VI. Pre-Installation Testing

Before mounting the air conditioner to the enclosure, test for proper operation. This will verify the
shipping integrity of the system. Please follow the steps below prior to installation.

CAUTION

1. Allow the unit to sit in an upright position at a room temperature of 65°F minimum, allowing the

system to warm-up. This is particularly important in winter months.

2. Refer to the nameplate for proper electrical voltage and current requirements. Then connect the

power cord to a properly grounded and fused electrical supply. Leave the electrical power off.

3. Note the factory thermostat setting which is typically 75 to 80°F.

4. Adjust thermostat to its maximum setting.  

5. If your unit is equipped with an on-off switch, move it to the on position.

6. Turn electrical power on.

7. Verify that the evaporator blower or fan is running.

8. Adjust the thermostat to its minimum setting. The compressor should start. On units equipped with a

short cycle protector, the compressor will have a delayed start of 6 minutes from the time power is
applied to the unit.  

9. Verify that the condenser blower or fan is running. Note, on units equipped with a low ambient kit, the

start of the condenser fan or blower will be delayed until the system pressures rise.

10. Operate the air conditioner for approximately ten minutes. During this period no unusual noise or

vibration should be evident. Both the evaporator and condenser fans or blowers should be delivering
air through their respective discharge ports. The cool air discharged should be less than 70°F when
the room temperature is between 70 and 80°F.  

11. On units equipped with heaters, adjust both the cooling and heating thermostats to their maximum

settings. Verify that the compressor and condenser fan or blower has stopped. Verify elevated
discharge air temperature from the evaporator air discharge.

12. If your unit is equipped with an on-off switch, leave it in the on position. Return the cooling thermostat

to its original setting. If unit is equipped with a heater, return the heating thermostat to its original
position.

13. Turn off the electrical power source, and disconnect the air conditioner from the power source.

14. If any cover plug is removed to adjust the unit, make certain to put back in place to maintain the

integrity of the closed-loop airflow system.

NOTE:

Before shipment all Kooltronic, Inc. Air Conditioners are subjected to a performance test.

The Air Conditioner must be standing in its proper mounting position for a minimum of

five (5) minutes prior to testing. Failure to follow this procedure will cause permanent

damage to the compressor.

Содержание K2NA4C1P32R5

Страница 1: ...MPORTANT THAT THIS MANUAL BE READ AND UNDERSTOOD THOROUGHLY KOOLTRONIC INC 30 Pennington Hopewell Road Pennington NJ 08534 609 466 3400 FAX 609 466 1114 www kooltronic com INTEGRITY SERIES KNA4C_P32R...

Страница 2: ...model page of the Kooltronic website I Introduction Kooltronic Air Conditioners are designed to provide a cool dehumidified environment for your electronic components There are models to fit virtuall...

Страница 3: ...s prior to operating in order to allow the compressor oil to drain to the compressor sump area CAUTION 3 Before operating this unit all electrical wiring must be checked to assure the proper connectio...

Страница 4: ...requirements y Use of incorrect type or amount of refrigerant will adversely affect performance and may damage the unit r Make sure that these parameters are met Failure to do so may result in permane...

Страница 5: ...nger The warm air inside the enclosure is drawn through the evaporator coil where it is cooled dehumidified and returned Any enclosure moisture accumulated on the evaporator coil is collected in the c...

Страница 6: ...ower will be delayed until the system pressures rise 10 Operate the air conditioner for approximately ten minutes During this period no unusual noise or vibration should be evident Both the evaporator...

Страница 7: ...ing the 4 mounting studs installed on the air conditioner side panels into the 4 inclined slots of the M TAB 6 Carefully mark all mounting holes from the flanges of the air conditioner to the cabinet...

Страница 8: ...00 60 50 6 0 105 K2NA4C1P32R5 1000 125 0 230 50 6 5 105 KNA4C2P32R 2000 125 0 115 100 60 50 13 0 12 0 105 KNA4C2P32R56 2000 125 0 115 50 60 13 0 105 K2NA4C2P32R 2000 120 0 230 200 60 50 6 0 105 K2NA4C...

Страница 9: ...rear part of the filter clears the rear filter retainer 2 To replace the rear filter in the P32 series lift the filter using both sides of the lower filter frame with both hands Push the filter towar...

Страница 10: ...ycle on and off Continued operation under these conditions will cause damage shorten compressor life and void the warranty A Filter Removal and Service Kooltronic Air Conditioners feature an easily re...

Страница 11: ...mmended that the air conditioner be returned to Kooltronic for service D Refrigerant Loss Kooltronic Air Conditioners are subjected to a series of tests to detect refrigerant leaks during and after ma...

Страница 12: ...r Relay Thermostat defective when applicable Failed Compressor Replace Compressor Ice on Evaporator Coil Insufficient Heat Load or Unit Contact Kooltronic Oversized for Application Failed Evaporator B...

Страница 13: ...nal customer Purchase Order number and date Date product was received by customer Number of parts to be returned Product description model and serial number Reason for return Action requested Contact...

Отзывы: