VI. Pre-Installation Testing

 

 

Before mounting the air conditioner to the enclosure, test for proper operation. This 
will verify the shipping integrity of the system.  Please follow the steps below prior to 
installation.

 

 

CAUTION

 

 
 
 
 

 

1. Allow the unit to sit in an upright position at a room temperature of 65°F minimum, 

allowing the system to warm-up particularly in winter months. 

2. Refer to the nameplate for proper electrical voltage and current requirements. Then 

connect the power cord to a properly grounded and fused electrical supply. Leave the 
electrical power off. 

3. Note the factory thermostat setting which is typically 75 to 80°F. 

4. Adjust thermostat to its maximum setting.   

5. If your unit is equipped with an on-off switch, move it to the on position. 

6. Turn electrical power on. 

7. Verify that the evaporator blower or fan is running. 

8. Adjust the thermostat to its minimum setting.  The compressor should start.  On units 

equipped with a short cycle protector, the compressor will have a delayed start of 6 
minutes from the time power is applied to the unit.   

9. Verify that the condenser blower or fan is running.  Note, on units equipped with a low 

ambient kit, the start of the condenser fan or blower will be delayed until the system 
pressures rise. 

10. Operate the air conditioner for approximately ten (10) minutes. During this period no 

unusual noise or vibration should be evident.  Both the evaporator and condenser fans 
or blowers should be delivering air through their respective discharge ports.  The cool 
air discharged should be less than 70°F when the room temperature is between 70 
and 80°F.   

11. On units equipped with heaters, adjust both the cooling and heating thermostats to 

their maximum settings.  Verify that the compressor and condenser fan or blower has 
stopped.  Verify elevated discharge air temperature from the evaporator air discharge. 

12. If your unit is equipped with an on-off switch, leave it in the on position.  Return the 

cooling thermostat to its original setting.  If unit is equipped with a heater, return the 
heating thermostat to its original position. 

13. Turn off the electrical power source, and disconnect the air conditioner from the power 

source. 

14. If any cover plug is removed to adjust the unit, make certain to put back in place to 

maintain the integrity of the closed-loop airflow system. 

NOTE:

  Before shipment all Kooltronic, Inc. Air Conditioners are subjected to a 

       performance test.

 

 

The Air Conditioner must be standing in its proper mounting position for a 

minimum of five (5) minutes prior to testing. Failure to follow this procedure 

will cause permanent damage to the compressor.

Содержание TRIMLINE K2A4C1.0NP17L

Страница 1: ...UAL BE READ AND UNDERSTOOD THOROUGHLY KOOLTRONIC INC 30 Pennington Hopewell Road Pennington NJ 08534 609 466 3400 FAX 609 466 1114 www kooltronic com TRIMLINE NP17 SERIES with Serial Numbers up to M16...

Страница 2: ...age of the Kooltronic website I Introduction Kooltronic Air Conditioners are designed to provide a cool dehumidified environment for your electronic components There are models to fit virtually all si...

Страница 3: ...prior to operating in order to allow the compressor oil to drain to the compressor sump area CAUTION 3 Before operating this unit all electrical wiring must be checked to assure the proper connection...

Страница 4: ...ect type or amount of refrigerant will adversely affect performance and may damage the unit r Make sure that these parameters are met Failure to do so may result in permanent damage to the unit ALL MO...

Страница 5: ...ure accumulated on the evaporator coil is collected in the condensate tray and released to the ambient air through the drain tube or the condensate evaporator The heat removed through the evaporator c...

Страница 6: ...be delayed until the system pressures rise 10 Operate the air conditioner for approximately ten 10 minutes During this period no unusual noise or vibration should be evident Both the evaporator and co...

Страница 7: ...tween the unit and M TAB before tightening the 10 32 self tapping screws NOTE Do not overtighten these screws 7 Attach overflow drain hose supplied to the drain exit in the side of the unit This hose...

Страница 8: ...ent Air In CONDENSER OUTLET Warm Ambient Air Out WARM AIR RETURN FROM ENCLOSURE COOL AIR OUTLET TO ENCLOSURE 12 13 308 1 6 1 4 20 WELD NUTS 2 1 3 4 12 25 311 2 9 00 228 6 17 50 444 5 2 1 3 4 Drawings...

Страница 9: ...mensional changes Switchable Switch is internally mounted for security Rating shown is for operation at maximum ambient temperature 115V 60 Hz and 230V 60 Hz models also perform at full capacity when...

Страница 10: ...nd the compressor will continue to cycle on and off Continued operation under these conditions will cause damage shorten compressor life and void the warranty A Filter Removal and Service Kooltronic A...

Страница 11: ...pass valve fails it is strongly recommended that the Air Conditioner be returned to Kooltronic for service D Refrigerant Loss Kooltronic Air Conditioners are subjected to a series of tests to detect r...

Страница 12: ...Control Replace Thermostat or Relay Thermostat defective when applicable Failed Compressor Replace Compressor Ice on Evaporator Coil Insufficient Heat Load or Unit Contact Kooltronic Oversized for Ap...

Страница 13: ...eceived by customer Number of parts to be returned Product description model and serial number Reason for return Action requested Contact name telephone FAX numbers and e mail address Pack unit in a s...

Отзывы: