Under conditions, when the outdoor air temperature is low and humidity is high, risk of heat exchanger 

frosting may appear. For this reason anti-frost protection function is foreseen in the controller of the Kom

-

fovent air handling units. Depending on the type of the air handling unit, different methods of anti-frost 

protection are available: cold air by-passing, supply air fan speed reducing and/or integrated preheater. 

Counter cross flow heat exchanger is the mostly sensitive for low outside air temperatures, as the risk of 

frosting appears in the temperature range from 0 to -5 °C and below. Standard aluminium cross-flow plate 

heat exchanger has better features, as the risk of freezing appears only at -10 °C. The lowest risk and the 

highest resistance to cold outside air is a competitive feature of the rotary heat exchanger, as it is not freez-

ing even at the temperatures of -30 °C if the humidity level of the air is appropriate.

In the units with counter flow or cross flow plate exchangers without inte

-

grated preheater, it is necessary to install additional duct mounted pre-

heater in the outside air intake duct, which will ensure temperature of the 

intake air higher than -4 °C.

• 

Selecting the management without pre-heater, but with cold air bypass the unit must be additionally 

equipped with a secondary duct mounted heater.

If the unit is mounted in premises with high humidity, condensation might occur on the surface of the unit 

when outdoor temperatures are low (see picture 3). When installing unit in such a premises, it is necessary 

to take additional measures, to avoid condensate damage to the building construction elements or furniture.

Relative humidity of the premises where the unit is mounted, %

80

75

70

65

60

55

50

45

40

35

30

25

20

12 14 16 18  20 22 24 26 28 30  32

Air temperature of the premises where the unit is mounted, °C

Outdoor air temperature, °C

10

5

0

-5

-10

-15
-20

-25

3 picture. Condensation on unit surface diagram

Содержание Domekt CF 250 F

Страница 1: ...DOMEKT EN Installation and service Manual ...

Страница 2: ......

Страница 3: ...lly associated with EEE At the same time your cooperation in the correct disposal of this product will contribute to the effective usage of natural resources For more information about where you can drop off your waste equipment for recycling please contact your local city office waste authority approved WEEE scheme or your household waste disposal service Content 1 SAFETY REQUIREMENTS 4 2 TRANSPO...

Страница 4: ...ing the unit check correct position of air filters Service maintenance should be carried out only in conformity with the instructions specified herein below If main cable is damaged only manufacturer service team or trained technician must change it in order to avoid accidents Drilling and using self tapping screws on the unit casing is prohibited where it is not provided by the construction since...

Страница 5: ... ambient temperature and relative humidity The unit is intended to be installed in the domestic or non residential premises Mineral wool is used for thermal insulation and sound attenuation Units cover panels are 25 50 mm thick As standard the unit is designed for indoor placement In cold wet rooms possible icing or condensation on the housing inside and outside The operating temperature range for...

Страница 6: ...nger as it is not freez ing even at the temperatures of 30 C if the humidity level of the air is appropriate In the units with counter flow or cross flow plate exchangers without inte grated preheater it is necessary to install additional duct mounted pre heater in the outside air intake duct which will ensure temperature of the intake air higher than 4 C Selecting the management without pre heate...

Страница 7: ... 2 Preheater should be installed to increase the supply air temperature It is recommended to keep air handling unit constantly running and in cases when ventilation is not necessary switch it to the minimum inten sity 20 In that way good indoor climate will be maintained and con densation inside of the unit will decrease avoiding humidity damage to electronic components Example No 1 Temperature of...

Страница 8: ...ce D_20 07 8 Air Handling Units Schemes 6 3 4 5 7 1 2 DOMEKT R 400 V DOMEKT R 450 V 5 2 7 4 3 6 1 B A C E D E DOMEKT R 190V 200V 6 3 1 5 4 C B A E D DOMEKT R 300 V D A C B 3 4 1 5 6 DOMEKT R 400 H E D A C B 3 4 1 5 6 2 DOMEKT R 250 F C6 C B A D E 6 3 1 5 4 2 DOMEKT R 400 F ...

Страница 9: ...erve the right to make changes without prior notice D_20 07 9 E D A C B 6 3 1 5 4 2 DOMEKT R 700 H D A E C B 6 3 1 4 5 2 DOMEKT R 600 H B E A D C 2 5 4 3 6 1 DOMEKT R 500 V DOMEKT R 700 V C B D A 2 6 1 3 5 4 DOMEKT R 700 F ...

Страница 10: ...ve the right to make changes without prior notice D_20 07 10 A D C B 3 6 2 1 DOMEKT CF 400 V C D 4 3 1 5 6 8 B E A 2 7 B C E D A DOMEKT PP 300 V 450 V 6 3 1 7 5 4 8 D A B C DOMEKT CF 250 V D A B C 1 2 6 3 5 4 2 DOMEKT CF 250 F ...

Страница 11: ... C B 6 2 3 4 5 2 DOMEKT CF 700 V 3 5 2 A B DOMEKT S 650 F 800 F 1000 F A Outdoor intake B Supply air C Extract indoor D Exhaust air E E Kitchen hood connection by pass extraction without heat recovery 1 Rotary or plate heat exchanger 2 Electric or water air heater 3 Supply air filter 4 Exhaust air filter 5 Supply fan 6 Exhaust fan 7 Air by pass damper 8 Condensate drain the water trap must be inst...

Страница 12: ...g The place for the unit must be selected with allowance for minimum access to the unit for maintenance or service and must comply with safety requirements Opening for inspection can not be smaller than dimensions of the unit and unit itself must be mounted in a way that if needed for example in case of complicated repair it can be easily dismounted Minimum Maintenance Space for Horizontal Units 1...

Страница 13: ...eserve the right to make changes without prior notice D_20 07 13 B ceiling A min 100 mm 5 B 1 Inspec tion trapdoor 2 2 3 5 a Picture 2 2 1 3 5 A A D C B B 5 b Picture Only F type units Only R 250F R 400 F and 700 F units ...

Страница 14: ...right to make changes without prior notice D_20 07 14 DOMEKT R 400 V Unit brackets positions B A 641 604 57 662 30 300 600 30 Ø125 Ø160 6 Picture DOMEKT R 450 V Unit brackets positions Ø125 Ø160 A 57 667 704 B 30 340 30 680 7 Picture ...

Страница 15: ...notice D_20 07 15 DOMEKT CF 250 V Unit brackets positions view 1 35 260 520 590 595 20 B A 510 700 824 795 8 Picture DOMEKT CF 250F CF 500F CF 700F Units brackets positions 15 9 Picture DOMEKT CF 400 V Unit brackets positions 520 750 838 867 598 600 260 39 10 Picture ...

Страница 16: ...ed with heating cable A condensate pipe and a drain trap Drain scheme of Vertical Unit view 1 D 15 12 a Picture Drain scheme of Horizontal Unit view 2 D 15 view 2 12 b Picture The bend of the water trap can be repositioned by turning it to the right or the left The drain line from the water trap must be arranged so that it will not damage adjacent unit sections or building elements If the drain li...

Страница 17: ...r complete condensate drainage from the air handling unit and prevention of penetration of offensive odours from an effluent into the ventilation system In case of the outdoor operation of the air handling unit the siphon and the bleeders should be heated with an electric thermal cable if ambient air temperature tamb 0 C The siphon and the bleeders should be heat insulated with an insulating mater...

Страница 18: ...SUP SUP Supply air duct connection DOMEKT R 190V 200V Unit hanging scheme without kitchen hood 1 2 3 4 5 8 9 8 5 6 7 SUP SUP 1 Air handling unit DOMEKT R 190V 200V 2 Wall plug 8 50 screw 4 5 50 3 Wall mounting bracket 4 Self tapping screw 4 2 13 5 Unit bracket 6 Bottom bracket 7 Screw M4x16 DIN 7895 8 Bracket for decorative panel 9 Screw 2 5 16 with cone head ...

Страница 19: ... 1 Air handling unit DOMEKT R 190V 200V 2 Kitchen hood adapter 392 12 3 Kitchen hood 392 12 4 Standard kitchen hood 5 Wall plug 8 50 screw 4 5 50 6 Wall mounting bracket 7 Unit bracket 8 Self tapping screw 4 2 13 9 Bracket for decorative panel 10 Screw 2 5 16 with cone head Dimensions for mounting furniture panel 22 625 600 500 250 22 32 5 500 250 32 5 Ø 2 d e p t h 5 m m 1 6 h o l e s 13 Picture ...

Страница 20: ...ling kitchen hood bottom cover plate must be removed by remooving fixing screws 14a pic 14b Picture Installation of standard kitchen hood 14c Picture Installation of kitchen hood 392 12 1 Kitchen hood adapter 392 12 2 Standard kitchen hood 3 Kitchen hood 392 12 4 Screws M4 for hood fixation 4 picture 5 Self tapping screws 4 2 13 for adapter fixation 10 picture 5 10 4 4 4 4 3 2 1 ...

Страница 21: ...prior notice D_20 07 21 Dimensions for the DOMEKT R 190V 200V installation space 804 42 325 625 777 500 140 140 4 560 575 600 15 Picture Dimensions with standard kitchen hood 16 Picture Dimensions with kitchen hood 392 12 325 42 738 94 625 140 4 560 140 25 600 ...

Страница 22: ..._20 07 22 DOMEKT PP 300 V DOMEKT PP 450 V Unit brackets positions 7 view 1 2 3 5 6 9 4 2 8 7 35 330 35 730 740 765 790 653 6 B A 17 Picture 1 Screw 2 Wall plug 3 Hanging bracket 1 4 Hanging bracket 2 5 Bolt M5 6 Gasket 7 Self tapping screw 8 L shape bracket 9 Washer M5 DIN9021 ...

Страница 23: ...C 4 8 3 2 1 1 2 6 5 7 C 18 Picture When closing unit doors fixing nuts 7 should be easily tightened by hand Do not over tighten since it will damage the doors or casing of the unit 1 Wall plug 8 50 2 Screw 4 5 50 3 Upper bracket 4 Fixing bolt M5 30 5 Self tapping screw 4 2 13 6 Lower bracket 7 Door fixing nut 8 Self tapping screw 4 2 13 optional ...

Страница 24: ...cling centre or the like Glycol is highly dangerous to consume and can cause fatal poisoning or damage the kidneys Contact a doctor Avoid breathing glycol vapour in confined spaces If you get glycol in your eyes fush them thoroughly with water for about 5 minutes When operating air handling unit in the temperatures lower than 0 C it is necessary to use glycol additionally or assure the reversible ...

Страница 25: ...ry heat exchanger continuity of the rotating belt absence of damages of the rotor drums and the seal gasket are checked It is necessary to check the stretch of belt Free belt will slide and the efficiency of rotary heat exchanger will fall down To reach maximal efficiency rotor must turn at least 8 times per minute Polluted heat exchanger will decrease efficiency Clean heat exchanger with an air b...

Страница 26: ...heck Change air filters when air filter clogging is indicated We recommend changing filters at least twice per year before and after heating season or more1 Filters are one time used We do not recommend cleaning them Stop the air handling unit before changing filters Pressure sensor 20 Picture 7 Pressure sensor setting which indicates impurity of filters Pressure sensor is set according to EN 1377...

Страница 27: ...1 6 2 0 2 180 4 250 1 125 700 F 424 1272 1240 854 80 1 230 11 6 2 0 2 176 4 250 DOMEKT P 300 V 345 740 725 700 42 1 230 5 5 1 0 2 67 5 125 450 V 345 740 725 700 42 1 230 6 7 1 0 2 167 5 125 DOMEKT CF C6 250 F 294 1282 1250 604 43 1 230 8 3 1 5 2 89 4x160 400V 600 600 765 750 55 1 230 10 5 2 0 2 91 4x160 500F 295 1430 1400 1045 70 1 230 11 6 2 0 2 171 4x200 700H 497 1533 1500 700 95 1 230 12 0 2 0 ...

Страница 28: ...0 F 145 145 145 145 165 225 165 225 400 H 267 157 267 157 183 153 153 183 450 V 130 255 130 255 110 0 0 110 700 H 402 257 257 402 198 198 198 198 500 V 700 V 229 186 229 186 190 228 228 190 600 H 375 285 375 285 170 120 170 120 700 F 202 202 202 202 202 218 202 218 DOMEKT P 300V 100 140 100 140 85 180 185 110 450 V 100 140 100 140 85 180 185 110 DOMEKT CF C6 250 F 128 128 128 128 162 192 162 142 4...

Страница 29: ...260 46 46 600 H KF5 KF7 475 235 46 46 700 V H KF5 KF7 540 260 46 46 700 F KF5 KF7 370 360 46 46 DOMEKT P 300 V KF5 KF7 300 200 46 46 450 V KF5 KF7 300 200 46 46 DOMEKT CF 250 F KF5 KF7 265 250 46 46 400 V KF5 KF7 235 350 46 46 500 F KF5 KF7 484 250 46 46 700 V H KF5 KF7 390 300 46 46 700 F KF5 KF7 400 300 46 46 DOMEKT S 650 F KF5 KF7 235 371 46 800 F KF5 KF7 287 371 46 1000 F KF5 KF7 558 287 46 Su...

Страница 30: ......

Страница 31: ......

Страница 32: ... iela 1 LV 1004 Riga Tel 371 24 664433 info komfovent lv www komfovent lv www komfovent com PARTNERS AT J PICHLER Gesellschaft m b H www pichlerluft at BE Ventilair group www ventilairgroup com ACB Airconditioning www acbairco be CZ REKUVENT s r o www rekuvent cz CH WESCO AG www wesco ch SUDCLIMATAIR SA www sudclimatair ch CLIMAIR GmbH www climair ch CH LI Trivent AG www trivent com DK Øland A S w...

Отзывы: