![background image](http://html1.mh-extra.com/html/kooltronic/compact-k2a4c1htl/compact-k2a4c1htl_operators-manual_1997178007.webp)
7
VII. Specific Model Data
Mounting
Kooltronic Air Conditioners have been engineered to be installed easily. To avoid damaging
your Air Conditioner, please read the following information before installation.
•
Top-Mounted Air Conditioners for external top installation contain weld-nuts.
•
Refer to page 8 for the location of all mounting holes and cutouts.
•
Make sure the cutouts don't interfere with components inside your cabinet.
•
Proper alignment of all air inlets and outlets is essential for optimum performance
of the Air Conditioner.
•
All externally-mounted Air Conditioners are fully gasketed to ensure proper sealing.
This seal is necessary to maintain the integrity of the closed loop system.
•
Use all existing mounting holes to insure stability and a tight seal.
•
High strength mounting screws are recommended.
•
The external drain hose must not be elevated above the exit port. Improper mounting
will impede the flow of condensate and may cause internal malfunctions.
CAUTION
When unmounting the unit from the cabinet, make certain
to keep the unit level, to avoid spilling of any water
that may be in the condensate pan.