VIII. Maintenance 

Kooltronic Air-Cooled Air Conditioners require routine cleaning of the condenser coil and the air filters to assure 
unimpeded airflow through the condenser heat exchanger. It is not possible to recommend specific condenser coil or 
filter cleaning intervals, since the level and the nature of airborne particulate matter differs widely with each 
installation. It is generally sufficient to clean the condenser coil and/or the aluminum mesh filter when the outer 
surfaces appear covered with a thin layer of dust, lint or other foreign matter. The condenser coil can be washed 
or blown out with air, depending on the foreign matter involved (see below - 

Filter and condenser coil service

). 

The aluminum mesh filter can be washed with warm water. Appropriate disposable replacement filters are available 
from Kooltronic. 

If routine condenser coil or filter service is neglected or delayed, the air conditioner will not perform at its design 
capacity. The first indication of an excessively clogged condenser coil or air filter is usually a gradual increase of 
temperature within the equipment cabinet. If operation is continued under these conditions, the compressor will be 
shut off by the thermal overload device. The compressor will restart when its external temperature drops below the 
protector threshold setting and the compressor will continue to cycle on and off. Continued operation under these 
conditions will cause damage, shorten compressor life and void the warranty. 

A. Filter and condenser coil service

The rear panel must be removed in order to clean the filters. After removal, the filters should be flushed
under warm running water with clean side up. If the accumulated dirt is oily, washing in a detergent bath
is recommended, followed by a warm water wash as above.

The exposed condenser coil must be cleaned by pressurized air or pressurized cleaning solution. Dirty
liquid will be removed through the condenser coil drain pan.

B. Blowers

The design life of the blowers used in all Kooltronic Air Conditioners is substantially in excess of 20,000
hours. All Kooltronic condenser and evaporator blowers are equipped with automatic-reset thermal
overload protectors.

CAUTION

 

If field replacement of a blower motor is necessary, most blower assemblies, including the mounting plate, are 
readily removable. Each of the blower mounting plates is held to the air conditioner cabinet structure by screws 
and nuts. For installation of the replacement blower, electrical connections may be broken at the terminal 
block, or power leads may be cut and appropriately spliced together.  

C. Compressor

All Kooltronic compressors are approved by UL and CSA, and require no maintenance. They are
hermetically sealed and charged at the factory, and equipped with automatic-reset thermal overload
protectors.

If the compressor fails, it is strongly recommended that the air conditioner be returned to Kooltronic for
service.

Before opening the air conditioner, disconnect all power.

Содержание EP56 Series

Страница 1: ...ONIC INC 30 Pennington Hopewell Road Pennington NJ 08534 609 466 3400 FAX 609 466 1114 www kooltronic com 900 039 106 12 21 CDR 20369 INTREPID EP56 SERIES K2A6C30EP56TR BR Find additional information...

Страница 2: ...fic model page of the Kooltronic website I Introduction Kooltronic Air Conditioners are designed to provide a cool dehumidified environment for your electronic components There are models to fit virtu...

Страница 3: ...prior to operating in order to allow the compressor oil to drain to the compressor sump area CAUTION 3 Before operating this unit all electrical wiring must be checked to assure the proper connection...

Страница 4: ...of incorrect type or amount of refrigerant will adversely affect performance and may damage the unit r Make sure that these parameters are met Failure to do so may result in permanent damage to the u...

Страница 5: ...then discharged to the environment When the Kooltronic Air Conditioner is properly sized it should operate constantly and maintain 75 F to 115 F enclosure temperature depending on the ambient temperat...

Страница 6: ...the new set point value push the SET key again or wait 10 seconds HOW TO CHANGE A PARAMETER VALUE To change a parameter s value operate as follows 1 Enter the Programming mode by pressing the SET plu...

Страница 7: ...p code 7 0 65535 rEL Software release 0 rSE Real set point 0 onF on off key enabling ES PbC Kind of probe ntc Adr Serial address 1 1 247 HES Differential for energy saving 0 F 54 54 rrd Regulation res...

Страница 8: ...should be delivering air through their respective discharge ports The cool air discharged should be less than 70 F when the room temperature is between 70 F and 80 F It is normal for the condenser bl...

Страница 9: ...nditioner Hang the air conditioner on the hooks Before the lift truck lowers the air conditioner make sure that the hooks are located inside of the small cutouts on the front panel 4 Tighten the air c...

Страница 10: ...4 163 7 11 38 289 1 7 37 187 2 17 75 450 8 18 57 471 7 53 75 1365 3 4 56 115 8 1 78 45 3 33 21 843 6 0 80 20 3 0 95 24 1 7 46 189 4 TYP 20 25 514 3 1 45 36 7 EP56T EP56B 3 4 3 375 9 5 DIA OPTIONAL MOU...

Страница 11: ...WER CORD 1 1 2 2 EP56B EP56T 3 4 EP56T EP56B 3 4 57 04 1448 7 DRAIN K2A6C30EP56TR BR Dimensions inches mm are for reference only and are subject to change Drawings and Dimensions CONDENSER AIR INLET A...

Страница 12: ...or Capacitor 0452111 Condenser Blower Motor 0261 274 Condenser Blower Capacitor 0452 04 Evaporator Blower Motor 0261 275 Evaporator Coil 0667 51 Condenser Coil 0666 59 01 Thermostat 0750 137 NOTE Part...

Страница 13: ...ued operation under these conditions will cause damage shorten compressor life and void the warranty A Filter and condenser coil service The rear panel must be removed in order to clean the filters Af...

Страница 14: ...running Low Line Voltage Check Nameplate Voltage against supply Voltage Compressor and Condenser Blower do not run Return temperature is Failed Compressor Check Compressor wire connections above set...

Страница 15: ...vaporator Clean Coil difference between return and Coil clogged supply air is less than 10 F Evaporator Blower Condenser Loss of Refrigerant Locate and repair leak Blower and Compressor are running Ic...

Страница 16: ...eceived by customer Number of parts to be returned Product description model and serial number Reason for return Action requested Contact name telephone FAX numbers and e mail address Pack unit in a s...

Отзывы: