II. Incoming Inspection

Kooltronic Air Conditioners are designed, built and packaged to withstand the shock and vibration normally
associated with shipment by common carriers. Occasionally improper handling during shipping causes damage.
Such handling could include unbanding of palletized shipments, failing to respect 

"This Side Up"

arrows, rough

handling, falling off conveyors, excessive vibration, crushing, etc. Therefore, a thorough inspection should be
done upon receipt of all shipments. Any carton tears, dents, scratches, loose articles or evidence of oil are signs
of damage and should be noted on the Freight Bill. Cartons should be opened promptly and the units inspected
for CONCEALED DAMAGE. Kooltronic Air Conditioners must be delivered in the proper mounting position to
assure that damage to the compressor has not occurred during shipping. Any Kooltronic Air Conditioner that is
delivered removed from the banded pallet, lying down or double stacked should be refused.

An immediate claim MUST be filed with the freight carrier and an inspection requested. Retain all packing
materials. Kooltronic cannot assume responsibility for Consignee's failure to file a timely freight claim.

III. Product Handling:

1) Do not attempt to operate your Kooltronic Air Conditioner until you read and thoroughly understand this

Manual. See section

VI PRE-INSTALLATION TESTING.

2) Before operating the Kooltronic Air Conditioner be certain that it is placed in its correct mounting position.

This Air Conditioners is designed to operate in a vertical position only. 

This placement must be done

a minimum of 5 minutes prior to operating in order to allow the compressor oil to drain to the compressor
sump area. 

CAUTION

3) Before operating this unit, all electrical wiring must be checked to assure the proper connection to the

correct power source. Minimum circuit ampacity should be at least 125% of the amperage found on the
nameplate for the corresponding voltage. Do not exceed the maximum fuse size found on the nameplate.

4) We do not recommend that Air Conditioners be shipped to their final destination attached to an enclosure.

In the event that the Air Conditioner needs to be shipped attached to an enclosure it is strongly
recommended that proper support be provided for the Air Conditioner. Excessive vibration can occur if Air
Conditioners are not properly supported when shipped on enclosures, increasing the potential for internal
damage and voiding the warranty.

5)

PROCEDURE FOR PROPER PACKING AND SHIPMENT OF KOOLTRONIC AIR
CONDITIONERS:

Keep Air Conditioner in proper upright position indicated by arrow markers.

Pack Air Conditioner in an appropriate carton (preferably original carton if possible), with
adequate internal protective packaging, making sure carton is marked and is kept in correct
upright position.

For local, controlled transportation, strap carton to a secure part of truck to prevent falling or
sliding, minimize vibration, etc.

For common carrier shipment, band unit(s) securely to a pallet. Unpalleted shipment risks
severe damage which voids the warranty.

Kooltronic Air Conditioners must be operated in their proper mounting position. If attempts are

made to operate a unit that is not in its designed mounting position, permanent compressor

damage will occur. This action will void the warranty. To avoid compressor damage do not tip the

unit more than 45° from its proper mounting position.

Содержание K2NA4C1P32R5

Страница 1: ...MPORTANT THAT THIS MANUAL BE READ AND UNDERSTOOD THOROUGHLY KOOLTRONIC INC 30 Pennington Hopewell Road Pennington NJ 08534 609 466 3400 FAX 609 466 1114 www kooltronic com INTEGRITY SERIES KNA4C_P32R...

Страница 2: ...model page of the Kooltronic website I Introduction Kooltronic Air Conditioners are designed to provide a cool dehumidified environment for your electronic components There are models to fit virtuall...

Страница 3: ...s prior to operating in order to allow the compressor oil to drain to the compressor sump area CAUTION 3 Before operating this unit all electrical wiring must be checked to assure the proper connectio...

Страница 4: ...requirements y Use of incorrect type or amount of refrigerant will adversely affect performance and may damage the unit r Make sure that these parameters are met Failure to do so may result in permane...

Страница 5: ...nger The warm air inside the enclosure is drawn through the evaporator coil where it is cooled dehumidified and returned Any enclosure moisture accumulated on the evaporator coil is collected in the c...

Страница 6: ...ower will be delayed until the system pressures rise 10 Operate the air conditioner for approximately ten minutes During this period no unusual noise or vibration should be evident Both the evaporator...

Страница 7: ...ing the 4 mounting studs installed on the air conditioner side panels into the 4 inclined slots of the M TAB 6 Carefully mark all mounting holes from the flanges of the air conditioner to the cabinet...

Страница 8: ...00 60 50 6 0 105 K2NA4C1P32R5 1000 125 0 230 50 6 5 105 KNA4C2P32R 2000 125 0 115 100 60 50 13 0 12 0 105 KNA4C2P32R56 2000 125 0 115 50 60 13 0 105 K2NA4C2P32R 2000 120 0 230 200 60 50 6 0 105 K2NA4C...

Страница 9: ...rear part of the filter clears the rear filter retainer 2 To replace the rear filter in the P32 series lift the filter using both sides of the lower filter frame with both hands Push the filter towar...

Страница 10: ...ycle on and off Continued operation under these conditions will cause damage shorten compressor life and void the warranty A Filter Removal and Service Kooltronic Air Conditioners feature an easily re...

Страница 11: ...mmended that the air conditioner be returned to Kooltronic for service D Refrigerant Loss Kooltronic Air Conditioners are subjected to a series of tests to detect refrigerant leaks during and after ma...

Страница 12: ...r Relay Thermostat defective when applicable Failed Compressor Replace Compressor Ice on Evaporator Coil Insufficient Heat Load or Unit Contact Kooltronic Oversized for Application Failed Evaporator B...

Страница 13: ...nal customer Purchase Order number and date Date product was received by customer Number of parts to be returned Product description model and serial number Reason for return Action requested Contact...