Parameter detail setup
92
© Copyright Reserved KONICS Co., Ltd.
8.4.1
Modbus Address (Communication address)
Designate communication address.
The designated communication address is able to apply to RS485, USB Device, also Ethernet
communication. However, duplicated communication address setting in same communication
line does not allow.
Set range: 1 to 127
Factory default: 1
8.4.2
RS485 Port (Use RS485 communication)
Set whether using RS485 communication.
If you set RS485 Port’s set value as ‘Enable’, Ethernet Port’s set value is changed ‘Disable’
automatically.
Set range: Enable
↔
Disable
Factory default: Enable
8.4.3
Baud Rate (Baud rate)
Designate baud rated.
Set range: 2400
↔
4800
↔
9600
↔
19200
↔
38400 (unit: bps)
Factory default: 9600
Содержание krn100
Страница 1: ... Copyright Reserved KONICS Co Ltd i USER MANUAL ...
Страница 2: ...ii Copyright Reserved KONICS Co Ltd ...
Страница 12: ...Table of Contents xii Copyright Reserved KONICS Co Ltd ...
Страница 26: ...2 Specification 26 Copyright Reserved KONICS Co Ltd ...
Страница 28: ...3 Dimensions 28 Copyright Reserved KONICS Co Ltd ...
Страница 32: ...4 Connection 32 Copyright Reserved KONICS Co Ltd ...
Страница 45: ...7 Operation Copyright Reserved KONICS Co Ltd 45 7 Operation ...
Страница 52: ...7 Operation 52 Copyright Reserved KONICS Co Ltd 7 3 2 Parameter ...
Страница 54: ...7 Operation 54 Copyright Reserved KONICS Co Ltd ...
Страница 144: ...9 DAQMaster 144 Copyright Reserved KONICS Co Ltd ...
Страница 150: ...10 Maintenance 150 Copyright Reserved KONICS Co Ltd ...
Страница 153: ...11 Troubleshooting Copyright Reserved KONICS Co Ltd 153 ...
Страница 154: ......