background image

X. Standard Warranty

THIS WARRANTY CONSTITUTES THE ENTIRE WARRANTY WITH RESPECT TO THE PRODUCT AND IS IN
LIEU OF ALL OTHERS, EXPRESSED OR IMPLIED, INCLUDING ANY WARRANTY OF MERCHANTABILITY
AND WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE AND IN NO EVENT IS KOOLTRONIC
RESPONSIBLE FOR ANY CONSEQUENTIAL DAMAGES OF ANY NATURE WHATSOEVER.

RETURN AUTHORIZATION (RA) PROCEDURE

KOOLTRONIC products are warranted to be free of defects
in workmanship, materials and components. The following
warranty periods apply from date of shipment:

Air moving devices/components and hermetic system
components: 1 year 

Spare parts, except filters: 90 days

The above warranty applies when the equipment is operated
under the following conditions:

Ambient temperature not in excess of 125°F (52°C) in
normal atmosphere or as stated on product nameplate

Voltage variation no greater than ±  10% from nameplate
rating

Frequency variation no greater than ± 3Hz from nameplate
rating

Maximum cooling load no higher than air conditioner
nameplate rating

Waiting five minutes before restarting air conditioner after
intentional or accidental shutoff

Compliance to all other installation, maintenance and
operating instructions, as supplied

The purchaser assumes the responsibility of grounding
the unit and installing it in accordance with local electrical
and safety codes, as well as the National Electric Code
(NEC) and OSHA

KOOLTRONIC cannot assume responsibility for
mis-application of its products or the erroneous
selection of an inappropriate product by a non-
authorized KOOLTRONIC representative . Our
applications engineers will gladly assist in the
selection of the proper product, provided all
required details of the application are furnished.

All returns require a Return Authorization number whether
the return is for warranty or non-warranty repair, rotation of
stock, damage or any other reason. Returns without an RA
number will be refused.

Customer must call KOOLTRONIC After Sale Kare (ASK),
Pennington, New Jersey (609 • 466 • 3400) to obtain an RA
number, or email [email protected].

The following information is required when an RA is
requested:

- Original customer Purchase Order number and date
- Date product was received by customer
- Number of parts to be returned
- Product description, model and serial number
- Reason for return
- Action requested
- Contact name, telephone, FAX numbers and e-mail address

Pack unit in a suitable container for shipment, preferably the

original packaging if available. All Air Conditioners must be
returned in an upright position properly secured to a pallet.

Improper packaging may void warranty claim.

If an Air

Conditioner is received laying down or shipped via UPS or
similar small parcel service the warranty will be void.

Mark carton prominently with KOOLTRONIC’s Return
Authorization Number.

Enclose all pertinent documents.

Freight charges on all products returned to KOOLTRONIC
shall be paid by the customer. Unauthorized collect shipments
will be refused.

If a unit is repaired under Warranty, KOOLTRONIC will pay
the freight charges both ways within the Continental USA
at KOOLTRONIC’s negotiated rates. Warranty repaired
units will be returned to customer at KOOLTRONIC expense
only within the Continental USA.

All authorized returns are subject to a restocking fee.

KOOLTRONIC assumes no liability beyond the repair or
replacement of its own product. This Warranty does not
cover:

Labor or reimbursement of labor for evaluation, removal,
installation, repair, or cost of any warranted part, unless
authorized in writing by KOOLTRONIC

Use of equipment for other than its designed purpose or
operating conditions

Operation in harsh, oily, corrosive or other abnormal
environmental conditions, without the proper filtration,
sealing, protective coatings and/or weather protection

Damage to hermetic system resulting from continuous
operation with dirty or clogged air filters or improper or
negligent maintenance

Use of refrigerant other than designated

Customer modification or abuse

Shipping damage or other accident (Claims for shipping
damage are the responsibility of the customer. Timely
claims must be filed by the customer with the freight carrier)

Cracked or broken hermetic tubing, brazed joints or  other
internal damage caused by shipping or mishandling

Damage caused by shipping units attached to an
enclosure

Any and all conditions resulting from noncompliance with
the preceding operating conditions

Returned freight must be paid by customer

This standard warranty does not apply to custom
products. Consult your KOOLTRONIC representative
for limitations

14

Содержание Trimline 13NP47 Series

Страница 1: ...ON BEFORE INSTALLING AND USING THIS AIR CONDITIONER IT IS IMPORTANT THAT THIS MANUAL BE READ AND UNDERSTOOD THOROUGHLY KOOLTRONIC INC 30 Pennington Hopewell Road Pennington NJ 08534 609 466 3400 FAX 609 466 1114 www kooltronic com 900 034 10 2 19 CDR 20131 TRIMLINE 13NP47 SERIES ...

Страница 2: ...ction Kooltronic Air Conditioners are designed to provide a cool dehumidified environment for your electronic components There are models to fit virtually all sizes and shapes of electronic enclosures in capacities ranging from 1 000 to 30 000 BTU H Our closed loop design also ensures that your components will not be exposed to hot dirty operating conditions This Manual provides you with the neces...

Страница 3: ...rate in a horizontal position only This placement must be done a minimum of 5 minutes prior to operating in order to allow the compressor oil to drain to the compressor sump area CAUTION 3 Before operating this unit all electrical wiring must be checked to assure the proper connection to the correct power source Minimum circuit ampacity should be at least 125 of the amperage found on the air condi...

Страница 4: ...rements y Use of incorrect type or amount of refrigerant will adversely affect performance and may damage the unit r Make sure that these parameters are met Failure to do so may result in permanent damage to the unit ALL MOTORS ARE THERMALLY PROTECTED VIOLATES WARRANTY UNAUTHORIZED SERVICE OR MODIFICATION COMPARTMENT ONLY NEMA EEMAC UL50 BY UNDERWRITERS LABORATORIES INC TYPE 1 SPECIAL PURPOSE AIR ...

Страница 5: ...t air through the drain tube or the condensate evaporator The heat removed through the evaporator coil is transferred by the compressed refrigerant to the condenser coil Ambient air or water is then passed through the condenser coil where it absorbs the heat and is then discharged to the environment The EPR Evaporator Pressure Regulator valve prevents the evaporator coil from freezing by reducing ...

Страница 6: ...ical supply leaving electrical power to the unit turned off 3 Note the factory thermostat setting which is 75o F 4 Turn the electrical power on 5 Verify that the evaporator blower or fan is running 6 Verify that the condenser blower or fan is running 7 Operate the air conditioner for approximately ten 10 minutes During this period no unusual noise or vibration should be evident Both the evaporator...

Страница 7: ...Mount the unit to the M TAB by sliding the studs located on each side panel into the slots on the M TAB 6 Insert the remaining 10 32 screws and seal washers supplied by Kooltronic through the air conditioner side panel and into the M TAB To avoid misalignment of parts do not tighten any of the screws until they are all installed Be careful not to overtighten the screws 7 The drain hose must not be...

Страница 8: ...TYP 15 12 384 0 18 00 457 2 12 50 317 5 3 00 76 2 12 88 327 1 12 24 310 8 47 26 1200 4 17 28 438 9 15 56 395 2 RIGHT SIDE BACK BOTTOM TOP LEFT SIDE FRONT 12 00 304 8 Drawings and Dimensions 13NP47 SERIES Dimensions inches metric are for reference only and are subject to change GA49100A Rev B ...

Страница 9: ... Weight Model 95 95 Max Min Volts Hz Amps Amps lbs Major Component Replacements KA3C13NP47R K2A3C13NP47R Part Part Number Part Number Compressor 0665 80 0665 81 Compressor Capacitor 0452 54 0452 32 Condenser Blower Motor 0194 103 0194 50 Condenser Blower Capacitor 0452 32 0452 06 Evaporator Blower Motor 0261 08 0261 54 Evaporator Blower Capacitor 0452 03 0452 03 Evaporator Coil 0666 29 0666 29 Con...

Страница 10: ...115 V 230 V RELAY TO CUSTOMER ALARM SYSTEM COMPRESSOR O L 0 1 4 8 2 6 1 3 C R S CAP COND BLOWER MOTOR CAP OPTIONAL PRESSURE SWITCH START ASSIST 115 V ONLY TERMINAL BLOCK COOLING EFFECT DETECTOR COMMON RED BLUE YELLOW h RED TO YELLOW CLOSES ON TEMPERATURE INCREASE RED TO BLUE OPENS ON TEMPERATURE INCREASE BK WD 838 13NP47R ...

Страница 11: ... off Continued operation under these conditions will cause damage shorten compressor life and void the warranty A Filter Removal and Service Kooltronic Air Conditioners feature an easily removable inlet filter to facilitate necessary cleaning CAUTION 1 Lift the filter using the attached tab to clear the lower filter retainer Pull filter toward you and downward until the top of the filter clears th...

Страница 12: ...he air conditioner be returned to Kooltronic for service D Refrigerant Loss Kooltronic Air Conditioners are subjected to a series of tests to detect refrigerant leaks during and after manufacture It is possible that shipping or other damage or microscopic leaks over a long period may result in the need for replenishment of refrigerant charge When it has been verified by a Certified EPA Technician ...

Страница 13: ... applicable Failed Compressor Replace Compressor Ice on Evaporator Coil Insufficient Heat Load or Unit Contact Kooltronic Oversized for Application Failed Evaporator Blower Replace Evaporator Blower Motor or Assembly Clogged Evaporator Coil Clean Coil Condensate draining Enclosure not properly sealed Check and seal all openings continuously Excessive opening of Enclosure Eliminate the frequency of...

Страница 14: ...received by customer Number of parts to be returned Product description model and serial number Reason for return Action requested Contact name telephone FAX numbers and e mail address Pack unit in a suitable container for shipment preferably the original packaging if available All Air Conditioners must be returned in an upright position properly secured to a pallet Improper packaging may void war...