The function of step rotation is provided, when capacities of coolers are 

the same.

The number of direct evaporation cooling units must be provided in ad-

vance.

2.7.4. Reversal of direct evaporation coolers

There is a reverse option of direct evaporation coolers, i.e. when the cooler is switched to the heating mode. In 

such case, there must be only max 3 cooling control steps. There are control terminals DX3 for connection of 

the cooler reversing signal “Heating” (Pic. 1.3 b.).

The option of reversal of direct evaporation cooling units must be pro-

vided in advance.

2.8. Troubleshooting

If the unit fails to operate:

•  Make sure that the unit is connected to the power supply network.

•  Check whether the main switch (if designed) is turned on.

•  Check all fuses of the automatics. If necessary, replace blown-out fuses with new ones having the same 

electrical parameters (the sizes of the fuses are indicated on the schematic electrical diagram).

•  Check whether there is any failure message on the control panel. If there is indication, it needs to be elimi-

nated first. In order to eliminate the failure, follow the table.

•  If nothing is indicated on the control panel, check whether cable connecting control panel with the unit is 

not damaged.

2.8 Table. Alarms indicated on the control panel, their possible causes and elimination methods

Code

Message

Possible cause

Elimination

14B

Service time

If unit continuous operation (without 

breaks) was 12 months, then periodic 

inspection message appears.

After disconnecting the unit from power 

supply, it is necessary to carry out peri-

odic inspection of the unit, i.e. to check 

the condition of the heat exchanger, 

the heater and fans.

1B, 19A

Low supply air flow

Too high resistance of the ventilation 

system.

Check pressure pipes, air dampers, air 

filters and make sure that the ventila

-

tion system is not blocked.

2B, 20A

Low extract air flow

Too high resistance of the ventilation 

system.

Check pressure pipes, air dampers, air 

filters and make sure that the ventilation 

system is not blocked.

3B

VAV calibration fail

Pressure sensors are not connected 

or broken.

Check connections of the sensor or 

replace the sensor.

4B

Change outdoor air filter The fresh air filter is blocked.

Shut down the unit and replace the 

filter.

5B

Change extract air filter

The extract air filter is blocked.

Shut down the unit and replace the 

filter.

6B-11B

Electric heater off

The heater is disconnected due to too 

low air volume.

As soon as the heater cools down, 

protection resets automatically. It is 

recommended to increase the ventila-

tion intensity level.

113B,114B

CF exchanger not 

calibrated

CF exchanger calibration not perfor

-

med or failed

Make sure that all doors are closed, 

there is no obstructions in the ducts 

and AHU can reached airflow setpoint 

of COMFORT 1 mode. Repeat cali

-

bration manually (see 2.5.1.3.).

127B

Service mode

Temporary mode, which can be acti-

vated by the service personnel.

The service mode is switched off by 

simply deleting the alert message.

Содержание C5

Страница 1: ...C5 1 EN Electrical installation and Operation Manual ...

Страница 2: ...s Sections Connection 3 1 2 Electric Power Supply Connection 3 1 3 External Elements Connection 4 1 4 Temperature Sensors Installation 5 1 5 Requirements for the installation of the control panel 5 1 6 Control panel connection 5 2 OPERATION MANUAL 6 2 1 Unit Control 6 2 2 Control panel indication 6 2 3 Parameters overview 7 2 4 Operation modes selection 7 2 5 Menu 8 2 5 1 Overview 8 2 5 1 1 Alarms...

Страница 3: ...or connection is performed strictly according to numeration giv en in wiring diagram or adequate markings see unit electric scheme When disconnecting unit sections do not pull by connecting wires and cables 1 2 Electric Power Supply Connection If the air handling unit voltage is 230 V 50 Hz it is necessary to install the socket with grounding of correspond ing capacity see electric diagram unit If...

Страница 4: ... 10V 0 10V NO NO NO NO NO C C FG1 DX Indication control Cold water Hot water Cooling water Heating water pump 230V AC 1A pump 230V AC 1A mixing valve mixing valve actuator actuator Humidifier Run Alarm Common Common Cooling control TG3 TG2 TG1 S1 S2 IN5 L L N N N N N 23 24 25 26 27 28 29 30 31 32 33 34 35 36 24V 24V 24V 24V 0 10V 0 10V 0 10V 0 10V C NTC B5 B9 B8 B7 B6 MODBUS RS485 connection OVR c...

Страница 5: ...here the following conditions are ensured 1 1 ambient temperature 0 ºC 40 ºC 1 2 relative humidity range 20 80 1 3 protection against dripping of water IP X0 2 Control panel connection is provided through a hole in the back or bottom side 3 The panel can be mounted on a flush mounting box or in any other place just screwing two holes on the fastening surface Do not use any other type or size screw...

Страница 6: ... air humidity Extract air humidity Extract room air quality Explanation of the displayed symbols 2 OPERATION MANUAL 2 1 Unit Control Air handling units control system ensures control of the physical pro cesses that are taking place inside the air handling unit Control system consists of main controller module circuit breakers and main switch control panel which can be installed in the convenient p...

Страница 7: ...OMY 1 21 9 C 21 3 C Temperature 16 30 ECONOMY 1 21 9 C 21 3 C Temperature 16 30 2 4 Operation modes selection Six operation modes are possible one of them user can select directly from control panel main window Two Comfort and two Economy modes for each of them the user can set air flow and temperature Special mode allows the user not only to set air flow and temperature but also to select blockin...

Страница 8: ...cy and energy recovery monitoring in real time Also in this menu it is possible to start CF ex changer calibration if it was not performed during first start of AHU If calibration was successful and Calibrated is shown there is no need to start cali bration again During calibration AHU will operate for about 10 minutes on different ventilation intensities while measuring internal pressure Thus do ...

Страница 9: ...ue Ventilation intensity will be increased automatically in the case of deviation from the set value and decreased again when it is approached For example if the unit is designed with the CO2 maintenance function and is equipped with a CO2 sensor after setting value 800 ppm this set CO2 level will be maintained by adjusting ventilation intensity i e ventilation intensity will be increased if the C...

Страница 10: ...ling function can start at night from 00 00 h to 06 00 h a m at any time even when the air handling unit is not working and is in standby mode User can set indoor temperature at which this function starts and stops When this function is active the current ventilation level is switched to the maximum ventilation intensity 100 and ventilation is performed only by means of fans i e at that time neith...

Страница 11: ...capacity of the humidifier from 0 to 100 If humidification is required the control is transferred through the output TG3 of the controller Dehumidification of air There is a control signal of 0 10 V directly reflecting the capacity of the dehu midifier from 0 to 100 If dehumidification is required the control is transferred through the output TG3 of the controller Dehumidification of air cooling h...

Страница 12: ...peration day of the week and the time interval 2 5 3 2 Holidays Holiday schedule specifies the time period during which the unit operates under selected mode Pos sible to set up to ten holidays Program 2 Operation mode COMFORT 1 Weekdays Mo Tu We Th Fr Sa Su Start time 00 00 Stop time 24 00 Delete program Holidays 2 Operation mode STANDBY From 12 14 Till 12 26 Delete holiday Holidays Holidays 1 Ad...

Страница 13: ...em according to which control is performed while the other air flow in this case discharged air operates as the slave ventilation system and always follows the master one If the supply air requirement in the ventilation system which is assigned as the master system decreases the intensity of discharged air in the slave system is reduced correspondingly by the same percentage If the variable air vo...

Страница 14: ...rk cable Standard CAT 5 network cable Time Date Time and date is required for air handling unit operation planning Also it is possible to activate automatic daylight saving time Enable Daylight saving time Time Date Time 09 40 Day Month 25 05 Year 2019 Daylight saving time On Connectivity IP address and subnet mask Setting is required when air handling unit is connected to PC network or Internet C...

Страница 15: ...ting circuit and operates only under the heating mode by default However upon transfer of the feedback signal confirming that there is cold water within the circulation system to the control ter minals IN4 of the external control e g by connecting additional device thermostat switch etc the air cool ing function will be activated and the mixing valve actuator TG1 will be controlled under the air c...

Страница 16: ...e cause Elimination 14B Service time If unit continuous operation without breaks was 12 months then periodic inspection message appears After disconnecting the unit from power supply it is necessary to carry out peri odic inspection of the unit i e to check the condition of the heat exchanger the heater and fans 1B 19A Low supply air flow Too high resistance of the ventilation system Check pressur...

Страница 17: ...ate in the previous mode 15A Heat exchanger failure Blocked or not rotating rotor by pass damper failure Check the rotor drive replace the belt or check the by pass channel operation 16A Heat exchanger icing Icing may form under a low outdoor temperature and high room humidity Check the operation of the rotation heat exchanger drive or the air bypass damper of the plate heat exchanger 17A Low supp...

Страница 18: ... fault signal has been received from exhaust fan drive Check the exhaust fan drive and its messages 105A Exhaust fan drive overload The exhaust fan drive is overloaded Check the condition of the exhaust fan drive and its cooling 106A Exhaust fan motor failure The exhaust fan is broken Check the exhaust fan and replace it if necessary 107A 108A Exhaust fan motor overload The exhaust fan is overload...

Страница 19: ...s shut down and a failure text message is shown on the control panel the fault must be eliminated Before performing any jobs inside the unit make sure that the unit is stopped and disconnected from the electrical power supply After failure has been eliminated and power supply connected the error messages should be deleted How ever if the failure has not been eliminated unit either starts operating...

Страница 20: ...išu iela 1 LV 1004 Riga Tel 371 24 664433 info komfovent lv www komfovent lv www komfovent com PARTNERS AT J PICHLER Gesellschaft m b H www pichlerluft at BE Ventilair group www ventilairgroup com ACB Airconditioning www acbairco be CZ REKUVENT s r o www rekuvent cz CH WESCO AG www wesco ch SUDCLIMATAIR SA www sudclimatair ch CLIMAIR GmbH www climair ch DK Øland A S www oeland dk EE BVT Partners w...

Отзывы: