VII. Specific Model Data
Mounting
Kooltronic Air Conditioners have been engineered to be installed easily. To avoid damaging your Air
Conditioner, please read the following information before installation:
1.
Loosen two screws on the bottom of the unit.
2.
See Figure 1 for proper M/TAB orientation.Place the M/TAB flush against the outside of the enclosure
to locate cutouts and mounting holes.
3.
NOTE: The top cutout for the warm air return does not have to match the full 7.75" opening on the
M/TAB. You can locate your cutout anywhere within this opening. Locate your cutout close to the bottom
and not less than 3" high. Make sure the cutouts don't interfere with components inside your cabinet.
4.
Mount the M/TAB to the outside of the cabinet using all the mounting hardware supplied by Kooltronic
(
1/
4
-20 screws/nuts/washers). NOTE: Make sure the screws are inserted with heads on M/TAB side.
Tighten nuts securely.
5.
Route the power cord through the top cut out in your cabinet. Mount the unit to the M/TAB by sliding the
slots located on the front panel on the hooks of the M/TAB.
6.
Tighten two screws on the bottom of the unit and seal the unit against the enclosure.
7.
Attach overflow drain hose supplied to the drain exit in bottom of the unit.
NOTE: The installer has the option of mounting the Air Conditioner to the M/TAB using torx
temper screws instead of hex screws. The (2) torx temper are supplied by Kooltronic in the
hardware bag.
CAUTION
If the Air Conditioner is mounted to the cabinet door you must be sure that the door
hinges will support the additional weight of the Air Conditioner. Also be certain
that when the door is opened fully, the cabinet does not become unbalanced. The
actual weight of the unit can be found in the Technical Data on page 9.
7
MOUNTING PLAN
FIGURE 1
Dimensions (inches) are for reference only and are subject to change.
10.25
[260.4]
1.78
[45.1]
4.00
[101.6]
7.75
[196.8]
9.00
[228.6]
1.78
[45.1]
16.50
[419.1]
1.28
[32.4]
(8) .281 [7.1]
DIA. HOLES
ENCLOSURE
AIR IN
ENCLOSURE
AIR OUT
CONDENSER
AIR IN
CONDENSER
AIR OUT
10.00
[254.0]
12.35
[313.8]
1.08
[27.4]
9.62
[244.5]
TYP.
1.15
[29.3]
1.94
[49.3]