#NDK-34-i R.1 July 2022
Hussong Mfg. Co., Inc. Kozy Heat Fireplaces
INSTALLATION
17
6.2
Kozy Heat #816 and #816-CAP
IMPORTANT: Proper operation of this insert requires the exhaust pipe
and combustion air pipe to be connected to their correct flue collar, on
both the termination kit and the gas fireplace insert vent adapter.
The fireplace insert exhaust flue collar is located on the right side.
Install termination cap with the exhaust flue collar on the right side.
IMPORTANT: Maximum horizontal vent runs of 24” (609mm) require
a 1” (25mm) rise per 12” (305mm) run. Care should be taken when
installing the flexible vent pipes to avoid a tight bend that may cause
abrasion or damage to the flexible pipes.
1.
Measure the total chimney length required. If needed,
carefully extend the pipes, and cut to the measured length.
2.
Slide the combustion air intake pipe over combustion air intake
collar (A) and secure with (3) self-tapping screws (not
provided).
3.
Place a bead of high temperature sealant around the base of the
exhaust vent collar (B). Slide the exhaust pipe over the collar and
into the high temperature sealant. Secure with (3) self- tapping
screws (not provided). Mark the opposite end of the exhaust pipe for
easy identification during the installation.
4.
Complete vent system installation by following the instructions
outlined in Sections 6.7 through 6.9.
Figure 6.1, #816 and #816-CAP
6.3 Restrictor Plate Assembly and
Installation
A restrictor plate (included in components packet) may be used to
achieve desired flame appearance on any venting installation with at
least 25 ft. (7.62m) of vertical pipe or more.
Restrictor plate installation