Operational Checks
Siphon System
To reduce mineral build-up and cleaning frequency, the
water in the sump trough must be purged during each
harvest cycle.
When the water pump de-energizes, the level in the
water trough rises above the standpipe, starting a siphon
action. The siphon action stops when the water level in
the sump trough drops. When the siphon action stops,
the float valve refills the water trough to the correct level.
Follow steps 1 through 6 under water level check to verify
the siphon system functions correctly.
Water Level
Check the water level while the ice machine is in the ice
mode and the water pump is running. The correct water
level is 1/4" (6.3 mm) to 3/8" (9.5 mm) below the top of
the standpipe. A line in the water trough indicates the
correct level.
SIPHON CAP
SET THE WATER LEVEL TO
THE LINE IN THE WATER
TROUGH
SV1689-1