6.5.1.5. Filter status
It is possible to monitor the pollution level of filters and to calibrate clean
filters.
It is recommended to perform the initial calibration of
filters after the first start of the unit. When filters are re-
placed during operation, it is recommended to perform
the clean filter calibration.
6.5.1.6. Inspection lightning
In this menu item you can switch on/off the light during the unit inspec-
tion, for instance, when replacing filters. The option appears on the panel only
if the air handling unit has been pre-ordered with built-in lighting.
Clean filters calibration
Filter status
Outdoor air filter impurity
55%
Extract air filter impurity
60%
6.5.2. Functions
In this menu item, the user can activate and
set additional unit functions.
blank box: function is not activated
gray box: function is activated, but currently not op-
erating
blue box: currently operating function
Functions
1 / 2
Air quality
control
Operation on
demand
Outdoor compen
-
sated ventilation
Summer night
cooling
Minimum tempera-
ture control
Functions
Settings
Overview
Scheduling
Menu
6.5.2.1. Air quality control
Air quality control is designed according to:
•
CO
2
sensor
1
[0...2000 ppm];
•
air quality sensor VOCq [0...100 %];
•
air pollution sensor VOCp [0...100 %];
•
relative humidity sensor [0...100 %];
•
temperature sensor [0...50 ºC].
Depending on the type of the selected sensor, the value of the air qual-
ity function to be maintained is set, and the air handling unit intensity will
be adjusted according to that value. Ventilation intensity will be increased
automatically in the case of deviation from the set value and decreased again
when it is approached. For example, if the unit is designed with the CO
2
main-
tenance function and is equipped with a CO
2
sensor, after setting value 800
ppm, this set CO
2
level will be maintained by adjusting ventilation intensity,
i.e. ventilation intensity will be increased if the CO
2
level grows and will be
decreased when it returns to the previous condition.
The function of air quality operates only if no other below func-
tion is active at the same time:
• summer night cooling;
• min. temperature control;
• outdoor compensated ventilation.
1
Factory setting.
Reset settings
Enable
Setpoint 1
1000 ppm
Setpoint 2
880 ppm
Mode 1
COMFORT 1
Mode 2
COMFORT 2
Air quality control