UAB KOMFOVENT we reserve the right to make changes without prior notice
V-C5.1_21-01
23
2
3
1
3
4
1. Sealant
2. Unit main-switch
3. Heater main-switch
4. Linkage connecting the heater and the unit
Electric Air Heaters Protection from Overheating
Three safety measures protect electric air heaters from overheating.
1. 70 °C heater overheating protection. When airflow velocity is too low, it does not allow the heater ele-
ments to get hotter more than 200 °C. Protection system works automatically, overheat is indicated on
the remote control device.
2. 100 °C heater overheating protection. After disconnecting electric power supply from the heater, protec-
tion is restored manually: the reset switch on the heater is pressed; overheating is indicated on the remote
control device.
3. 60 °C triac overheating protection. Heater control is terminated, protection resumed automatically, mes-
sage is displayed on the remote control device.
There is a possibility to resume overheat danger safety by pressing RESET button
only if before reasons for the heater overheating are clarified and eliminated.
Cleaning and Inspection of Electric Air Heaters
Recommended to perform periodical inspection and cleaning of heater. Check the plates of water
air heater. The air heater is cleaned with hoover from supply air side or with air blast from exhaust air side.
If it is very dirty, wash with tepid water, which will not make corrosion of aluminium. Check if position of
return water temperature sensor is right. Check if electric air heater is properly fixed, wires connections
are not damaged and heating elements are not bent. They can be damaged or bent due to uneven heat
or uneven and turbulent air direction. Check if electric air heater is clear of unnecessary things and heat-
ing elements are not clogged, because this can cause unpleasant smell or in the worst case – dust can
start burning. Air flow through the air heater should be greater than 1,5 m/s. Heating elements can be
cleaned with hoover or wet textile.
2.10. VERSO Series Air Handling Units Designed for the Outdoor Use
VERSO airhandling units, intended to be installed outdoor, should be fixed to the base frame and
air dampers must be installed on to the duct
connections. AHU must be protected from the
weather influence by installing dedicated roof
and hoods.
If during ordering, it was stated that unit
will be used outdoor, each section will have
roof already installed. Also intake and outlet
hoods will be included or mounted.
5 4
3
2
1
1. Roof
2. Air damper actua-
tor cover
3. Air intake hood
4. Exhaust hood
5. External grills