Part Number STH047 5/16
121
Main Fuse
Volt
Amp
K170 - K270
250
10
Bin Switch
Bin switch operation is controlled by the movement of
the ice damper.
ON/OFF/WASH Toggle Switch
Single-pole, double-throw switch. The switch is
connected into a varying low D.C. voltage circuit.
Fan Control Cycle
Model
Cut-in (Close)
Cut-out (Open)
K170
275 psig ±5
225 psig ±5
K270
250 psig ±5
200 psig ±5
High Pressure Cutout (HPCO) Control
Cut-out
Cut-in
450 psig ±10
(3103 kPa ±69)
31 bar ±.69
Automatic Reset
Must be below 300 psig
(2068 kPa, 20.68 bar) to reset.
Filter-Driers
Drier with dirt-retaining filtration.
Component Specifications