65
Mini Bio
and
Mini Bio Luxury
User Manual - ENGV 08.15
Experts in heating
5.
Design
guide
l
ines
Fig. Boiler location in the boiler room - dimension diagram
5.B Boiler room requirements
a) Boiler foundation min.0.05 m
Boiler foundation requirements:
³
the foundation must protrude over the boiler room floor
³
the foundation edges must be secured with steel angle sections
b) Boiler room floor
Boiler room floor requirements:
³
the boiler room must be made of non-flammable materials,
resistant to extreme temperature changes and impact
³
the floor must descend in the well direction
c) Boiler room ventilation
Boiler room ventilation requirements:
³
do not use mechanical ventilation system in the room with solid
fuel furnace if the combustion air is supplied directly from the
room and the flue gas is discharged gravitationally via a duct
from the device
³
the boiler room must be fitted with a ventilation duct with a cross
section of at least 50% of the flue cross sectional area, min.
20x20 cm
³
the boiler room must be fitted with a ventilation duct with a cross
section of at least 25% of the flue cross sectional area with the
outlet under the boiler room ceiling
³
the outlet duct cross section must be min. 14x14 cm
³
the vents must be made of non-flammable materials
5.C Hydraulic system requirements
³
the hydraulic system must be made in accordance with the good
building practices, relevant standards and regulations, and the
design input
³
the boiler may operate in a sealed heating system (sealed
diaphragm tank) provided that the boiler supply and return line is
fitted with a dual action relief valve
³
a pressure reducer must be installed with a relief valve to avoid
safety valve opening in case of a rapid increase in boiler water
pressure
³
an expansion tank must be installed in the highest point of the
heating system and protected against frost
³
the expansion tank should be installed at the boiler return
³
to guarantee proper working conditions and failure free boiler
operation, ensure a minimum temperature at the boiler return
by installing the boiler pump with a mixing valve (boiler mixing
system)*
³
a temperature sensor of the system protecting against exceeding
permissible temperatures must be installed directly on the boiler
³
the boiler is compatible with water as a medium conforming to
the water quality requirements.
* Water temperature at the boiler return must be min.
45°C to prevent boiler corrosion as a result of undesirable
and excessive flue gas condensation in the boiler.
The boiler circulation pump must be fitted with a control
valve. The pump output must be approx. 40÷50%
of the nominal water flow through the boiler. The boiler
circuit design must guarantee the difference
in temperature between the supply and the return
of max. 15°C.
CAUTION!
The boiler pump must be installed between two
cut-off valves. To protect the pump against high
pressure difference between the suction and discharge:
´TY^_LWW_SPMZTWP][`X[L__SP^d^_PX]P_`]YP^[PNTLWWd
in systems with high water capacity, where the discharge
pressure is very high)
´[]Z_PN__SPMZTWP][`X[L__SP^`N_TZYLRLTY^_
low
pressure
Содержание Mini Bio
Страница 1: ......
Страница 2: ......
Страница 4: ......
Страница 5: ...P O L S K I P L K l a s a k ot awgnormyPN EN303 5 2 0 1 2 K l a s a k ot awgnormyPN EN30 3 5 2 0 1 2...
Страница 6: ......
Страница 8: ......
Страница 26: ...26 Instrukcja Mini Bio i Mini Bio Luxury PLV 08 15 Specjali ci w ogrzewaniu 5 Zalecenia projektowe...
Страница 27: ...27 Instrukcja Mini Bio i Mini Bio Luxury PLV 08 15 Specjali ci w ogrzewaniu 5 Zalecenia projektowe...
Страница 28: ...28 Instrukcja Mini Bio i Mini Bio Luxury PLV 08 15 Specjali ci w ogrzewaniu 5 Zalecenia projektowe...
Страница 45: ...E N G L I S H E N B o i l e r c lass as per EN 303 5 2 0 1 2 B o i l e r class as per EN 303 5 2 0 1 2...
Страница 46: ......
Страница 48: ......
Страница 86: ......
Страница 88: ......
Страница 126: ......
Страница 127: ...Twin Bio PLV 09 13 Twin Bio PLV 09 13 R U PN EN303 5 2 0 1 2 PN EN30 3 5 2 0 1 2...
Страница 128: ......
Страница 130: ......
Страница 135: ...Sp cialistes en chauffage Mini Bio Mini Bio Luxury RUV 08 15 135 3 135 Mini Bio Mini Bio Luxury...
Страница 146: ...Sp cialistes en chauffage Mini Bio Mini Bio Luxury RUV 08 15 146 5 146 5 5 a A 500 B 500 C 500 D 1000 E 2000 F 50...
Страница 148: ...Sp cialistes en chauffage Mini Bio Mini Bio Luxury RUV 08 15 148 5 148 Platinum Bio Mini Bio SYR 5067 GSM...
Страница 149: ...Sp cialistes en chauffage Mini Bio Mini Bio Luxury RUV 08 15 149 5 149 Platinum Bio Mini Bio SYR 5067 GSM...
Страница 150: ...Sp cialistes en chauffage Mini Bio Mini Bio Luxury RUV 08 15 150 5 150 Platinum Bio Mini Bio SYR 5067 GSM...
Страница 154: ...Sp cialistes en chauffage Mini Bio Mini Bio Luxury RUV 08 15 154 6 154 ON 6...
Страница 155: ...Sp cialistes en chauffage Mini Bio Mini Bio Luxury RUV 08 15 155 7 155 7...
Страница 165: ...Sp cialistes en chauffage Mini Bio Mini Bio Luxury RUV 08 15 165 13 165 a STB STB...
Страница 166: ...Sp cialistes en chauffage Mini Bio Mini Bio Luxury RUV 08 15 166 13 166 a...
Страница 167: ...F R A N C E F R C l a s s e d elachaudi re selonEN30 3 5 2 0 1 2 C l a s s e d e lachaudi reselonEN3 0 3 5 2 0 1 2...
Страница 168: ......
Страница 170: ......
Страница 208: ......
Страница 210: ......
Страница 247: ......
Страница 248: ......