Komfovent ping Скачать руководство пользователя страница 5

 
 
 
 
 
 

 

Network module manual  

 
 

                          - 5 - 

 
 
5.

 

If AHU is connected to the computer network, standard CAT5E UTP cable is connected 
to “Ethernet” socket: 

 

 

6.

 

For  connection  of  air  handling  unit  to  the  another  MODBUS  RTU  based  network  is 
provided  RS485  serial  interface.  MODBUS  network  line  is  connected  to  J3  socket  of 
“Ping”  module.  J3  socket  type:  :  PHOENIX  CONTACT  -  MC  1,5/3-ST-3,5  -  PLUG, 
FREE, 3.5MM, 3WAY): 

 

 

 

 
 
Note:    In  one  serial  line  of  RS-485  network  may  be  connected  not  more  as  30  “Ping” 

modules.  

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Содержание ping

Страница 1: ...Installation Manual ...

Страница 2: ...Network module manual 2 TABLE OF CONTENTS INTRODUCTION 3 NETWORK MODULE CONNECTIONS 3 NETWORK MODULE INSTALLATION 3 EXAMPLES OF NETWORK CONNECTION 6 IP ADDRESS CHANGING 7 MODBUS ADDRESS CHANGING 10 ...

Страница 3: ...additionally except units with C2 controller For this case user need to have installation kit 1 Network module Ping 2 Additional connection cable 5 m 3 CD with software and manuals NETWORK MODULE CONNECTIONS NETWORK MODULE INSTALLATION 1 Network module can be installed provided place under given following conditions ambient temperature range 0 C 40 C relative humidity limits 20 80 protection must ...

Страница 4: ...n provided place control panel needed to be disconnected from air handling unit 3 Disconnected from the panel cable connect to the Ping module J1 socket 4 Connect one end of the cable from installation kit to the panel and another end to J2 socket of Ping module ...

Страница 5: ...6 For connection of air handling unit to the another MODBUS RTU based network is provided RS485 serial interface MODBUS network line is connected to J3 socket of Ping module J3 socket type PHOENIX CONTACT MC 1 5 3 ST 3 5 PLUG FREE 3 5MM 3WAY Note In one serial line of RS 485 network may be connected not more as 30 Ping modules ...

Страница 6: ...Network module manual 6 EXAMPLES OF NETWORK CONNECTION Picture 1 Connection through Ethernet network Picture 2 Connection through RS485 line ...

Страница 7: ...twork addresses if standard does not fit by connection through Ethernet or J3 socket using standard USB RS485 adapter Network addresses changing sequence is described below 1 After software is installed from included CD run in you computer the Ping Manager program 2 In left side of Ping Manager program is selected connection type 1 For Ethernet connection needed to enter default IP address 2 if Se...

Страница 8: ...s that connection between computer and network module is enabled There is possibility to see programmed network addresses by pressing Read button 6 4 Programmed network addresses are displayed in Static Configuration and Current Configuration columns 6 5 ...

Страница 9: ...uld be written a new IP address 213 226 94 133 in Gate cell new gateway address 213 226 94 1 in Subnet cell subnet mask address 255 255 255 0 To save a new addresses first must be pressed Write 7 and then Set Static Configuration 8 button 6 Restart connection 9 and by pressing Read button 10 a new network addresses will be shown in Static Configuration and Current Configuration columns 7 8 10 9 ...

Страница 10: ...Manager program must be inserted retranslating address 11 push the Write button 12 and after few seconds push Set Static Configuration 13 Note If Ping module should retranslate only one address write the same address in the program Min Address and Max Address windows example 20 If to the serial connection of Ping module is connected more that one unit then is needed to write interval of retranslat...