How to connect the unit directly to your computer:

1.  Plug one end of the network cable into the controller port on the unit (see Picture 1.3 a) and the other end 

to the computer.

2.  Go to the properties of your network card and enter IP address, e.g. 192.168.0.200, and subnet mask 

255.255.0.0.

3.  Open the web browser on your computer and disable all proxy servers in the settings. 

4.  In the address bar of your web browser enter the IP address associated with the air handling unit; the default 

IP address is 192.168.0.50. You can change it at any time on the control panel or from web browser (see 

connection settings).

Note: 

It is recommended to download the latest version of your web browser before use.

5.  If the connection is successful, a window prompting to enter your user name and password appears:

Note:

 the user name is 

“user”

. The default password is also 

“user”

; after logging in, the user can later change 

the password to any other of his/her choice (see user interface settings).

If the user has forgotten the modified password, it can be set to the de

-

fault. To do this, user should to restore the factory settings of the air 

handling unit.

2.7. Additional control options

2.7.1. Combined water coil control

For the air handling unit with the combined water coil (Combi-coil – heater and cooler in one) the control of the 

mixing valve actuator is provided both under the air heating and cooling modes. The actuator is connected to 

the control terminals of the heating circuit and operates only under the heating mode by default. However upon 

transfer of the feedback signal confirming that there is cold water within the circulation system to the control ter

-

minals (IN4) of the external control (e. g., by connecting additional device: thermostat, switch, etc.), the air cool-

ing function will be activated, and the mixing valve actuator (TG1) will be controlled under the air cooling mode.

2.7.2. Inverter direct evaporation cooler control

By default all units are provided with inverter type DX cooler control, which allows stepless control of the com-

pressor. For the inverter unit power control, there is a modulated signal (TG2), as well as signals: cooler start 

(DX1), cooling demand DX2, heating demand DX3 (see Pic. 1.3 b).

There are three different control methods: 

1.  Universal control, suitable for most cooler units

1

.

2.  Control adapted to Panasonic cooler units.

3  Control adapted to Daikin cooler units.

2.7.3. Multi-level control of direct evaporation cooler

For air cooling in the air handling unit there is provided 3 control contacts (connection is shown in Picture 1.3 b). 

Depending on how much will be cooling steps and how it will be divided on steps, it is recommended to select 

theoptimal control method. If the capacity of all steps is the same, then only three control steps are possible. 

If cooling capacities of steps are close to ratio 1-2-4 (the capacity of each of the following steps is double the 

previous), then cooler control will be realized with seven cooling steps.

Example: To the terminals DX1 is connected 1kW cooler, to DX2 – 2kW and to terminals DX3 connected 

cooler with 4kW capacity. Control will be in steps:

1: 1 kW; 2: 2 kW; 3: 1 kW + 2 kW; 4: 4 kW; 5: 1 kW + 4 kW; 6: 2 kW + 4 kW; 7: 1 kW + 2 kW + 4 kW.

Factory setting.

Содержание C5

Страница 1: ...C5 1 EN Electrical installation and Operation Manual ...

Страница 2: ...s Sections Connection 3 1 2 Electric Power Supply Connection 3 1 3 External Elements Connection 4 1 4 Temperature Sensors Installation 5 1 5 Requirements for the installation of the control panel 5 1 6 Control panel connection 5 2 OPERATION MANUAL 6 2 1 Unit Control 6 2 2 Control panel indication 6 2 3 Parameters overview 7 2 4 Operation modes selection 7 2 5 Menu 8 2 5 1 Overview 8 2 5 1 1 Alarms...

Страница 3: ...or connection is performed strictly according to numeration giv en in wiring diagram or adequate markings see unit electric scheme When disconnecting unit sections do not pull by connecting wires and cables 1 2 Electric Power Supply Connection If the air handling unit voltage is 230 V 50 Hz it is necessary to install the socket with grounding of correspond ing capacity see electric diagram unit If...

Страница 4: ... 10V 0 10V NO NO NO NO NO C C FG1 DX Indication control Cold water Hot water Cooling water Heating water pump 230V AC 1A pump 230V AC 1A mixing valve mixing valve actuator actuator Humidifier Run Alarm Common Common Cooling control TG3 TG2 TG1 S1 S2 IN5 L L N N N N N 23 24 25 26 27 28 29 30 31 32 33 34 35 36 24V 24V 24V 24V 0 10V 0 10V 0 10V 0 10V C NTC B5 B9 B8 B7 B6 MODBUS RS485 connection OVR c...

Страница 5: ...here the following conditions are ensured 1 1 ambient temperature 0 ºC 40 ºC 1 2 relative humidity range 20 80 1 3 protection against dripping of water IP X0 2 Control panel connection is provided through a hole in the back or bottom side 3 The panel can be mounted on a flush mounting box or in any other place just screwing two holes on the fastening surface Do not use any other type or size screw...

Страница 6: ... air humidity Extract air humidity Extract room air quality Explanation of the displayed symbols 2 OPERATION MANUAL 2 1 Unit Control Air handling units control system ensures control of the physical pro cesses that are taking place inside the air handling unit Control system consists of main controller module circuit breakers and main switch control panel which can be installed in the convenient p...

Страница 7: ...OMY 1 21 9 C 21 3 C Temperature 16 30 ECONOMY 1 21 9 C 21 3 C Temperature 16 30 2 4 Operation modes selection Six operation modes are possible one of them user can select directly from control panel main window Two Comfort and two Economy modes for each of them the user can set air flow and temperature Special mode allows the user not only to set air flow and temperature but also to select blockin...

Страница 8: ...cy and energy recovery monitoring in real time Also in this menu it is possible to start CF ex changer calibration if it was not performed during first start of AHU If calibration was successful and Calibrated is shown there is no need to start cali bration again During calibration AHU will operate for about 10 minutes on different ventilation intensities while measuring internal pressure Thus do ...

Страница 9: ...ue Ventilation intensity will be increased automatically in the case of deviation from the set value and decreased again when it is approached For example if the unit is designed with the CO2 maintenance function and is equipped with a CO2 sensor after setting value 800 ppm this set CO2 level will be maintained by adjusting ventilation intensity i e ventilation intensity will be increased if the C...

Страница 10: ...ling function can start at night from 00 00 h to 06 00 h a m at any time even when the air handling unit is not working and is in standby mode User can set indoor temperature at which this function starts and stops When this function is active the current ventilation level is switched to the maximum ventilation intensity 100 and ventilation is performed only by means of fans i e at that time neith...

Страница 11: ...capacity of the humidifier from 0 to 100 If humidification is required the control is transferred through the output TG3 of the controller Dehumidification of air There is a control signal of 0 10 V directly reflecting the capacity of the dehu midifier from 0 to 100 If dehumidification is required the control is transferred through the output TG3 of the controller Dehumidification of air cooling h...

Страница 12: ...peration day of the week and the time interval 2 5 3 2 Holidays Holiday schedule specifies the time period during which the unit operates under selected mode Pos sible to set up to ten holidays Program 2 Operation mode COMFORT 1 Weekdays Mo Tu We Th Fr Sa Su Start time 00 00 Stop time 24 00 Delete program Holidays 2 Operation mode STANDBY From 12 14 Till 12 26 Delete holiday Holidays Holidays 1 Ad...

Страница 13: ...em according to which control is performed while the other air flow in this case discharged air operates as the slave ventilation system and always follows the master one If the supply air requirement in the ventilation system which is assigned as the master system decreases the intensity of discharged air in the slave system is reduced correspondingly by the same percentage If the variable air vo...

Страница 14: ...rk cable Standard CAT 5 network cable Time Date Time and date is required for air handling unit operation planning Also it is possible to activate automatic daylight saving time Enable Daylight saving time Time Date Time 09 40 Day Month 25 05 Year 2019 Daylight saving time On Connectivity IP address and subnet mask Setting is required when air handling unit is connected to PC network or Internet C...

Страница 15: ...ting circuit and operates only under the heating mode by default However upon transfer of the feedback signal confirming that there is cold water within the circulation system to the control ter minals IN4 of the external control e g by connecting additional device thermostat switch etc the air cool ing function will be activated and the mixing valve actuator TG1 will be controlled under the air c...

Страница 16: ...e cause Elimination 14B Service time If unit continuous operation without breaks was 12 months then periodic inspection message appears After disconnecting the unit from power supply it is necessary to carry out peri odic inspection of the unit i e to check the condition of the heat exchanger the heater and fans 1B 19A Low supply air flow Too high resistance of the ventilation system Check pressur...

Страница 17: ...ate in the previous mode 15A Heat exchanger failure Blocked or not rotating rotor by pass damper failure Check the rotor drive replace the belt or check the by pass channel operation 16A Heat exchanger icing Icing may form under a low outdoor temperature and high room humidity Check the operation of the rotation heat exchanger drive or the air bypass damper of the plate heat exchanger 17A Low supp...

Страница 18: ... fault signal has been received from exhaust fan drive Check the exhaust fan drive and its messages 105A Exhaust fan drive overload The exhaust fan drive is overloaded Check the condition of the exhaust fan drive and its cooling 106A Exhaust fan motor failure The exhaust fan is broken Check the exhaust fan and replace it if necessary 107A 108A Exhaust fan motor overload The exhaust fan is overload...

Страница 19: ...s shut down and a failure text message is shown on the control panel the fault must be eliminated Before performing any jobs inside the unit make sure that the unit is stopped and disconnected from the electrical power supply After failure has been eliminated and power supply connected the error messages should be deleted How ever if the failure has not been eliminated unit either starts operating...

Страница 20: ...išu iela 1 LV 1004 Riga Tel 371 24 664433 info komfovent lv www komfovent lv www komfovent com PARTNERS AT J PICHLER Gesellschaft m b H www pichlerluft at BE Ventilair group www ventilairgroup com ACB Airconditioning www acbairco be CZ REKUVENT s r o www rekuvent cz CH WESCO AG www wesco ch SUDCLIMATAIR SA www sudclimatair ch CLIMAIR GmbH www climair ch DK Øland A S www oeland dk EE BVT Partners w...

Отзывы: