VIII. Maintenance

Kooltronic Water-Cooled Air Conditioners require no maintenance. Air-Cooled Air
Conditioners are designed to require only the routine cleaning of air filters to assure
unimpeded air flow through the condenser heat exchanger. It is not possible to
recommend specific filter cleaning intervals since the level and the nature of airborne
particulate matter differs widely with each installation. It is generally sufficient to remove
and wash the reusable aluminum mesh air filters when the outer surfaces of these filters
appear covered with a thin layer of dust or lint. Filter recoating adhesive is recommended.
Appropriate disposable filters are available from Kooltronic.

If filter service is neglected or delayed, the air conditioner will not perform at its design
capacity. The first indication of excessively clogged air filters is usually a gradual
increase of temperature within the equipment cabinet. If operation is continued under
these conditions, the compressor will be shut off by the thermal overload device. The
compressor will restart when its external temperature drops below the protector threshold
setting and the compressor will continue to cycle on and off. Continued operation under
these conditions will cause damage, shorten compressor life and void the warranty.

A. Filter Removal and Service

Kooltronic Air Conditioners feature an easily removable inlet filter to facilitate
necessary cleaning.

CAUTION

1) Lift the filter, using the attached tab, to clear the lower filter retainer. Pull filter

toward you and downward until the top of the filter clears the upper filter retainer.

2) After removal, the filters should be flushed under warm running water with

the clean side up, driving contaminants out the dirty side of the filter. If the
accumulated dirt is oily, washing in a detergent bath is recommended, followed
by a warm water rinse as above.

3) The filters may be sprayed with Kooltronic A-16 Filter Recoating Adhesive to

trap fine airborne contaminants, or they may simply be dried and reinstalled as
strainer type filters. Recoating is recommended for best results.

4) Reinstall the filter: (a) keeping the tab at the bottom, slide filter into the upper

retainer, (b) press filter against the unit and (c) slide down into lower retainer.

Do not operate the Air Conditioner for extended periods of time with the

filter removed. The condenser coil may become clogged with dust or

lint from the air entering the face. A clogged condenser coil is not

readily detected and will give the same reaction as a clogged filter. A

clean filter is the best protection.

11

Содержание P24 SERIES

Страница 1: ...ORTANT THAT THIS MANUAL BE READ AND UNDERSTOOD THOROUGHLY KOOLTRONIC INC 30 Pennington Hopewell Road Pennington NJ 08534 609 466 3400 FAX 609 466 1114 www kooltronic com P24 SERIES P28 SERIES P36 SERI...

Страница 2: ...ntroduction Kooltronic Air Conditioners are designed to provide a cool dehumidified environment for your electronic components There are models to fit virtually all sizes and shapes of electronics enc...

Страница 3: ...e in a horizontal position only This placement must be done a minimum of 5 minutes prior to operating in order to allow the compressor oil to drain to the compressor sump area CAUTION 3 Before operati...

Страница 4: ...ce matches these requirements Use of incorrect type or amount of refrigerant will adversely affect performance and may damage the unit Make sure that these parameters are met Failure to do so may resu...

Страница 5: ...by means of the vapor compression refrigeration cycle This takes place in a hermetically sealed refrigeration system utilizing either an air cooled or water cooled condenser heat exchanger The warm ai...

Страница 6: ...blower will be delayed until the system pressures rise 10 Operate the air conditioner for approximately ten 10 minutes During this period no unusual noise or vibration should be evident Both the evapo...

Страница 7: ...densate Evaporator The drain hoses fittings and Condensate Evaporator must be removed before dismounting the Air Conditioner as they will not support the weight of the Air Conditioner unit The externa...

Страница 8: ...ing should be located as high as possible within this area and equal or exceed size of cool air outlets FILTERED CONDENSER AIR INLET Ambient Air In CONDENSER OUTLET Warm Ambient Air Out COOL AIR OUTLE...

Страница 9: ...00 125 50 115 100 60 50 12 0 90 90 110 G KA4C4P_ _L56 4000 120 50 115 50 60 14 2 90 90 110 G G KA4C4P_ _L56 4000 120 50 115 50 60 12 5 12 0 90 90 110 G K2A4C4P_ _L 4000 125 50 230 200 60 50 6 2 90 90...

Страница 10: ...AL CAP 1 3 EVAP BLOWER MOTOR 0 1 4 8 2 6 CRANKCASE HEATER MOTOR BLOWER COND TIMER CYCLE SHORT PRESSURE SWITCH OPTIONAL RELAY RELAY S L 2 1 M CAP WE BK RED ALARM SYSTEM TO CUSTOMER BLOCK TERMINAL EXCES...

Страница 11: ...Continued operation under these conditions will cause damage shorten compressor life and void the warranty A Filter Removal and Service Kooltronic Air Conditioners feature an easily removable inlet f...

Страница 12: ...valve fails it is strongly recommended that the Air Conditioner be returned to Kooltronic for service D Refrigerant Loss Kooltronic Air Conditioners are subjected to a series of tests to detect refri...

Страница 13: ...ntrol Replace Thermostat or Relay Thermostat defective when applicable Failed Compressor Replace Compressor Ice on Evaporator Coil Insufficient Heat Load or Unit Contact Kooltronic Oversized for Appli...

Страница 14: ...unted Cooled Mini NP33 Horizontal Accessories and Options HS P24 P47 NP36 Rack Top Panel MM NM P28 P52 NP47 Mounted Mounted Mounted SM NP17 P36 P59 NP59 H V HT WP Adapter Plate for Rack Mounting N A N...

Страница 15: ...riginal customer Purchase Order number and date Date product was received by customer Number of parts to be returned Product description model and serial number Reason for return Action requested Cont...

Отзывы: