Operation and Gauging
When performing gauging:
1.
Pull the pump handle downwards until it stops and release
2.
Observe the movement of the indicator
3.
The position where the indicator stops will be the contents (tank) level.
Note!
Gauging shall not be done during filling.
Faultfinding
Fault
Possible reason
Action
The pointer goes
beyond the max
value on scale.
The connection pipe is blocked.
Disconnect the connection pipe from the
instrument and check pipe for any obstructions.
The measurement range of the
instrument is set incorrect.
Check tank height or tank diameter setting.
The instrument
gives no reading,
or the reading is
too low.
Leak on the connection pipe or at the
pump piston.
Tighten the screw connections and check the seal
ring on the pump piston.
Tank is empty
The measurement range of the
instrument is set wrongly.
Check tank height or tank diameter setting.