLE MATERIAL 4 102mm 12 305mm 9 229mm 11 286mm 8 210mm 281 8 714mm...

Страница 20: ...Align leg section holes on the shroud to the corresponding mounting nuts in mounting brackets on each side of the insert metal cabinet 3 Secure with 4 phillips truss head screws provided 4 Reinstall...

Страница 21: ...s assembly into position 2 Using the glass latch tool pull latches out and down over latch tabs to secure glass frame assembly bottom 9 2 Light Kit CAUTION Disconnect all electrical power from the fir...

Страница 22: ...along the front of the plate positions at the bottom of the firebox Tilt the bottom of the plate in first The plates will install along the side of the burner and sit on the firebox floor 2 Install t...

Страница 23: ...nversion before installing the log set Follow the conversion instructions included with the kit Log numbers located on the bottom of each log Refer to following instructions and illustrations for prop...

Страница 24: ...ol board on the left side of the firebox 12 Pull out control board out to reveal gas line to disconnect the gas line flex tube from fireplace valve 9 5 2 Control Board Installation 1 Place control boa...

Страница 25: ...ceptacle Do not cut or remove the grounding prong from this plug 10 1 Electrical Specifications This appliance when installed must be electrically grounded in accordance with local codes or in the abs...

Страница 26: ...an ignition device which automatically lights the pilot Do not try to light the pilot by hand 5 Locate the manual valve installed by your qualified service technician 6 Turn the manual valve clockwis...

Страница 27: ...control operation of the main burner and fireplace features 11 3 Reset the System for Manual Operation 1 Set the ON OFF rocker switch to OFF position 2 Press the remote sync button on the IFC module u...

Страница 28: ...h to the OFF position 2 After approximately 2 seconds move the switch to the ON position The ignition sequence will start again 11 6 1 2 Remote Control ON OFF Key 1 Press the remote control ON OFF key...

Страница 29: ...ark to pilot system to the standing pilot option The standing pilot will keep the firebox warm and establish a draft in the vent which allows the main burner to ignite with less air flow disruption Wh...

Страница 30: ...off key and the mode key at the same time 4 Reinsert 1 AAA battery 5 While still holding the on off key let go of ONLY the mode key 6 Index over to the flame graphic on the LCD screen to edit Use the...

Страница 31: ...replace before fan operation The fan will continue to operate for approximately 12 minutes after the fireplace has been turned off Manual mode Fan s will operate at previous setting There is no delay...

Страница 32: ...mum and maximum recommended pressure settings 4 Turn off burner and pilot 5 Disconnect hose and tighten the inlet IN pressure tap by turning screw clockwise Screw should be snug Do not over tighten 6...

Страница 33: ...3 Factory Set Venturi Openings Fuel FRONT BACK Natural Gas 1 16 1 5 mm OPEN 1 16 1 5 mm OPEN Propane 3 8 9 5 mm OPEN 3 8 9 5 mm OPEN 12 2 1 1 Venturi Adjustment NOTE If soot is present on the glass c...

Страница 34: ...Do not over tighten Pilot flame always on or will not extinguish Control system set to CPI mode Set control system to IPI mode Main burner flame will not light ON OFF rocker switch in OFF position Swi...

Страница 35: ...nturi setting Venturi air shutter may need to be opened slightly to allow more air into the gas mix Refer to section 12 2 1 Burner Venturi on page 33 Incorrect vent cap installation Adjust if necessar...

Страница 36: ...uctions provided with installation Refer to Section 6 0 on page 15 Performed by Qualified Service Person Frequency Annually Action Examination of the vent system is required The flow of combustion and...

Страница 37: ...ion device Visually check pilot light when in operation Inspect and ensure the lighting of the main burner occurs within 4 seconds of the main gas valve opening Check for faulty or incorrect wiring an...

Страница 38: ...T IPI Gas Valve Propane 700 567 1 Valve Step Motor Propane 700 504 1 Proflame 2 IFC Board 700 652 15 in Flexible Gas Line Black 700 227f IFC Wire Harness Assembly 700 653 Flexible Gas Line Valve to Bu...

Страница 39: ...f but not limited to improper chimney venting installation will also render this warranty void 7 This warranty does not cover installation and operational related problems such as environmental condit...

Отзывы: