Problem

Cause

Solution 

Unit not cooling. (Temperature            

Failed Evaporator Blower.      Check Blower wire connections.

 

difference between return and

Check Blower Capacitor.

 

supply air is less than 10°F).

Replace Evaporator Blower. 

Compressor and Condenser Blower 
are running. Evaporator Blower does 
not run. 

Unit not cooling. (Temperature            

Low Refrigerant charge.        Check discharge and suction pressure for

 

difference between return and

Refrigerant leak.

 

supply air is less than 10°F).

Failed Condenser Blower.      Check Blower wire connections. 

Compressor and Evaporator Blower 

Check Blower Capacitor. 

are running. Condenser Blower does

Replace Condenser Blower.

not run.

Failed Condenser Blower       Replace Condenser Blower Thermostat
Thermostat or Sensor.           Replace Sensor 

Unit not cooling. (Temperature

           Condenser or Evaporator      Clean Coil.

difference between return and

Coil clogged.

supply air is less than 10°F).

Evaporator Blower, Condenser

Loss of Refrigerant.

Locate and repair leak.

Blower and Compressor are running.

Ice on Evaporator Coil.          Clean Evaporator Coil.

Check discharge and suction pressure for 
Refrigerant leak.
Check for any obstruction of Evaporator airflow.
Check and seal all openings.

Excessive condensate           Eliminate the frequency of door openings.
draining and loss of A/C        
sensible cooling performance. 

Unit overcooling.

Failed Thermostat.

Check Thermostat wire connections

Evaporator Blower, Condenser

Replace Thermostat. 

Blower and Compressor are running.     Failed Relay.

Replace Relay. 

Compressor cycling more than

           Short circuiting of air

Provide baffle in the enclosure separating A/C

10 cycles per hour.

 

between A/C discharge         outlet and inlet.  
and inlet openings. 

Excess vibration.

Defective motor in Blower.     Replace motor. 

Defective wheel in Blower.     Replace wheel. 

Bad Compressor.

Replace Compressor. 

Содержание EP56 Series

Страница 1: ...ONIC INC 30 Pennington Hopewell Road Pennington NJ 08534 609 466 3400 FAX 609 466 1114 www kooltronic com 900 039 106 12 21 CDR 20369 INTREPID EP56 SERIES K2A6C30EP56TR BR Find additional information...

Страница 2: ...fic model page of the Kooltronic website I Introduction Kooltronic Air Conditioners are designed to provide a cool dehumidified environment for your electronic components There are models to fit virtu...

Страница 3: ...prior to operating in order to allow the compressor oil to drain to the compressor sump area CAUTION 3 Before operating this unit all electrical wiring must be checked to assure the proper connection...

Страница 4: ...of incorrect type or amount of refrigerant will adversely affect performance and may damage the unit r Make sure that these parameters are met Failure to do so may result in permanent damage to the u...

Страница 5: ...then discharged to the environment When the Kooltronic Air Conditioner is properly sized it should operate constantly and maintain 75 F to 115 F enclosure temperature depending on the ambient temperat...

Страница 6: ...the new set point value push the SET key again or wait 10 seconds HOW TO CHANGE A PARAMETER VALUE To change a parameter s value operate as follows 1 Enter the Programming mode by pressing the SET plu...

Страница 7: ...p code 7 0 65535 rEL Software release 0 rSE Real set point 0 onF on off key enabling ES PbC Kind of probe ntc Adr Serial address 1 1 247 HES Differential for energy saving 0 F 54 54 rrd Regulation res...

Страница 8: ...should be delivering air through their respective discharge ports The cool air discharged should be less than 70 F when the room temperature is between 70 F and 80 F It is normal for the condenser bl...

Страница 9: ...nditioner Hang the air conditioner on the hooks Before the lift truck lowers the air conditioner make sure that the hooks are located inside of the small cutouts on the front panel 4 Tighten the air c...

Страница 10: ...4 163 7 11 38 289 1 7 37 187 2 17 75 450 8 18 57 471 7 53 75 1365 3 4 56 115 8 1 78 45 3 33 21 843 6 0 80 20 3 0 95 24 1 7 46 189 4 TYP 20 25 514 3 1 45 36 7 EP56T EP56B 3 4 3 375 9 5 DIA OPTIONAL MOU...

Страница 11: ...WER CORD 1 1 2 2 EP56B EP56T 3 4 EP56T EP56B 3 4 57 04 1448 7 DRAIN K2A6C30EP56TR BR Dimensions inches mm are for reference only and are subject to change Drawings and Dimensions CONDENSER AIR INLET A...

Страница 12: ...or Capacitor 0452111 Condenser Blower Motor 0261 274 Condenser Blower Capacitor 0452 04 Evaporator Blower Motor 0261 275 Evaporator Coil 0667 51 Condenser Coil 0666 59 01 Thermostat 0750 137 NOTE Part...

Страница 13: ...ued operation under these conditions will cause damage shorten compressor life and void the warranty A Filter and condenser coil service The rear panel must be removed in order to clean the filters Af...

Страница 14: ...running Low Line Voltage Check Nameplate Voltage against supply Voltage Compressor and Condenser Blower do not run Return temperature is Failed Compressor Check Compressor wire connections above set...

Страница 15: ...vaporator Clean Coil difference between return and Coil clogged supply air is less than 10 F Evaporator Blower Condenser Loss of Refrigerant Locate and repair leak Blower and Compressor are running Ic...

Страница 16: ...eceived by customer Number of parts to be returned Product description model and serial number Reason for return Action requested Contact name telephone FAX numbers and e mail address Pack unit in a s...

Отзывы: