VIII. Maintenance

 

 
Kooltronic Water-Cooled Air Conditioners require no maintenance. Air-Cooled Air Conditioners are designed to 
require only the routine cleaning of air filters to assure unimpeded airflow through the condenser heat 
exchanger. It is not possible to recommend specific filter cleaning intervals since the level and the nature 
of airborne particulate matter differs widely with each installation. It is generally sufficient to remove and wash 
the reusable aluminum mesh air filters when the outer surfaces of these filters appear covered with a thin layer 
of dust or lint. Filter recoating adhesive is recommended. Appropriate disposable filters are available from 
Kooltronic. 
 
If filter service is neglected or delayed, the air conditioner will not perform at its design capacity. The first 
indication of excessively clogged air filters is usually a gradual increase of temperature within the equipment 
cabinet. If operation is continued under these conditions, the compressor will be shut off by the thermal 
overload device. The compressor will restart when its external temperature drops below the protector 
threshold setting and the compressor will continue to cycle on and off. Continued operation under these 
conditions will cause damage, shorten compressor life and void the warranty. 

 

A. Filter Removal and Service

 

 

Kooltronic Air Conditioners feature an easily removable inlet filter to facilitate necessary cleaning. 
 

CAUTION 

 
 

 
 
 

1) Lift the filter using the attached tab to clear the lower filter retainer. 
 
2) After removal, the filters should be flushed under warm running water with the clean side up, driving 

contaminants out the dirty side of the filter. If the accumulated dirt is oily, washing in a detergent 
bath is recommended, followed by a warm water rinse as above. 

 
3) The filters may be sprayed with 

Kooltronic A-16 Filter Recoating Adhesive

 to trap fine airborne 

contaminants, or they may simply be dried and reinstalled as strainer type filters. 

Recoating is 

recommended for best results. 

 
4) Reinstall the filter: (a) keeping the tab at the bottom, slide filter into the upper retainer, (b) press filter 

against the unit and, (c) slide down into lower retainer.

Do not operate the Air Conditioner for extended periods of time with the filter removed. 

The condenser coil may become clogged with dust or lint from the air entering the face. 

A clogged condenser coil is not readily detected and will give the same reaction as a 

clogged filter. A clean filter is the best protection.

B. Compressor

 

 

All Kooltronic compressors are approved by UL and CSA, and require no maintenance. They 
are hermetically sealed and charged at the factory, and equipped with automatic-reset thermal overload 
protectors. 

 
If the compressor or the hot gas bypass valve fails, it is strongly recommended that the Air Conditioner 
be returned to Kooltronic for service. 

Содержание TRIMLINE KA4C2.0NP17L

Страница 1: ...L BE READ AND UNDERSTOOD THOROUGHLY KOOLTRONIC INC 30 Pennington Hopewell Road Pennington NJ 08534 609 466 3400 FAX 609 466 1114 www kooltronic com TRIMLINE KA4C2 0NP17L with Serial Numbers B17A0456 a...

Страница 2: ...fic model page of the Kooltronic website I Introduction Kooltronic Air Conditioners are designed to provide a cool dehumidified environment for your electronic components There are models to fit virtu...

Страница 3: ...prior to operating in order to allow the compressor oil to drain to the compressor sump area CAUTION 3 Before operating this unit all electrical wiring must be checked to assure the proper connection...

Страница 4: ...ect type or amount of refrigerant will adversely affect performance and may damage the unit r Make sure that these parameters are met Failure to do so may result in permanent damage to the unit ALL MO...

Страница 5: ...bs the heat and is then discharged to the environment When the Kooltronic Air Conditioner is properly sized it should operate constantly and maintain 75 F to 115 F enclosure temperature depending on t...

Страница 6: ...re the new set point value push the SET key again or wait 10 seconds HOW TO CHANGE A PARAMETER VALUE To change a parameter s value operate as follows 1 Enter the Programming mode by pressing the SET p...

Страница 7: ...p code 7 0 65535 rEL Software release 0 rSE Real set point 0 onF on off key enabling ES PbC Kind of probe ntc Adr Serial address 1 1 247 HES Differential for energy saving 0 F 54 54 rrd Regulation res...

Страница 8: ...te the factory setting is 75o F Refer to page 6 for instructions on adjustment of the thermostat 8 Operate the air conditioner for approximately ten 10 minutes During this period no unusual noise or v...

Страница 9: ...washers NOTE Make sure the press studs are inserted with heads toward you Tighten nuts securely 4 To facilitate easy mounting the three screws located on each side of the unit should be backed out en...

Страница 10: ...102 4 1 12 28 6 0 75 19 0 M TAB MOUNTING PLAN 5 61 142 5 5 61 142 5 50 12 7 16 50 419 1 3 12 79 2 50 12 7 8 12 206 4 8 12 206 4 8 312 7 9 DIA HOLES 5 78 146 8 38 9 7 5 12 130 2 3 75 95 2 6 38 162 1 1...

Страница 11: ...9 07 230 3 5 66 143 7 45 11 4 9 90 251 5 5 96 151 4 2 03 51 6 59 15 0 3 30 83 7 14 20 360 8 6 20 157 6 95 24 0 1 2 3 4 Drawings and Dimensions KA4C2 0NP17L Dimensions inches are for reference only and...

Страница 12: ...Short Cycle Protector Filter Low Ambient Kit NEMA 12 Rating Maintained UL50 Programmable Temperature Alarm Programmable Thermostat UL CUL Listed Accessories and Options Filter Recoating Adhesive Inte...

Страница 13: ...nd Service Kooltronic Air Conditioners feature an easily removable inlet filter to facilitate necessary cleaning CAUTION 1 Lift the filter using the attached tab to clear the lower filter retainer 2 A...

Страница 14: ...erformance and built for reliability They are designed to require only routine maintenance If your air conditioner should require warranty service please contact Kooltronic If you require service out...

Страница 15: ...r Clean Coil difference between return and Coil clogged supply air is less than 10 F Evaporator Blower Condenser Loss of Refrigerant Locate and repair leak Blower and Compressor are running Ice on Eva...

Страница 16: ...eceived by customer Number of parts to be returned Product description model and serial number Reason for return Action requested Contact name telephone FAX numbers and e mail address Pack unit in a s...

Отзывы: