82

Platinum Bio ecoMAX 860P  

User Manual – EN 03.17

Leader in pellet boilers

 15. Service settings

15. Service settings

15.1 Burner

Burner settings

Startup
Heating time

Igniter heating time before fan activation. Heating time cannot be too long to avoid damage to the heater.  
After the heating time elapses, the heater is enabled until the increase in flue gas temperature is detected.

Start fuel charge

Fuel charge fed during startup. Applies to first startup attempt. The fuel charge is smaller in subsequent tests.

Flame detection

Flame detection threshold in light percentage at which the controller treats the furnace as
started. Also, used as a no flame detector.

Startup blow-in

Blow-in percentage at startup. Note: high value will extend the startup time or will result in failed startup attempt

Startup time

Subsequent startup attempt time After that time, the controller makes another startup attempt (max. 3 attempts).

Operation
Maximum burner power

Burner power setpoint in OPERATION mode.

Maximum FL burner power

Maximum burner power in Fuzzy Logic mode.

Minimum FL burner power

Minimum burner power in Fuzzy Logic mode.

Blow-in settings

Nominal/intermediate/minimum blow-in power - fan blow-in power for burner operation at
nominal/intermediate and minimum power.
Oxygen at nominal/intermediate power - flue gas oxygen content at nominal/intermediate burner power.  
Intermediate power - H2 hysteresis - temperature transition threshold between maximum and intermediate 
burner power. Minimum power - H1 hysteresis - temperature transition threshold between intermediate and 
minimum burner power. Boiler hysteresis - if the boiler temperature is reduced below the boiler temperature 
setpoint by the boiler hysteresis, the burner is started automatically. 

Cycle time in OPERATION mode

Fuel feeding cycle time in OPERATION mode. OPERATION cycle time = OPERATION mode feeding time  
+ feeder idle time

Monitoring time

After the monitoring time elapses, the controller switches to SHUTDOWN and then to STAND-BY mode. If Monito-
ring time = 0, the controller omits MONITORING mode and switches to SHUTDOWN mode. If Monitoring time = 
255, the controller operates in MONITORING mode, until the boiler temperature decreases to the level at which it 
switches to OPERATION mode.

Feeder output

Feeder output in kg/h. Enter measured fuel weight at constant fuel feeding (continuous fuel feeder operation). The 
parameter does not affect boiler operation and is used to calculate the fuel level and the boiler power.

Fuel calorific value

Fuel calorific value in kWh/kg. This parameter is for information only. The parameter does
not affect boiler operation and is used to calculate the fuel level and the boiler power.

Operation with the oxygen sensor

If set to „ENABLED”, controller will operate using oxygen sensor data. A volume of air delivered to the furnace will 
be automatically determined to achieve a preset oxygen content in the flue gas. If set to „DISABLED”, oxygen sensor 
indications will not affect the controller operation.  

Cleaning
Max. linear actuator operation time

Maximum operation time for linear actuator.

Linear actuator extended

Voltage level corresponding to extended linear actuator.

Linear actuator retracted 

Voltage level corresponding to retracted linear actuator.

Ash removal time 

Duration of ash removal to the feeder screw trough and the central ash container.

Heat exchanger cleaning time 

Heat exchanger cleaning duration

Содержание Platinum Bio ecoMAX860P3-O TOUCH (VG)

Страница 1: ...Platinum Bio ecoMAX860P3 OTOUCH VG USER MANUAL RU EN...

Страница 2: ......

Страница 3: ...RU EN USER MANUAL 5 49...

Страница 4: ......

Страница 5: ...Platinum Bio ecoMAX860P3 OTOUCH VG R U...

Страница 6: ......

Страница 7: ......

Страница 8: ......

Страница 9: ......

Страница 10: ......

Страница 11: ......

Страница 12: ......

Страница 13: ......

Страница 14: ......

Страница 15: ......

Страница 16: ......

Страница 17: ......

Страница 18: ......

Страница 19: ......

Страница 20: ......

Страница 21: ......

Страница 22: ...Platinum Bio ecoMAX860P3 OTOUCH VG...

Страница 23: ......

Страница 24: ......

Страница 25: ......

Страница 26: ......

Страница 27: ......

Страница 28: ......

Страница 29: ......

Страница 30: ......

Страница 31: ......

Страница 32: ......

Страница 33: ......

Страница 34: ......

Страница 35: ...5...

Страница 36: ......

Страница 37: ......

Страница 38: ......

Страница 39: ......

Страница 40: ......

Страница 41: ......

Страница 42: ......

Страница 43: ......

Страница 44: ......

Страница 45: ......

Страница 46: ......

Страница 47: ......

Страница 48: ......

Страница 49: ...Leader in pellet boilers Platinum Bio ecoMAX860P3 O TOUCH VG controller User Manual E N G L I S H E N...

Страница 50: ...50 Platinum Bio ecoMAX 860P User Manual EN 03 17 Leader in pellet boilers...

Страница 51: ...choosing KOSTRZEWA equipment top quality device manufactured by a renowned and highly valued company both in Poland and abroad The KOSTRZEWA company was established in 1978 From the very beginning the...

Страница 52: ...52 Platinum Bio ecoMAX 860P User Manual EN 03 17 Leader in pellet boilers...

Страница 53: ...4 4 Storing documents 54 5 Symbols and designations 54 6 WEEE Directive 2002 96 WE 54 7 User menu 55 8 Operation 57 9 Alarm description 63 Platinum Bio ecoMAX 860P controller Service manual 65 10 Hydr...

Страница 54: ...out of reach of children 2 General The controller is a device for controlling an operation of a boiler with an automatic solid fuel feeder and an igniter The flame is detected by an optical flame brig...

Страница 55: ...temperature sensor CH sensor Continuous pump Boiler settings Boiler temperature setpoint Boiler outdoor temperature compensation Boiler heating curve Curve translation Room temperature coefficient Po...

Страница 56: ...ings 2 3 Mixing valve temperature setpoint Mixing valve room thermostat Mixing valve outdoor temperature compensation Mixing valve heating curve Curve translation Room temperature coefficient Mixing v...

Страница 57: ...perature weather compensation 9 values affecting temperature setpoint room thermostat contacts open room temperature setpoint not reached temperature setpoint decreased by active intervals boiler temp...

Страница 58: ...vice settings Burner settings Operation Feeder operation time is determined automatically based on the required current burner power feeder output and fuel calorific value OPERATION mode parameters ca...

Страница 59: ...leaning settings Burner cleaning settings can be modified in Boiler settings Cleaning Continuous burner operation time after which it is automatically shut down cleaned and started again is set in Bur...

Страница 60: ...k hysteresis DHW pump is activated to charge the DHW storage tank AT LOW HYSTERESIS SETTING DHW PUMPWILL ACTIVATE QUICKER AFTERTHE DHWTEMPERATURE DECREASES 8 17 DHW circulation The settings can be mod...

Страница 61: ...too high room temperature may fluctuate 8 20 Outdoor temperature compensation Depending on the measured outdoor temperature both the boiler temperature setpoint and the mixing valve circuit temperatur...

Страница 62: ...rrent fuel level value the following message is displayed Set fuel level to 100 PressYES to set fuel level to 100 Note The fuel can be added anytime i e there is no need to wait for the fuel storage t...

Страница 63: ...ith room temperature controller The controllers are compatible with ecoSTERTOUCH room temperature controller with room thermostat function The room temperature controller provides useful information f...

Страница 64: ...ected to the electronics via a digital communication link RS485 If cable is damaged Caution No communication alarm is displayed The controller continues operation with programmed parameters Check repl...

Страница 65: ...Leader in pellet boilers Platinum Bio ecoMAX860P3 O TOUCH VG controller SERVICE manual E N G L I S H E N...

Страница 66: ...valve circuit pump 8 CT4 mixing valve circuit temperature sensor 9 DHW storage tank 10 DHW pump 11 temperature sensor CT4 DHW 12 CT6 P weather compensator 13 ecoSTERTOUCH room temperature controller w...

Страница 67: ...1 settings Select mixing valve 1 thermostat ecoSTERT1 menu service settings mixing valve 1 settings Diagram with two controlled heating circuits and DHW storage tank 10 Hydraulic diagrams 1 boiler 2...

Страница 68: ...ng valve 2 heating curve 0 3 0 8 menu mixing valve 2 settings Mixing valve 2 outdoor temperature compensation ON menu mixing valve 2 settings Select mixing valve 2 thermostat ecoSTERT1 menu service se...

Страница 69: ...ture compensation ON menu mixing valve 1 settings Select mixing valve 1 thermostat ecoSTERT1 menu service settings mixing valve 1 settings Mixing valve 2 control Floor heating ON menu service settings...

Страница 70: ...in and sunlight Storage and transport temperature must not exceed 15 65 C Do not expose to vibrations above those occurring in standard vehicle traffic conditions 13 Installing controller 13 1 Environ...

Страница 71: ...g terminals Standard enclosure may be used User has access to the module front panel only The module can also be installed in the boiler components enclosing the entire module The enclosure does not p...

Страница 72: ...als 1 21 are used for connecting devices which require 230V mains supplyTerminals22 49areusedforconnectinglowvoltagedevices upto12V CONNECTION CABLES MUST NOT CONTACT ANY SURFACESWITH TEMPERATURE HIGH...

Страница 73: ...module variant O module B GRATE ACTUATOR MALE CONNECTOR GREEN MALE CONNECTOR TURQUOISE MALE CONNECTOR BLUE BLUE ORANGE SYSTEM ENCLOSURE BURNER TEMP BLOWER GEAR MOTOR HEATER TERMINAL BLOCK FEMALE CONNE...

Страница 74: ...74 Platinum Bio ecoMAX 860P User Manual EN 03 17 Leader in pellet boilers 13 Installing controller Wiring diagram for ecoMAX860P3 OTOUCH VG controller...

Страница 75: ...75 Platinum Bio ecoMAX 860P User Manual EN 03 17 Leader in pellet boilers 13 Installing controller Wiring diagram auxiliary module B to ecoMAX860P3 OTOUCH VG controller...

Страница 76: ...auxiliary boiler control alarm signaling or DHW circulation pump control AC ash removal motor HWP DHW circulation pump BC cleaning motor PM C CH pump circuit C GC grate actuator SM C CH mixing valve c...

Страница 77: ...ters above the ground at least 1 5 m from windows chimneys and other heat sources which may affect temperature measurements Use min 0 5 mm2 cables with length up to 25 m Cable polarity is not relevant...

Страница 78: ...nstaller in accordance with the boiler documentation The auxiliary boiler should be connected via a relay to the terminals 46 47 Example wiring diagram 1 controller 2 auxiliary boiler gas or oil 3 rel...

Страница 79: ...lve circuit temperature is minimum corresponds to 0 OFF position of the controller Note the position for verification purposes disconnect the controller power supply connect the mixing valve actuator...

Страница 80: ...alorificvalue Operationwithoxygensensor ON OFF Cleaning Max linearactuatoroperationtime Linearactuatorextended Linearactuatorretracted Ashremovaltime OFF Heatexchangercleaningtime OFF Variable grate g...

Страница 81: ...ffer tank control Charging start temperature Charging end temperature Heating system start Mixing valve 1 5 settings 1 Mixing valve control Select thermostat Mixing valve minimum temperature Maximum m...

Страница 82: ...s if the boiler temperature is reduced below the boiler temperature setpoint by the boiler hysteresis the burner is started automatically Cycle time in OPERATION mode Fuel feeding cycle time in OPERAT...

Страница 83: ...not use this parameter after fuel level calibration Fuel level sensor Enabling the fuel level sensor means that after low fuel level is detected the controller will automatically shutdown after burni...

Страница 84: ...ted It protects the boiler against condensation due to the cooling with cold water returning from the system Note deactivating the boiler pump does not guarantee boiler protection against condensation...

Страница 85: ...ode or DHW priority mode NO boiler pump works normally 15 4 Buffer tank Buffer tank setting Buffer tank control Activates operation mode with buffer tank Charging start temperature Charging start temp...

Страница 86: ...ration time constant The higher the value the slower the actuator response to temperature deviation If the value is too low it may cau se unnecessary actuator movement if the value is too high it will...

Страница 87: ...re is below 5 C the boiler pump is activated to force circulation of the boiler water If the temperature does not increase the burner is activated THIS FUNCTION MAY NOT BETHE SOLE PROTECTION AGAINST F...

Страница 88: ...earactuatorretracted Ashremovaltime OFF Heatexchangercleaningtime OFF Variable grate geometry Control Actuatoratnominalpower Actuatoratminimumpower Linearactuatordelay Actuatorstrokeatreturn Burnerstr...

Страница 89: ...tings Buffer tank control Charging start temperature Charging end temperature Heating system start Mixing valve settings 1 Mixing valve control Select thermostat Mixing valve minimum temperature Maxim...

Страница 90: ...pump nighttime setback Mixing valve settings 1 Mixing valve temperature setpoint Mixing valve room thermostat Mixing valve outdoor temperature compensation Mixing valve heating curve Curve translation...

Страница 91: ...91 Platinum Bio ecoMAX 860P User Manual EN 03 17 Leader in pellet boilers Notes...

Страница 92: ...92 Platinum Bio ecoMAX 860P User Manual EN 03 17 Leader in pellet boilers Notes...

Страница 93: ...93 Platinum Bio ecoMAX 860P User Manual EN 03 17 Leader in pellet boilers...

Страница 94: ......

Отзывы: