Kooltronic Air Conditioners are required when the equipment operating temperature must be kept near or lower
than the ambient room temperature, and/or the cabinet must be sealed from dust, fumes, oil, corrosives and
other contaminants. This Air Conditioner utilizes a "Closed-Loop Cooling System" to ensure optimum performance
of the installed components.

Closed-Loop cooling seals the electronics enclosure from hostile elements in the environment. Two separate
circulation systems are employed. The internal system cools and dehumidifies the air inside the cabinet, totally
isolating the sensitive electronics and other components from the environment. The external system uses
circulating ambient air or water to discharge the heat removed from the electronics. The heat is dissipated from
the enclosure by means of the vapor compression refrigeration cycle. This takes place in a hermetically-sealed
refrigeration system, utilizing either an air-cooled or water-cooled condenser heat exchanger. The warm air inside
the enclosure is drawn through the evaporator coil where it is cooled, dehumidified and returned.

Any enclosure moisture accumulated on the evaporator coil is collected and evaporated in the condensate
evaporator tray and released to the ambient air by the condenser blower. If latent heat exceeds 25% of the total
cooling capacity excess condensate is released to the ambient through the drain tube.

The heat removed through the evaporator coil is transferred by the compressed refrigerant to the condenser coil.
Ambient air or water is then passed through the condenser coil, where it absorbs the heat and is then discharged
to the environment.

The unit is equipped with a Low Temperature Thermostat to prevent the evaporator coil from freezing. A high
head pressure switch is standard on this unit and prevents the evaporator coil from freezing under low ambient
temperature. The crankcase compressor heater allows the unit to start with an ambient temperature of 0ºF. In
applications having frequent voluntary heat load fluctuations, an optional Short Cycle Protector is recommended.

V. Principles of Operation

COOL AIR TO 

ENCLOSURE

M/TAB

HEATED AIR FROM

ENCLOSURE

ACCUMULATOR

COMPRESSOR

REFRIGERANT
FILTER DRYER

CONDENSATE AIR

EVAPORATOR TRAY

CONDENSER HEAT

EXCHANGER

CONDENSER AIR

OUTLET

(Heated Ambient Air Out)

CONDENSER AIR

INLET

(Ambient Air In)

EVAPORATOR

HEAT EXCHANGER

Содержание ADVANTAGE K2A3C5RP33R

Страница 1: ...TANT THAT THIS MANUAL BE READ AND UNDERSTOOD THOROUGHLY KOOLTRONIC INC 30 Pennington Hopewell Road Pennington NJ 08534 609 466 3400 FAX 609 466 1114 www kooltronic com ADVANTAGE RP33 SERIES 900 039 32...

Страница 2: ...age of the Kooltronic website I Introduction Kooltronic Air Conditioners are designed to provide a cool dehumidified environment for your electronic components There are models to fit virtually all si...

Страница 3: ...operating in order to allow the compressor oil to drain to the compressor sump area CAUTION 3 Before operating this unit all electrical wiring must be checked to assure the proper connection to the c...

Страница 4: ...Use of incorrect type or amount of refrigerant will adversely affect performance and may damage the unit r Make sure that these parameters are met Failure to do so may result in permanent damage to t...

Страница 5: ...ied and returned Any enclosure moisture accumulated on the evaporator coil is collected and evaporated in the condensate evaporator tray and released to the ambient air by the condenser blower If late...

Страница 6: ...a delayed start of 6 minutes from the time power is applied to the unit 8 Verify that the condenser blower or fan is running Note the start of the condenser fan or blower will be delayed until the sys...

Страница 7: ...ut out in your cabinet Mount the unit to the M TAB by sliding the slots located on the front panel on the hooks of the M TAB 6 Tighten two screws on the bottom of the unit and seal the unit against th...

Страница 8: ...4 1 56 39 6 2 68 68 2 6 18 156 9 1 00 25 4 DIA HOLE 12 35 313 6 10 45 265 4 8 59 218 2 10 94 277 9 12 35 313 7 Drawings and Dimensions RP33 SERIES 8 Dimensions inches mm are for reference only and are...

Страница 9: ...odels also operate at 100V 50 Hz or 200V 50 Hz respectively No transformer is required Major Component Replacements KA4C_RP33R K2A4C_RP33R Part Part Number Part Number Compressor 0665 101 0665 107 Com...

Страница 10: ...off Continued operation under these conditions will cause damage shorten compressor life and void the warranty A Filter Removal and Service Kooltronic Air Conditioners feature an easily removable inle...

Страница 11: ...mmended that the air conditioner be returned to Kooltronic for service D Refrigerant Loss Kooltronic Air Conditioners are subjected to a series of tests to detect refrigerant leaks during and after ma...

Страница 12: ...applicable Failed Compressor Replace Compressor Ice on Evaporator Coil Insufficient Heat Load or Unit Contact Kooltronic Oversized for Application Failed Evaporator Blower Replace Evaporator Blower Mo...

Страница 13: ...eceived by customer Number of parts to be returned Product description model and serial number Reason for return Action requested Contact name telephone FAX numbers and e mail address Pack unit in a s...