background image

3

II. Incoming Inspection

Kooltronic Heat Exchangers are designed, built, and packaged to withstand the shock and vibration
normally associated with shipment by common carriers.  Occasionally improper handling during
shipping causes damage.  Such handling could include unbanding of palletized shipments, failing to
respect any carton handling instructions, falling off conveyors, excessive vibration, crushing, etc.
Therefore, a thorough inspection should be done upon receipt of all shipments.  Any carton tears,
dents, scratches, or loose articles should be noted on the Freight Bill.  Cartons should be opened
promptly and the units inspected for CONCEALED DAMAGE.
An immediate claim MUST be filed with the freight carrier and an inspection requested. Retain all
packing materials.  Kooltronic cannot assume responsibility for Consignee’s failure to file a timely
freight claim.

III. Product Handling

Do not attempt to operate your Kooltronic Heat Exchanger until you read and thoroughly under-
stand this Manual.

Before operating this unit, all electrical wiring must be checked to assure the proper connections.

IV. Product Identification and Nameplate

Each Kooltronic Heat Exchanger includes an identification nameplate.  This nameplate provides:

CAUTION

Operate this unit only on the proper voltages and frequencies as noted on the nameplate.

MODEL NO.

SERIAL NO.

MAX. CABINET

VOLTS.

FREQ.

PH.

AMPS

TEMP. 

o

F

MAX.

FILTER P/N

FUSE SIZE

UNAUTHORIZED SERVICE OR MODIFICATION VIOLATES WARRANTY

ALL MOTORS ARE THERMALLY PROTECTED

THIS PRODUCT IS PROTECTED BY ONE OR MORE OF THE FOLLOWING
PATENTS: 3,019,965  3,120,166  3,211,360  3,559,728  3,807,493  AND 
OTHER PATENTS PENDING

MANUFACTURED BY:

KOOLTRONIC, INC.

PENNINGTON, NJ

VENTURA, CA

Heat Exchanger

     

Model Number

Serial Number

Electrical power characteristics

Maximum enclosure temperature

Filter Part Number

We recommend you copy this information from
your unit.

   

When ordering parts,

specify the Model Number and
Serial Number.

 

Before operating, be sure that

the power source matches these
requirements.

Make sure that these parameters

are met.  Failure to do so may result
in permanent damage to the unit

LISTED

SPECIAL PURPOSE

HEAT EXCHANGER

Содержание KNHX32 Series

Страница 1: ...S HEAT EXCHANGER IT IS IMPORTANT THAT THIS MANUAL BE READ AND UNDERSTOOD THOROUGHLY KOOLTRONIC INC 30 Pennington Hopewell Road Pennington NJ 08534 609 466 3400 FAX 609 466 1114 www kooltronic com 900 046 06 12 18 CDR 20111 Find additional information on this model at kooltronic com or use the Technical Documents QR code below Technical Documents ...

Страница 2: ...c TrimLine Heat Exchangers are designed for indoor applications with ambient temperatures from 50 F to 131 F and maximum allowable enclosure temperature of 160 F These heat exchangers utilize a counterflow airstream for maximum heat transfer efficiency in a closed loop system providing cooling within sealed electronic cabinets This Manual provides you with the necessary general information for pro...

Страница 3: ...er stand this Manual Before operating this unit all electrical wiring must be checked to assure the proper connections IV Product Identification and Nameplate Each Kooltronic Heat Exchanger includes an identification nameplate This nameplate provides CAUTION Operate this unit only on the proper voltages and frequencies as noted on the nameplate MODEL NO SERIAL NO MAX CABINET VOLTS FREQ PH AMPS TEM...

Страница 4: ...d Air Cabinet Blower Heated Air Ambient Air In an Air to Air Heat Exchanger heat from air surrounding the components is removed by a specially designed heat transfer element before being routed back into the enclosure Optional bimetal thermostat is used as Cooling Effect Detector The thermostat contacts close at 130 F and open at 90 F Major Component Replacements KNHX32 KNHX32E Condenser Blower As...

Страница 5: ... mounting studs installed on the heat exchanger side panels into the inclined slots of the M TAB 6 Carefully mark all mounting holes from the flanges of the heat exchanger to the cabinet wall All holes in the heat exchanger flange must be used to maintain the NEMA 4 rating 7 Remove the heat exchanger from the M TAB and drill 218 dia mounting holes in the cabinet Do not attempt to drill mounting ho...

Страница 6: ...and void the warranty 3 4 4 00 101 6 TYP 24 250 6 4 DIA HOLES 6 312 7 9 DIA HOLES UNIT MOUNTING PLAN M TAB MOUNTING PLAN 87 22 2 1 15 29 2 3 13 79 4 11 50 292 1 8 00 203 2 2 17 55 0 3 12 79 2 11 50 292 1 5 12 130 0 3 86 97 9 2 68 68 0 8 00 203 2 89 22 5 99 25 1 4 25 107 9 4 25 107 9 4 25 107 9 4 25 107 9 4 25 107 9 4 00 101 6 1 00 25 5 3 4 11 50 292 1 11 50 292 1 5 12 130 0 3 86 97 9 10 50 266 7 5...

Страница 7: ...e tab slide the filter into the near retainer b press filter against the unit and c slide forward into far retainer CAUTION Do not operate the Heat Exchanger for extended periods of time with the filter removed The heat exchanger element may become clogged with dust or lint from the ambient environment A clogged heat exchanger element is not readily detected and will give the same reaction as clog...

Страница 8: ...s received by customer Number of parts to be returned Product description model and serial number Reason for return Action requested Contact name telephone FAX numbers and e mail address Pack unit in a suitable container for shipment preferably the original packaging if available All Heat Exchangers must be returned in an upright position properly secured to a pallet Improper packaging may void wa...

Отзывы: