VI. Pre-Installation Testing

Before mounting the air conditioner to the enclosure, test for proper operation. This will verify the shipping
integrity of the system. Please follow the steps below prior to installation.

CAUTION

1

. The unit must sit in an upright position at a minimum room temperature of 65°F to allow the system to

warm-up. This is particularly important during winter months.

2. Refer to the nameplate for proper electrical voltage and current requirements. Connect the power cord

to a properly grounded and fused electrical supply, leaving electrical power to the unit turned off.

3. Remove the rubber plug from the lower panel. The thermostat dial is visible through the hole in the

lower panel. Note the factory thermostat setting which is typically 75

o

F. 

4. Adjust the thermostat to its maximum setting (turn it clockwise). 

5. Turn the electrical power on.

6. Verify that the evaporator blower is running.

7. Adjust the thermostat to its minimum setting (turn it counterclockwise). The compressor should start.

On units equipped with a short cycle protector, the compressor will have a delayed start of 6 minutes
from the time power is applied to the unit.   

8. Verify that the condenser fan is running. 

9. Operate the air conditioner for approximately ten (10) minutes. During this period no unusual noise or

vibration should be evident. Both the evaporator and condenser fans or blowers should be delivering
air through their respective discharge ports. The cool air discharged should be less than 70°F when the
room temperature is between 70°F and 80°F.  

10. Turn off the electrical power and disconnect the air conditioner from the power source.

11. Adjust the thermostat back to 70°F.  Failure to do this will cause the coil to freeze.

12. Reinstall the rubber plug.

NOTE:

Before shipment all Kooltronic Air Conditioners are subjected to a performance test.

The air conditioner must be standing in its proper mounting position for a minimum of

five (5) minutes prior to testing. Failure to follow this procedure will cause permanent

damage to the compressor.

Содержание C20A0647

Страница 1: ...OOLTRONIC INC 30 Pennington Hopewell Road Pennington NJ 08534 609 466 3400 FAX 609 466 1114 www kooltronic com 900 039 39 8 21 CDR 20346 INTREPID EP56 SERIES K2A4C30EP56TR BR Find additional informati...

Страница 2: ...onic website I Introduction Kooltronic Air Conditioners are designed to provide a cool dehumidified environment for your electronic components There are models to fit virtually all sizes and shapes of...

Страница 3: ...rior to operating in order to allow the compressor oil to drain to the compressor sump area CAUTION 3 Before operating this unit all electrical wiring must be checked to assure the proper connection t...

Страница 4: ...that the power source matches these requirements r Make sure that these parameters are met Failure to do so may result in permanent damage to the unit ALL MOTORS ARE THERMALLY PROTECTED VIOLATES WARRA...

Страница 5: ...where it absorbs the heat and is then discharged to the environment The unit is equipped with a Low Temperature Thermostat to prevent the evaporator coil from freezing and must not be set below the f...

Страница 6: ...the thermostat to its minimum setting turn it counterclockwise The compressor should start On units equipped with a short cycle protector the compressor will have a delayed start of 6 minutes from the...

Страница 7: ...in hose to the drain tubing on the bottom of the air conditioner using the plastic clamp CAUTION 7 If the air conditioner is mounted to the cabinet door you must be sure that the door hinges will supp...

Страница 8: ...0 POWER CORD 1 1 2 EP56B EP56T 3 4 EP56T EP56B 3 4 57 04 1448 7 DRAIN Drawings and Dimensions EP56 SERIES Dimensions inches metric are for reference only and are subject to change FILTERED CONDENSER...

Страница 9: ...ing BTU H Ambient Temp F Max Min Volts Hz Cooling Amps Heating Amps Approx Weight lbs K2A3C30EP56TR K2A3C30EP56BR K2A6C30EP56TR K2A6C30EP56BR 30000 30000 30000 24000 30000 24000 26000 26000 28000 2200...

Страница 10: ...mal overload protectors If the compressor fails it is strongly recommended that the air conditioner be returned to Kooltronic for service C Refrigerant Loss Kooltronic Air Conditioners are subjected t...

Страница 11: ...ssor Ice on Evaporator Coil Insufficient Heat Load or Unit Contact Kooltronic Oversized for Application Failed Evaporator Blower Replace Evaporator Blower Motor or Assembly Clogged Evaporator Coil Cle...

Страница 12: ...eceived by customer Number of parts to be returned Product description model and serial number Reason for return Action requested Contact name telephone FAX numbers and e mail address Pack unit in a s...

Отзывы: