Principles of Operation (con’t)

 

 
The unit is equipped with a Temperature Alarm, which has normally closed and normally open contacts, and a factory  
set point of 115°F. 
The unit is equipped with optional inputs for an external thermostat. The external thermostat is connected to the 
unit via a terminal block located adjacent to the temperature display and activated with a bypass switch located 
inside the electrical box. The temperature display, alarm and communications functions will remain active.

 

 

 

 

 

 

 

VI. Pre-Installation Testing

 

Before installing the air conditioner, test for proper operation. This will verify the shipping integrity of the system. 
Please follow the steps below prior to installation. 

 

 

 

CAUTION 

 
 
 
 

 

 

 1

. The unit must sit in an upright position at a minimum room temperature of 65°F to allow the system to warm 

up. This is particularly important during winter months. 

 2. Refer to the nameplate for proper electrical voltage and current requirements. Connect the power cord to a 

properly grounded and fused electrical supply, leaving electrical power to the unit turned off. 

 3. Turn the electrical power on.  

 4. Verify that the evaporator blower or fan is running. 

 5. Observe the temperature on the digital display. The thermostat must be set a minimum of 10°F below this 

temperature for the compressor to operate (the factory setting is 75°F). Refer to page 6 for instructions on 
adjustment of the thermostat. 

 6. Operate the air conditioner for approximately ten (10) minutes. During this period the evaporator fan should 

operate continuously and no unusual noise or vibration should be evident. The condenser blower is 
controlled by a pressure switch and may not start for several minutes. Depending on ambient conditions, the 
condenser blower may cycle during the test. The cool air discharged should be less than 70°F when the 
room temperature is between 70°F and 80°F.    

 7 Reset the thermostat to the factory setting. 

WARNING: Operating the unit below 75°F may result in 

freezing of the evaporator coil.

 

 8. Turn off the electrical power and disconnect the air conditioner from the power source.  

 

NOTE:

   Before shipment all Kooltronic Air Conditioners are subjected to a performance test.

The air conditioner must be standing in its proper mounting position for a minimum of five 

(5) minutes prior to testing. Failure to follow this procedure will cause permanent damage to 

the compressor. To avoid compressor damage do not tip the unit more than 45° from its 

proper mounting position.

Содержание Intrepid Series

Страница 1: ...HAT THIS MANUAL BE READ AND UNDERSTOOD THOROUGHLY KOOLTRONIC INC 30 Pennington Hopewell Road Pennington NJ 08534 609 466 3400 FAX 609 466 1114 www kooltronic com 900 039 95 12 21 CDR 20369 INTREPID SE...

Страница 2: ...X Warranty 17 I Introduction Kooltronic Air Conditioners are designed to provide a cool dehumidified environment for your electronic components There are models to fit virtually all sizes and shapes o...

Страница 3: ...minimum of 5 minutes prior to operating in order to allow the compressor oil to drain to the compressor sump area CAUTION 3 Before operating this unit all electrical wiring must be checked to assure t...

Страница 4: ...the power source matches these requirements y Use of incorrect type or amount of refrigerant will adversely affect performance and may damage the unit r Make sure that these parameters are met Failure...

Страница 5: ...oltronic Air Conditioner is properly sized it should operate constantly and maintain 75 F to 115 F enclosure temperature depending on the ambient temperatures CONTROL ACTION The evaporator blower oper...

Страница 6: ...the new set point value push the SET key again or wait 10 seconds HOW TO CHANGE A PARAMETER VALUE To change a parameter s value operate as follows 1 Enter the Programming mode by pressing the SET plu...

Страница 7: ...p code 7 0 65535 rEL Software release 0 rSE Real set point 0 onF on off key enabling ES PbC Kind of probe ntc Adr Serial address 1 1 247 HES Differential for energy saving 0 F 54 54 rrd Regulation res...

Страница 8: ...tor blower or fan is running 5 Observe the temperature on the digital display The thermostat must be set a minimum of 10 F below this temperature for the compressor to operate the factory setting is 7...

Страница 9: ...e casters will prevent both rolling and swivelling The casters are factory set to a minimum height and provide one inch of adjustment To adjust the height loosen the two allen head set screws in the c...

Страница 10: ...Drawings and Dimensions 10 DRAWINGS ATTACHED...

Страница 11: ...imit 0712 32 Condensate Pump 0664 01 Standard Features Adjustable Casters Baked Powder Finish Blygold PoluAI XT Coil Coating Closed Loop Cooling Condenser Blower Controller Compressor Crankcase Heater...

Страница 12: ...12 Wiring Diagram WIRING DIAGRAMS ATTACHED...

Страница 13: ...13 Commissioning Test Results COMMISSIONING TEST RESULTS ATTACHED...

Страница 14: ...reset thermal overload protectors If the compressor fails it is strongly recommended that the air conditioner be returned to Kooltronic for service C Refrigerant Loss Kooltronic Air Conditioners are...

Страница 15: ...ilter and secure in position by tightening the center screw 3 Lift filter up slightly to clear lower bracket and pull away from unit 4 Place new filter in lower bracket with flow arrows pointing towar...

Страница 16: ...Relay Thermostat defective when applicable Failed Compressor Replace Compressor Ice on Evaporator Coil Insufficient Heat Load or Unit Contact Kooltronic Oversized for Application Failed Evaporator Bl...

Страница 17: ...eceived by customer Number of parts to be returned Product description model and serial number Reason for return Action requested Contact name telephone FAX numbers and e mail address Pack unit in a s...

Отзывы: